background image

4

FR

ONT VIEW

REAR VIEW

T

OP VIEW

RIGHT 

S

IDE

LEFT 

S

IDE

C

D

M

M

L

BO

TT

OM VIEW

1-1/2

2-

3

/4

3

8

K

B

A

G

E

F

I

H

a40-1847

1-

3

/8

Fi

g.

 2

 —

 40

WA

D0

07

-0

24

 D

ime

ns

io

n

s

NOTE: 

Al

d

imension

s

 shown in inche

s

.

4

0WAD 

UNI

T SIZE

DIMENSION (in

.)

AB

C

D

E

F

G

H

I

J

K

L

M

00

7-01

2

27

 

1

/

2

1

/

4

19 

3

/

4

17

 

3

/

4

30 

3

/

4

1

/

4

20

 

1

/

8

5

/

8

3

/

4

23 

5

/

8

3

/

4

29

 

1

/

8

13

 

3

/

4

015

,0

18

36

 

1

/

4

39 

1

/

4

28

 

3

/

4

32 

1

/

4

7

/

8

37

 

3

/

4

024

44

 

7

/

8

48

37 

7

/

16

41

7

/

8

46

 

1

/

2

Summary of Contents for 40WAD007

Page 1: ...rds DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death...

Page 2: ...ze Figure 2 shows unit dimen sions See Fig 3 for fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regul...

Page 3: ...wg 0 04 to 0 20 INDOOR NOISE LEVEL dBA Low 31 31 33 33 34 Medium 34 34 36 37 38 High 35 36 37 38 40 UNIT Unit Dimensions W x H x D in 27 1 2 x 8 1 4 x 19 3 4 36 1 4 x 8 1 4 x 19 3 4 44 7 8 x 8 1 4 x...

Page 4: ...1847 1 3 8 Fig 2 40WAD007 024 Dimensions NOTE All dimensions shown in inches 40WAD UNIT SIZE DIMENSION in A B C D E F G H I J K L M 007 012 27 1 2 8 1 4 19 3 4 17 3 4 30 3 4 1 1 4 20 1 8 5 8 5 3 4 23...

Page 5: ...erial on the motor or blower wheels will not be covered by the manufacturer s war ranty Some units and or job conditions may require some form of temporary covering during construction PREPARING JOBSI...

Page 6: ...for the drain 3 Secure the unit in position with locknuts and washers on both sides of the mounting bracket Ensure that the threaded rod does not protrude more than 2 in below the mounting brackets as...

Page 7: ...ring must comply with CSA C22 1 Electrical Code This equipment in its standard form is designed for an elec trical supply of 208 230 1 60 Any damage to or failure of units caused by incorrect wiring o...

Page 8: ...r electrical devices WIRED REMOTE CONTROLLER PROGRAMMA BLE To connect a programmable wired remote controller thermostat to the indoor unit use 4 core shielded cable and 4 pin connector from electrical...

Page 9: ...nd liquid line service valves are in open posi tion Drain Pump and Drainage Test Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 12 2 Us...

Page 10: ...addition Be sure all electrical connections are secure Check condensate pump operation if applicable Check the heating and cooling action to confirm proper operation TROUBLESHOOTING Figure 14 shows t...

Page 11: ...are short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance th...

Page 12: ...2 a40 1932 Fig B SW2 Settings POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON O...

Reviews: