Table 20 — Direct Expansion Coil Circuiting Data (cont)
LARGE FACE AREA COILS (cont)
39T UNIT SIZE
17
21
26
CIRCUITING TYPE
Half
Full
Double
Half
Full
Double
Half
Full
Double
Airflow (cfm) at 550 fpm
8895
11,439
14,215
Total Face Area (sq ft)
16.2
20.8
25.8
Tubes in Face
28
34
38
Tube Length (in.)
66
9
⁄
16
70
1
⁄
2
78
3
⁄
8
No. of Circuits — Total
14
28
56
17
34
68
19
38
76
4-Row Coil
Circuit Equivalent Length (in.)
54.9
32.7
—
57.5
34.0
—
62.7
36.6
—
Face-Split Coils
No. of TXVs
2
2
—
2
2
—
2
4
—
No. of Circuits/Distributor*
7
14
—
8,9
17
—
9,10
9,10
—
Suction Connections (in. OD)
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
21
21
—
15
21
—
28
18
—
Distributor Nozzle Size†
10
10
—
12
12
—
15
15
—
Row-Split Coils
No. of TXVs
2
2
—
2
2
—
2
4
—
No. of Circuits/Distributor*
7
14
—
8,9
17
—
9,10
9,10
—
Suction Connections (in. OD)
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
21
21
—
15
21
—
28
18
—
Distributor Nozzle Size†
10
10
—
12
12
—
15
15
—
6-Row Coil
Circuit Equivalent Length (in.)
83.0
40.8
—
87.0
42.7
—
94.9
46.7
—
Face-Split Coils
No. of TXVs
2
2
—
2
2
—
2
4
—
No. of Circuits/Distributor*
7
14
—
8,9
17
—
9,10
9,10
—
Suction Connections (in. OD)
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
21
21
—
15
21
—
28
18
—
Distributor Nozzle Size†
10
10
—
12
12
—
15
15
—
Row-Split Coils
No. of TXVs
2
2
—
2
2
—
2
4
—
No. of Circuits/Distributor*
7
14
—
8,9
17
—
9,10
9,10
—
Suction Connections (in. OD)
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
1
3
⁄
8
1
5
⁄
8
—
Distributor Connections (in. OD)
7
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
—
Distributor Tube Length (in.)
21
21
—
15
21
—
28
18
—
Distributor Nozzle Size†
10
10
—
12
12
—
15
15
—
8-Row Coil
Circuit Equivalent Length (in.)
—
54.9
26.7
—
57.5
28.0
—
62.7
30.6
Face-Split Coils
No. of TXVs
—
2
4
—
2
4
—
4
8
No. of Circuits/Distributor*
—
14
14
—
17
17
—
9,10
9,10
Suction Connections (in. OD)
—
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
Distributor Connections (in. OD)
—
1
3
⁄
8
1
3
⁄
8
—
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
Distributor Tube Length (in.)
—
21
13
—
21
21
—
18
13
Distributor Nozzle Size†
—
10
5
—
12
6
—
15
8
Row-Split Coils
No. of TXVs
—
2
4
—
2
4
—
4
8
No. of Circuits/Distributor*
—
14
14
—
17
17
—
9,10
9,10
Suction Connections (in. OD)
—
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
—
1
5
⁄
8
1
5
⁄
8
Distributor Connections (in. OD)
—
1
3
⁄
8
1
3
⁄
8
—
1
3
⁄
8
1
3
⁄
8
—
1
1
⁄
8
1
1
⁄
8
Distributor Tube Length (in.)
—
21
13
—
21
21
—
18
13
Distributor Nozzle Size†
—
10
5
—
12
6
—
15
8
LEGEND
TXV — Thermostatic Expansion Valve (Field-Supplied)
*Where each distributor has the same number of circuits, that number is shown once. When a coil has
an uneven number of circuits per distributor, both values are shown. For example, the upper coil of a
half-circuit size 32 large face area coil has 5 circuits on one distributor and 6 circuits on the other
distributor; the lower coil has 6 circuits on each distributor.
†Factory-supplied distributors have factory-selected nozzle sizes shown. If necessary, replace factory-
supplied nozzles with field-supplied and installed nozzles. Consult Electronic Catalog
AHU Builder™
program for correct nozzle selection.
52
Summary of Contents for 39T
Page 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Page 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Page 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Page 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Page 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Page 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Page 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Page 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Page 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Page 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Page 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Page 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Page 102: ......
Page 103: ......