Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1 (cont)
39T
UNIT SIZE
HEATER
AREA
(Sq Ft)
NO. OF
CONTROL
STEPS
HEATER
COIL
kW
TEMP
RISE
(°F)
MIN COIL
FACE VEL
(Fpm)
POWER SUPPLY, 3-PHASE CIRCUITS
480 Volts
600 Volts
Total FLA
No. Sub-Ckts*
MWG
Fuse
Total FLA
No. Sub-Ckts*
MWG
Fuse
07
6.39
3
12
20
300
15
1
12
20
12
1
14
15
17
24
350
21
1
10
30
17
1
10
25
24
30
400
29
1
8
40
24
1
10
30
34
38
450
41
1
6
60
33
1
8
45
45
45
500
55
2
4
70
44
1
6
60
57
52
550
69
2
3
90
55
2
4
70
64
53
600
77
2(U)
3
100
62
2
4
80
09
8.23
3
17
22
300
21
1
10
30
17
1
10
25
24
27
350
29
1
8
40
24
1
10
30
34
33
400
41
1
6
60
33
1
8
45
45
39
450
55
2
4
70
44
1
6
60
64
50
500
77
2(U)
3
100
62
2
4
80
6
78
55
550
94
2
1
125
76
2
3
100
86
56
600
104
3
1
150
83
2
2
110
11
9.67
3
15
17
300
19
1
10
25
15
1
12
20
25
24
350
31
1
8
40
25
1
8
35
39
32
400
47
1
6
60
38
1
6
50
56
41
450
68
2
4
90
54
2
4
70
78
52
500
94
2(U)
1
125
76
2 (U)
3
100
6
90
54
550
109
3
1/0
150
87
2
2
110
112
62
600
135
3
2/0
175
108
3
1/0
150
13
12.77
3
29
24
300
35
1
8
45
28
1
8
35
45
32
350
55
2
4
70
44
1
6
60
64
40
400
77
2(U)
3
100
62
2
4
80
78
43
450
94
2(U)
1
125
76
2 (U)
3
100
92
46
500
111
3
1/0
150
89
2 (U)
2
125
6
119
54
550
144
3
3/0
200
115
3
1/0
150
8
132
55
600
159
4
3/0
200
128
3
2/0
175
17
15.37
3
29
20
300
35
1
8
45
28
1
8
35
45
27
350
55
2
4
70
44
1
6
60
64
33
400
77
2
3
100
62
2
4
80
78
36
450
94
2
1
125
76
2 (U)
3
100
6
92
38
500
111
3
1/0
150
89
2
2
125
119
45
550
144
3
3/0
200
115
3
1/0
150
8
132
46
600
159
4
3/0
200
128
3 (U)
2/0
175
21
18.62
3
45
26
300
55
2
4
70
44
1
6
60
74
36
350
90
2(U)
2
125
72
2 (U)
3
90
99
42
400
120
3
1/0
150
96
2 (U)
1
125
6
119
45
450
144
3
3/0
200
115
3
1/0
150
8
159
55
500
192
4
250
250
154
4
3/0
200
198
62
550
239
5(U)
350
300
191
4
250
250
228
65
600
275
6(U)
500
350
220
5
300
300
26
22.55
3
34
16
300
41
1
6
60
33
1
8
45
74
30
350
90
2(U)
2
125
72
2 (U)
3
90
99
35
400
120
3
1/0
150
96
2 (U)
1
125
6
119
37
450
144
3
3/0
200
115
3
1/0
150
8
159
45
500
192
4
250
250
154
4
3/0
200
212
55
550
256
6(U)
400
350
205
5 (U)
300
300
265
63
600
319
7(U)
(2) 250
400
256
6 (U)
400
350
LEGEND
ARI
— Air Conditioning & Refrigeration Institute
FLA
— Total Full Load Amps of Electric Heating Coils
Fuse
— External Fuse Size Required Per Circuit
kW
— Kilowatt Rating
MWG — Minimum Wire Gage
VEL
— Velocity
*(U) signifies unequal kW per step.
NOTES:
1. Subcircuits are internal heater circuits of 48 A or less ampacity.
2. Minimum wire gage is based on 75 C copper conductors; 3 conductors per
circuit.
IMPORTANT: To avoid damage from overheating, coils must not be
operated at less than minimum airflow (cfm).
Minimum Cfm = Coil Face Area x Minimum Coil Face Velocity
3. Electric heat performance is not within the scope of ARI Standard 430
certification.
4. All ratings shown are at 60 Hz. To obtain kW ratings at 50 Hz when voltage
does not change, multiply the 60 Hz rating by 0.833. For example, a 6-step
heater in a size 32 unit has a rating of 119 kW at 60 Hz. To obtain the
50 Hz rating:
119 x 0.833 = 99 kW at 50 Hz
If the voltage also varies from that shown in the table, use the formula in the
following example to arrive at the correct rating at the new voltage before
multiplying by 0.833:
Given:
2
V
2
( )
kW
2
= kW
1
V
1
Where kW
1
= 60 Hz rating
kW
2
= 50 Hz rating
V
1
= 60 Hz voltage
V
2
= 50 Hz voltage
Example:
2
450
kW
2
= 119
( )
480
kW
2
= 105
105 x 0.833 = 87 kW at 450 v, 50 Hz
208-, 240- and 480-V
208- and 600-V
Heaters.
Heaters.
70
Summary of Contents for 39T
Page 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Page 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Page 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Page 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Page 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Page 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Page 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Page 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Page 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Page 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Page 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Page 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Page 102: ......
Page 103: ......