40KMC---N

GB - 16

Fresh air renewal and conditioned air supply to an adjacent room

Diagram of conditioned air supply to an adjacent room: one louvre closed

 Supply air duct to adjacent room

Fresh air renewal

• The supplementary fan motor for outside air intake has to be

supplied separately and controlled by a bipolar ON-OFF switch
with safety fuses (field-installed).

  To adjust the fan motor air flow to the required values it is

advisable to install a speed controller.

  Fresh air flow must be less than 10% of the total air flow, to

avoid operating problems.

  For fresh air ventilation rates higher than 10%, a primary air

treatment system with separate deflectors is recommended.

• Install an air inlet grille with filter inspection port to prevent

dust and dirt from entering and fouling the indoor unit heat
exchanger.
Filter installation also makes the installation of a duct closing
damper during shutdown periods unnecessary.

Conditioned air supply to an adjacent room

• Air supply to an adjacent room requires that the outlet

corresponding with the duct is closed, using the air
supply outlet obstruction kit supplied.
The kit cannot be used in units equipped with electric
heater.
An air inlet grille must be fitted (if possible near the floor)
between the air conditioned room (where the unit is situated)
and the adjacent room or, alternatively, the door must be
undercut, as shown in the drawing.

• The duct lengths can be calculated in accordance with the “air

distribution to an adjacent room” diagram, also taking into
account the pressure drop through air diffusers and fresh air
filters.

• DO NOT use active carbon or electrostatic filter kits for ducts

towards adjacent rooms.

Air flow

In case of two louvres closed, the fresh air flow towards the adjacent room is 50% higher compared with only one louvre
closed (with equal static external pressure).

30

20

10

0

0

100

200

300

400

24/28

12

18

450

410

60

48

36

40

m

3

/h

0

30

60

90

120

113,9

l/s

125

External static pressure - Pa

Summary of Contents for 40KMC---N

Page 1: ...AM PM 40KMC N INSTALLATION MANUAL...

Page 2: ...3 Technical data of electric heaters 3 Material supplied 3 Operating limits 3 Components required for a complete installation 3 General information 4 Accessories 4 Warnings avoid 5 6 Installation 6 8...

Page 3: ...036 048 060 Unit 17 5 19 19 36 38 38 41 Frame Grille assembly 3 3 3 5 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8...

Page 4: ...8 8 8 8 8 6 5 10 8 10 8 7 5 7 5 7 5 7 5 Control device GMC electronic control Safety thermostat N 1 Manual reset thermostat ST1 60 C N 1 Manual reset thermostat ST2 100 C Power supply cables mm2 3 G...

Page 5: ...bility for damage resulting from modifications or errors in the electrical or refrigerant connections Failure to observe the installation instructions or use of the unit under conditions other than th...

Page 6: ...unit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conde...

Page 7: ...utlets as indicated in the drawing WARNING To close one or two air outlets use the special kit Install the unit as centrally as possible in the room the air flow direction can be controlled by means o...

Page 8: ...the unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant c...

Page 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate w...

Page 10: ...ns The length of the flared walls must be uniform Lubricate the end of pipe and the thread of the flare connection with anti freeze oil Tighten by hand and then use two wrenches to tighten all connect...

Page 11: ...VER connector Float connector Pump connector Louvre connector A Electric heater supply connection B Outdoor unit connection CP CG CA CV CLR CONTROL PANEL mod 28 36 48 60 SYSTEM CONFIGURATION IMPORTANT...

Page 12: ...split unit 4G1 WARNING The ground wire for the indoor unit outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole WARNING The ground wire for the...

Page 13: ...tin plated eyelet terminal with M4 screw hole 1 2 3 10 80 10 100 4 5 Terminal box legend all models Earth L Live power supply N Neutral power supply N Neutral connection indoor outdoor unit Y Compres...

Page 14: ...F Interconnection cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Notes See outdoor unit installation manual For correct passage of cables please refer to the drawing sho...

Page 15: ...MICROSWITCH LOUVRE RELAY BOARD ELECTRIC HEATER SAFETY THERMOSTAT IF PRESENT WIRE COLOURS BROWN BLUE BLACK GREY YELLOW GREEN ORANGE RED WHITE YELLOW IMPORTANT THE WARRANTY WILL BE INVALIDATED IF FACTO...

Page 16: ...tted grille Air intake grille Fresh air renewal and conditioned air supply to an adjacent room Use locally purchased material suitable for operating temperatures of 60 C continuous Conduits can be of...

Page 17: ...per during shutdown periods unnecessary Conditioned air supply to an adjacent room Air supply to an adjacent room requires that the outlet corresponding with the duct is closed using the air supply ou...

Page 18: ...will be cleared the time segments will display the first configuration item rAdr remote address and the tempera ture segments will display the default value of this configuration item Ab control of bo...

Page 19: ...te When 30 minutes have elapsed and no buttons have been pressed the remote control will automatically exit the test menu and resume its normal operation Address selector If you are installing two ind...

Page 20: ...code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses with enabled code Guide for the owner When...

Page 21: ...L010127H26 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Reviews: