APPENDIX A — CONTROL SETTINGS

There are 4 DIP switches on the main board. Figures A-E

show the settings for each parameter controlled by a switch.

Switches are shown in the default settings.

v

Terminal J1 is located on the main control board. The de-

fault setting for J1 is no jumper and the Power Off Memory

function is enabled. When J1 jumper is in place, the Power Off

Memory function will be disabled.

POSITION 1 — START-UP 

OFF

— Auto Addressing Mode (Default)

ON

— Factory Test Mode

POSITION 2 — FAN 

ON

— DC Fan (Default)

OFF

— Do not set switch to OFF

Fig. A — SW1 Settings

ON

OFF

1 2

a40-1931

ON

OFF

1 2

a40-1932

Fig. B — SW2 Settings

POSITION 1, 2 — COIL TEMPERATURE, HEATING MODE 

OFF, OFF — Coil Temperature < 59 F, No Heat (Default)
OFF, ON

— Coil Temperature < 68 F, No Heat

ON, OFF

— Coil Temperature < 75.2 F, No Heat

ON, ON

— Coil Temperature < 78.8 F, No Heat

ON

OFF

1 2

a40-1925

Fig. C — SW3 Settings

ON

OFF

1 2

a40-1925

POSITION 1, 2 — MODE, FAN STATUS, SP REACHED 

SP — Set Point

OFF, OFF — Cooling Mode/Fan On/SP Reached, 

Heating Mode/Fan On/SP Reached (Default)

OFF, ON

— Cooling Mode/Fan On/SP Reached, 

Heating Mode/Fan Off/SP Reached

ON, OFF

— Cooling Mode/Fan Off/SP Reached, 

Heating Mode/Fan On/SP Reached

ON, ON

— Cooling Mode/Fan Off/SP Reached, 

Heating Mode/Fan Off/SP Reached

Fig. D — SW4 Settings

ON

OFF

1 2

a40-1925

POSITION 1, 2 — HEATING TEMPERATURE OFFSET 

OFF, OFF — Temperature Offset is 1.8 F (Default)
OFF, ON

— Temperature Offset is 3.6 F

ON, OFF

— Temperature Offset is 7.2.F

ON, ON

— Temperature Offset is 10.8 F

Fig. E — SW5 Settings

POSITION 1 — CONTROLS  

OFF

— Display Board (Default)

ON

— Not Used

POSITION 2 — FAN MODE  

OFF

— Non-Auto Mode (Default)

ON

— Auto Mode

ON

OFF

1 2

a40-1933

ON

OFF

1 2

a40-1934

Summary of Contents for 40WAD007

Page 1: ...rds DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death...

Page 2: ...ze Figure 2 shows unit dimen sions See Fig 3 for fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regul...

Page 3: ...wg 0 04 to 0 20 INDOOR NOISE LEVEL dBA Low 31 31 33 33 34 Medium 34 34 36 37 38 High 35 36 37 38 40 UNIT Unit Dimensions W x H x D in 27 1 2 x 8 1 4 x 19 3 4 36 1 4 x 8 1 4 x 19 3 4 44 7 8 x 8 1 4 x...

Page 4: ...1847 1 3 8 Fig 2 40WAD007 024 Dimensions NOTE All dimensions shown in inches 40WAD UNIT SIZE DIMENSION in A B C D E F G H I J K L M 007 012 27 1 2 8 1 4 19 3 4 17 3 4 30 3 4 1 1 4 20 1 8 5 8 5 3 4 23...

Page 5: ...erial on the motor or blower wheels will not be covered by the manufacturer s war ranty Some units and or job conditions may require some form of temporary covering during construction PREPARING JOBSI...

Page 6: ...for the drain 3 Secure the unit in position with locknuts and washers on both sides of the mounting bracket Ensure that the threaded rod does not protrude more than 2 in below the mounting brackets as...

Page 7: ...ring must comply with CSA C22 1 Electrical Code This equipment in its standard form is designed for an elec trical supply of 208 230 1 60 Any damage to or failure of units caused by incorrect wiring o...

Page 8: ...r electrical devices WIRED REMOTE CONTROLLER PROGRAMMA BLE To connect a programmable wired remote controller thermostat to the indoor unit use 4 core shielded cable and 4 pin connector from electrical...

Page 9: ...nd liquid line service valves are in open posi tion Drain Pump and Drainage Test Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 12 2 Us...

Page 10: ...addition Be sure all electrical connections are secure Check condensate pump operation if applicable Check the heating and cooling action to confirm proper operation TROUBLESHOOTING Figure 14 shows t...

Page 11: ...are short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance th...

Page 12: ...2 a40 1932 Fig B SW2 Settings POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON O...

Reviews: