background image

7

• Condensate piping should slope downward in the direc-

tion of condensate flow, with a minimum gradient of

1 in. per 100 inches.

• When multiple units are connected to a common conden-

sate drain, ensure that the drain is large enough to accom-

modate the volume of condensate from all units. It is also

recommended to have an air vent in the condensate pip-

ing to prevent air lock.

• Condensate piping must not be installed where it may be

exposed to freezing temperatures.

REFRIGERANT PIPING

When connecting from an indoor unit to an outdoor unit,

follow these procedures:
• Check maximum height drop and length of refrigerant

piping between the indoor and outdoor units. If the dif-

ference between them is more than is 33 ft, consider

mounting the outdoor unit above the indoor unit.

• The number of bends in the refrigeration piping must be

fewer than 15.

• Refrigerant piping connection between indoor and out-

door units should be performed once the units are

secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the outdoor unit. 

• The refrigerant piping should be dry and free of dust and

other impurities.

• The bending angle of the refrigerant pipe should not

exceed 90 degrees and the bending radius should be as

large as possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.
• Before insulating the suction and liquid refrigeration

pipes, perform pressure and leak tests. For details, see

the outdoor unit installation manual. Insulating both suc-

tion and liquid refrigerant pipes is mandatory. 

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

Step 5 — Complete Electrical Connections —

Installation of wiring must conform with local building codes

and with National Electric Code ANSI/NFPA 70, current edi-

tions. Units must be electrically grounded in conformance with

the code. In Canada, wiring must comply with CSA C22.1,

Electrical Code.

This equipment in its standard form is designed for an elec-

trical supply of 208/230-1-60. Any damage to or failure of

units caused by incorrect wiring or voltage is not covered by

warranty.

Electric wiring must be sized to carry the full load amp

draw of the motor, starter, and any other controls that are used

with the unit. See Table 2 for electrical data.

Table 2 — 40WAD Electrical Data

                            LEGEND

After the pipe work is complete, the electrical supply can be

connected by routing the cable through the appropriate casing

holes or knockouts and connecting the supply and ground ca-

bles to the unit’s power terminal.

Be sure the power wiring and control wiring do not cross, as

this might cause disturbance on the controls side. See Fig. 8 for

wiring diagram.
NOTE: The indoor unit requires its own power supply. Indoor

units are not powered through outdoor units.

CAUTION

When connecting from an indoor unit to an outdoor unit,

the isolation valve at the outdoor unit should be in the

closed position throughout the refrigerant piping process.

Failure to follow this procedure may result in equipment

damage.

WARNING

Electrical shock can cause personal injury and death. Dis-

connect power supply before making wiring connections.

There may be more than one disconnect switch. Tag all dis-

connect locations to alert others not to restore power until

work is completed. 

WARNING

All units must be wired strictly in accordance with the wir-

ing diagram furnished with the unit. Any wiring different

from the wiring diagram could result in personal injury and

property damage.

CAUTION

Any original factory wiring that requires replacement must

be replaced with wiring material having a temperature rat-

ing of at least 105 C.
Ensure supply voltage to the unit, as indicated on the serial

plate, is not more than 10% over the rated voltage or 10%

under the rated voltage.
Failure to follow these recommendations may result in

equipment damage.

40WAD UNIT SIZE

POWER SUPPLY

MCA

MOPD

007

0.5

15

009

0.5

15

012

0.6

15

015

0.7

15

018

0.9

15

024

1.1

15

MCA

— Minimum Circuit Amps

MOPD — Maximum Overcurrent

Protective Device

Summary of Contents for 40WAD007

Page 1: ...rds DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death...

Page 2: ...ze Figure 2 shows unit dimen sions See Fig 3 for fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regul...

Page 3: ...wg 0 04 to 0 20 INDOOR NOISE LEVEL dBA Low 31 31 33 33 34 Medium 34 34 36 37 38 High 35 36 37 38 40 UNIT Unit Dimensions W x H x D in 27 1 2 x 8 1 4 x 19 3 4 36 1 4 x 8 1 4 x 19 3 4 44 7 8 x 8 1 4 x...

Page 4: ...1847 1 3 8 Fig 2 40WAD007 024 Dimensions NOTE All dimensions shown in inches 40WAD UNIT SIZE DIMENSION in A B C D E F G H I J K L M 007 012 27 1 2 8 1 4 19 3 4 17 3 4 30 3 4 1 1 4 20 1 8 5 8 5 3 4 23...

Page 5: ...erial on the motor or blower wheels will not be covered by the manufacturer s war ranty Some units and or job conditions may require some form of temporary covering during construction PREPARING JOBSI...

Page 6: ...for the drain 3 Secure the unit in position with locknuts and washers on both sides of the mounting bracket Ensure that the threaded rod does not protrude more than 2 in below the mounting brackets as...

Page 7: ...ring must comply with CSA C22 1 Electrical Code This equipment in its standard form is designed for an elec trical supply of 208 230 1 60 Any damage to or failure of units caused by incorrect wiring o...

Page 8: ...r electrical devices WIRED REMOTE CONTROLLER PROGRAMMA BLE To connect a programmable wired remote controller thermostat to the indoor unit use 4 core shielded cable and 4 pin connector from electrical...

Page 9: ...nd liquid line service valves are in open posi tion Drain Pump and Drainage Test Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 12 2 Us...

Page 10: ...addition Be sure all electrical connections are secure Check condensate pump operation if applicable Check the heating and cooling action to confirm proper operation TROUBLESHOOTING Figure 14 shows t...

Page 11: ...are short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance th...

Page 12: ...2 a40 1932 Fig B SW2 Settings POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON O...

Reviews: