background image

40KMC---N

GB - 4

Unit installation

Read this instruction manual thoroughly before starting
installation.

• This unit complies with the low-voltage (EEC/73/23) and

electromagnetic compatibility (EEC/ 89/336) directives.

• Follow all current national safety code requirements.

In particular ensure that a properly sized and connected ground
wire is in place.

• Check that the voltage and frequency of the mains power supply

are as required for the unit to be installed; the available power
source must be adequate to operate all other appliances
connected to the same line.
Also ensure that national safety code requirements have been
followed for the main supply circuit.

• Connection of the system to the mains power supply is to be

carried out in compliance with the wiring diagram shown in
the installation instructions of the external section.

• Connect indoor and outdoor units with field-supplied copper

pipes by means of flare connections. Use insulated seamless
refrigeration grade pipe only, (Cu DHP type according to
ISO1337), degreased and deoxidized, suitable for operating
pressures of at least 4200 kPa and for burst pressure of at least
20700 kPa. Under no circumstances must sanitary type copper
pipe be used.

• Where necessary, use field-supplied 25 mm I.D. PVC pipe (not

supplied) of appropriate length and with the correct thermal
insulation for the condensate drain extension.

• After installation thoroughly test system operation and explain all

system functions to the owner.

• Use this unit only for factory approved applications: the unit

cannot be used in laundry or steam pressing premises.

WARNING:
Disconnect the mains power supply switch before servicing
the system or handling any internal parts of the unit.

• Do not open the remote control to avoid possible damage. In case

of malfunctioning contact a qualified service engineer.

• This installation manual describes the installation procedures of

the indoor unit of a residential split system consisting of two
Carrier manufactured units.
Do not connect this unit to any other manufacturer's outdoor unit.
The manufacturer declines any liability for system malfunction
resulting from unauthorised system combinations.

• The manufacturer declines any liability for damage resulting

from modifications or errors in the electrical or refrigerant
connections.
Failure to observe the installation instructions, or use of the
unit under conditions other than those indicated in table

General information

“Operating limits” of the outdoor unit installation manual, will
immediately invalidate the unit warranty.

• Failure to observe electric safety codes may cause a fire hazard in

the event of short circuits.

• Inspect equipment for damage during transport. In case of

damage file an immediate claim with the shipping company.
Do not install or use damaged units.

• In case of malfunction turn the unit off, disconnect the mains

power supply and contact a qualified service engineer.

• Maintenance of the refrigerant circuit must only be carried out by

qualified personnel.

• All of the manufacturing and packaging materials used for this

appliance are biodegradable and recyclable.

• Dispose of the packaging material in accordance with local

requiremements.

• This equipment contains refrigerant that must be disposed of

correctly.
When disposing of the unit at the end of its operational life,
take the unit to an authorised waste disposal centre, or to the
original equipment dealer, for correct disposal.

Choosing the installation site

Positions to avoid:

• Exposure to direct sunlight.

• Areas close to heat sources.

• On damp walls or in positions that may be exposed to water

hazard.

• Where curtains or furniture may obstruct free air circulation.

Recommendations:

• Choose an area free from obstructions which may cause uneven

air distribution and/or return.

• Consider using an area where installation is easy.

• Choose a position that allows for the clearances required.

• Look for a position in the room which ensures the best possible air

distribution.

• Install unit in a position where condensate can easily be piped to an

appropriate drain.

Notes:

(1)

 Not to be used on units equipped with electric heater.

(2)

 IMQ approved kit.

Table VI: Accessories

A= mod. 012, 018, 024.

B= mod. 028, 036, 048, 060.

Description

Code

A

B

Air supply outlet obstruction kit

 (1)

40GK-900---003-40

X

40GK-900---013-40

X

Room Controller kit (Grouping)

33MC9002

X

X

Zone manager kit (Zoning)

33MC9001

X

X

Zone manager

33MC-ZM

X

X

Infrared control kit 

(2)

33MC-MC

X

X

Description

Code

A

B

Electrostatic filter

40GK-900---001-40

X

40GK-900---011-40

X

Active carbon filter

40GK-900---002-40

X

40GK-900---012-40

X

Room Controller

33MC-RC

X

X

Summary of Contents for 40KMC---N

Page 1: ...AM PM 40KMC N INSTALLATION MANUAL...

Page 2: ...3 Technical data of electric heaters 3 Material supplied 3 Operating limits 3 Components required for a complete installation 3 General information 4 Accessories 4 Warnings avoid 5 6 Installation 6 8...

Page 3: ...036 048 060 Unit 17 5 19 19 36 38 38 41 Frame Grille assembly 3 3 3 5 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8...

Page 4: ...8 8 8 8 8 6 5 10 8 10 8 7 5 7 5 7 5 7 5 Control device GMC electronic control Safety thermostat N 1 Manual reset thermostat ST1 60 C N 1 Manual reset thermostat ST2 100 C Power supply cables mm2 3 G...

Page 5: ...bility for damage resulting from modifications or errors in the electrical or refrigerant connections Failure to observe the installation instructions or use of the unit under conditions other than th...

Page 6: ...unit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conde...

Page 7: ...utlets as indicated in the drawing WARNING To close one or two air outlets use the special kit Install the unit as centrally as possible in the room the air flow direction can be controlled by means o...

Page 8: ...the unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant c...

Page 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate w...

Page 10: ...ns The length of the flared walls must be uniform Lubricate the end of pipe and the thread of the flare connection with anti freeze oil Tighten by hand and then use two wrenches to tighten all connect...

Page 11: ...VER connector Float connector Pump connector Louvre connector A Electric heater supply connection B Outdoor unit connection CP CG CA CV CLR CONTROL PANEL mod 28 36 48 60 SYSTEM CONFIGURATION IMPORTANT...

Page 12: ...split unit 4G1 WARNING The ground wire for the indoor unit outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole WARNING The ground wire for the...

Page 13: ...tin plated eyelet terminal with M4 screw hole 1 2 3 10 80 10 100 4 5 Terminal box legend all models Earth L Live power supply N Neutral power supply N Neutral connection indoor outdoor unit Y Compres...

Page 14: ...F Interconnection cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Notes See outdoor unit installation manual For correct passage of cables please refer to the drawing sho...

Page 15: ...MICROSWITCH LOUVRE RELAY BOARD ELECTRIC HEATER SAFETY THERMOSTAT IF PRESENT WIRE COLOURS BROWN BLUE BLACK GREY YELLOW GREEN ORANGE RED WHITE YELLOW IMPORTANT THE WARRANTY WILL BE INVALIDATED IF FACTO...

Page 16: ...tted grille Air intake grille Fresh air renewal and conditioned air supply to an adjacent room Use locally purchased material suitable for operating temperatures of 60 C continuous Conduits can be of...

Page 17: ...per during shutdown periods unnecessary Conditioned air supply to an adjacent room Air supply to an adjacent room requires that the outlet corresponding with the duct is closed using the air supply ou...

Page 18: ...will be cleared the time segments will display the first configuration item rAdr remote address and the tempera ture segments will display the default value of this configuration item Ab control of bo...

Page 19: ...te When 30 minutes have elapsed and no buttons have been pressed the remote control will automatically exit the test menu and resume its normal operation Address selector If you are installing two ind...

Page 20: ...code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses with enabled code Guide for the owner When...

Page 21: ...L010127H26 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Reviews: