Installation of grille/frame assembly

Carefully unpack the assembly and check for damage sustained in
transport. Attach the assembly to the unit by using the two hooks.

Tighten the four screws, link the electrical connectors and insert the
wires in the cable clamp.
Use the screws supplied to fix the frame in position.

Ensure that the frame is not distorted by excessive tightening,
that it is aligned with the false ceiling and above all that there is
a seal between the air inlet and outlet.
In the drawing gasket “A” prevents return air from mixing with
the supply air and gasket “B” prevents the supply air from
leaking into the ceiling void.
On completion, the gap between the unit frame and the false
ceiling must not be more than 5 mm.

Making the hole for connection pipes in the external wall

• After positioning the units and determining the connection position,

make a 70 mm Ø hole in the wall. The same hole can be used as a
condensate drain pipe conduit.

• The hole should have a 5 - 10 mm slope toward the outside.

Insert the plastic conduit provided.

• Pass the power connection cables through the conduit (see

electrical connections).

Condensate drain pipe

• To ensure correct condensate water flow, the drain pipe should

have a gradient of 2% without obstructions.
Furthermore an odour trap of at least 50 mm depth should be
made to prevent unpleasant odours from reaching the room.

• Condensate may be discharged at a maximum height of 200 mm

above the unit, as long as the ascending tube is vertical and
aligned with the drainage flange.

• If it is necessary to discharge the condensate from a level

above 200 mm, install an auxiliary water discharge pump and
float valve.
A float valve is recommended to stop the compressor if there
is a fault at the auxiliary pump.

• The condensate pipe must be insulated with a condensation-

proof material such as polyurethane, propylene or neoprene of
5 to 10 mm thickness.

• If more than one unit is installed in the room, the drain system can

be made as shown in the drawing.

Installation

 Indoors

 Outdoors

Frame support brackets

A. Gasket  "A"
B. Gasket  "B"

Power connection
cables from frame

Power connection
cables from unit

Safety cord

Cable clamp

Frame support
screws

Summary of Contents for 40KMC---N

Page 1: ...AM PM 40KMC N INSTALLATION MANUAL...

Page 2: ...3 Technical data of electric heaters 3 Material supplied 3 Operating limits 3 Components required for a complete installation 3 General information 4 Accessories 4 Warnings avoid 5 6 Installation 6 8...

Page 3: ...036 048 060 Unit 17 5 19 19 36 38 38 41 Frame Grille assembly 3 3 3 5 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8...

Page 4: ...8 8 8 8 8 6 5 10 8 10 8 7 5 7 5 7 5 7 5 Control device GMC electronic control Safety thermostat N 1 Manual reset thermostat ST1 60 C N 1 Manual reset thermostat ST2 100 C Power supply cables mm2 3 G...

Page 5: ...bility for damage resulting from modifications or errors in the electrical or refrigerant connections Failure to observe the installation instructions or use of the unit under conditions other than th...

Page 6: ...unit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conde...

Page 7: ...utlets as indicated in the drawing WARNING To close one or two air outlets use the special kit Install the unit as centrally as possible in the room the air flow direction can be controlled by means o...

Page 8: ...the unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant c...

Page 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate w...

Page 10: ...ns The length of the flared walls must be uniform Lubricate the end of pipe and the thread of the flare connection with anti freeze oil Tighten by hand and then use two wrenches to tighten all connect...

Page 11: ...VER connector Float connector Pump connector Louvre connector A Electric heater supply connection B Outdoor unit connection CP CG CA CV CLR CONTROL PANEL mod 28 36 48 60 SYSTEM CONFIGURATION IMPORTANT...

Page 12: ...split unit 4G1 WARNING The ground wire for the indoor unit outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole WARNING The ground wire for the...

Page 13: ...tin plated eyelet terminal with M4 screw hole 1 2 3 10 80 10 100 4 5 Terminal box legend all models Earth L Live power supply N Neutral power supply N Neutral connection indoor outdoor unit Y Compres...

Page 14: ...F Interconnection cable H07 RN F Interconnection cable H07 RN F Interconnection cable H07 RN F Notes See outdoor unit installation manual For correct passage of cables please refer to the drawing sho...

Page 15: ...MICROSWITCH LOUVRE RELAY BOARD ELECTRIC HEATER SAFETY THERMOSTAT IF PRESENT WIRE COLOURS BROWN BLUE BLACK GREY YELLOW GREEN ORANGE RED WHITE YELLOW IMPORTANT THE WARRANTY WILL BE INVALIDATED IF FACTO...

Page 16: ...tted grille Air intake grille Fresh air renewal and conditioned air supply to an adjacent room Use locally purchased material suitable for operating temperatures of 60 C continuous Conduits can be of...

Page 17: ...per during shutdown periods unnecessary Conditioned air supply to an adjacent room Air supply to an adjacent room requires that the outlet corresponding with the duct is closed using the air supply ou...

Page 18: ...will be cleared the time segments will display the first configuration item rAdr remote address and the tempera ture segments will display the default value of this configuration item Ab control of bo...

Page 19: ...te When 30 minutes have elapsed and no buttons have been pressed the remote control will automatically exit the test menu and resume its normal operation Address selector If you are installing two ind...

Page 20: ...code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses with enabled code Guide for the owner When...

Page 21: ...L010127H26 1205 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2005 Printed in Italy...

Reviews: