Table 22 — Electric Heater Data, Horizontal Heaters Used in EHS1
39T
UNIT SIZE
HEATER
AREA
(Sq Ft)
NO. OF
CONTROL
STEPS
HEATER
COIL
kW
TEMP
RISE
(°F)
MIN COIL
FACE VEL
(Fpm)
POWER SUPPLY, 3-PHASE CIRCUITS
208 Volts
240 Volts
Total FLA
No. Sub-Ckts*
MWG
Fuse
Total FLA
No. Sub-Ckts*
MWG
Fuse
07
6.39
3
12
20
300
34
1
8
45
29
1
8
40
17
24
350
48
1
6
60
41
1
6
60
24
30
400
67
2
4
90
58
2
4
80
34
38
450
95
2(U)
1
125
92
2 (U)
2
110
45
45
500
125
3
2/0
175
109
3
1/0
150
57
52
550
159
4(U)
3/0
200
138
3
2/0
175
64
53
600
178
4(U)
4/0
225
154
4 (U)
3/0
200
09
8.23
3
17
22
300
48
1
6
60
41
1
6
60
24
27
350
67
2
4
90
58
2
4
80
34
33
400
95
2(U)
1
125
82
2 (U)
2
110
45
39
450
125
3
2/0
175
109
3
1/0
150
64
50
500
178
4(U)
4/0
225
154
4 (U)
3/0
200
6
78
55
550
217
5(U)
300
300
188
4 (U)
250
250
86
56
600
239
5(U)
350
300
207
5 (U)
300
300
11
9.67
3
15
17
300
42
1
6
60
37
1
6
50
25
24
350
70
2
3
90
61
2
4
80
39
32
400
109
3
1/0
150
94
2 (U)
1
125
56
41
450
156
4(U)
3/0
200
135
3
2/0
175
78
52
500
217
5(U)
300
300
188
4 (U)
250
250
6
90
54
550
250
6
400
350
217
5 (U)
300
300
13
12.77
3
29
24
300
81
2(U)
2
110
70
2
3
90
45
32
350
125
3
2/0
175
109
3
1/0
150
64
40
400
178
4(U)
4/0
225
154
4 (U)
3/0
200
78
43
450
217
5(U)
300
300
188
4 (U)
250
250
92
46
500
256
6
400
350
222
5 (U)
300
300
17
15.37
3
29
20
300
81
2(U)
2
110
70
2
3
90
45
27
350
125
3
2/0
175
109
3
1/0
150
64
33
400
178
4(U)
4/0
225
154
4 (U)
3/0
200
78
36
450
217
5(U)
300
300
188
4 (U)
250
250
6
92
38
500
256
6
400
350
222
5 (U)
300
300
21
18.62
3
45
26
300
125
3
2/0
175
109
3
1/0
150
74
36
350
206
5(U)
300
300
179
4
4/0
225
99
42
400
275
6
500
350
239
5 (U)
350
300
26
22.55
3
34
16
300
95
2(U)
1
125
82
2 (U)
2
110
74
30
350
206
5(U)
300
300
179
4 (U)
4/0
255
99
35
400
275
6
500
350
239
5 (U)
350
300
LEGEND
ARI
— Air Conditioning & Refrigeration Institute
FLA
— Total Full Load Amps of Electric Heating Coils
Fuse
— External Fuse Size Required Per Circuit
kW
— Kilowatt Rating
MWG — Minimum Wire Gage
VEL
— Velocity
*(U) signifies unequal kW per step.
NOTES:
1. Subcircuits are internal heater circuits of 48 A or less ampacity.
2. Minimum wire gage is based on 75 C copper conductors; 3 conductors per
circuit.
IMPORTANT: To avoid damage from overheating, coils must not be
operated at less than minimum airflow (cfm).
Minimum Cfm = Coil Face Area x Minimum Coil Face Velocity
3. Electric heat performance is not within the scope of ARI Standard 430
certification.
4. All ratings shown are at 60 Hz. To obtain kW ratings at 50 Hz when voltage
does not change, multiply the 60 Hz rating by 0.833. For example, a 6-step
heater in a size 32 unit has a rating of 119 kW at 60 Hz. To obtain the
50 Hz rating:
119 x 0.833 = 99 kW at 50 Hz
If the voltage also varies from that shown in the table, use the formula in the
following example to arrive at the correct rating at the new voltage before
multiplying by 0.833:
Given:
2
V
2
( )
kW
2
= kW
1
V
1
Where kW
1
= 60 Hz rating
kW
2
= 50 Hz rating
V
1
= 60 Hz voltage
V
2
= 50 Hz voltage
Example:
2
450
kW
2
= 119
( )
480
kW
2
= 105
105 x 0.833 = 87 kW at 450 v, 50 Hz
208-, 240- and 480-V
208- and 600-V
Heaters.
Heaters.
68
Summary of Contents for 39T
Page 43: ...Fig 34 Discharge Fabrication Draw Thru Plenum Fans 43 ...
Page 49: ...Fig 41 Coil Connections and Lifting Points Fig 42 Steam Coil PIping 49 ...
Page 78: ...Fig 64 Blow Thru Unit Coil Removal Fig 65 Plan View Typical Coil 78 ...
Page 81: ...Fig 68 Filter Arrangement 2 in and 4 in Flat 81 ...
Page 82: ...Fig 68 Filter Arrangement 2 in and 4 in Flat cont 82 ...
Page 83: ...Fig 69 Filter Arrangement Angle Filters 2 in Only 83 ...
Page 84: ...Fig 69 Filter Arrangement Angle Filters 2 in Only cont 84 ...
Page 85: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru 85 ...
Page 86: ...Fig 70 Filter Arrangement BCF1 Bag or Cartridge Draw Thru cont 86 ...
Page 87: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru 87 ...
Page 88: ...Fig 71 Filter Arrangement BCF3 Bag or Cartridge Blow Thru cont 88 ...
Page 92: ...NOTE A frame shown shaded Fig 74 Fan Discharge Positions 92 ...
Page 102: ......
Page 103: ......