Condensate Drain —
Install a condensate-trapping drain
line at the unit’s drain connection; use 1
1
⁄
4
-in. standard pipe.
See Fig. 56 and 57 for correct drain layout.
To determine the trap dimensions for draw-thru units, cal-
culate the coil’s maximum negative static pressure (P
1
in
Fig. 56). The maximum negative static pressure equals the
pressure drop for the mixing box damper, dirty filter, and
dirty coil, at the design flow. Add 1 in. to the pressure drop.
(P
1
= negative static pr 1 inch.)
Traps on draw-thru units must store enough condensate to
prevent losing the drain seal at start-up. The ‘‘Minimum
1
⁄
2
P
1
’’ dimension ensures that enough condensate is stored.
To determine the trap dimensions for blow-thru units, find
the coil’s maximum positive pressure (P
1
in Fig. 57). This
figure is normally the fan total static pressure (P
1
= fan total
static pressure).
For all units, provide condensate freeze-up protection as
required. On units with internal spring isolators, be sure the
unit is mounted to allow sufficient clearance for the required
drain trap depth.
Fig. 56 — Condensate Drain, Draw-Thru Units
Fig. 57 — Condensate Drain, Blow-Thru Units
65
Summary of Contents for 39T
Page 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Page 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Page 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Page 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Page 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Page 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Page 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Page 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Page 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Page 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Page 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Page 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Page 102: ......
Page 103: ......