background image

Step 2—Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 3
to determine base pan size and knockout hole location.

On rooftop applications, mount on level platform or frame 6 in.
above roof surface. Place unit above a load-bearing wall and
isolate unit and tubing set from structure. Arrange supporting
members to adequately support unit and minimize transmission of
vibration to building. Consult local codes governing rooftop
applications.

Roof mounted units exposed to winds above 5 mph may require
wind baffles to achieve adequate defrost. Consult Low-Ambient
Guideline for wind baffle construction.

NOTE:

Unit must be level to within

±

2° (

±

3/8 in./ft) per

compressor manufacturer specifications.

Step 3—Clearance Requirements

When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.

On rooftop applications, locate unit at least 6 in. above roof
surface.

Step 4—Operating Ambients

The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F. The maximum outdoor operating ambient in heating mode
is 66°F.

Step 5—Elevate Unit

Accumulation of water and ice in base pan may cause
equipment damage.

Elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate
drainage of unit. Fig. 4 shows unit with accessory support feet
installed. Use accessory snow stand in areas where prolonged
freezing temperatures are encountered. Refer to separate Installa-
tion Instructions packaged with accessories.

Step 6—Check Indoor and Outdoor AccuRater® Piston

Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace

Fig. 2—Connecting Tubing Installation

A94028

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 MIN.

SUSPENSION

Fig. 3—Mounting Unit to Pad

Dimensions (In.)

UNIT

SIZE

MINIMUM MOUNTING

PAD DIMENSIONS

TIEDOWN KNOCKOUT

LOCATIONS

Support

Feet

Snow

Stand

A

B

018, 024

20 X 27

24 X 28

4-1/8

7-1/8

030–060

26 X 32

31 X 35

5-1/16

9-11/16

A97548

C

L

A

B

VIEW FROM TOP

8

 3

/

16

 

3/8-

IN. DIA TIEDOWN

KNOCKOUTS IN BASEPAN

(2) PLACES

Fig. 4—Accessory Support Feet

A98534

2

Summary of Contents for 38YKC Series

Page 1: ...y from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly a...

Page 2: ...ications locate unit at least 6 in above roof surface Step 4 Operating Ambients The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode...

Page 3: ...f refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDO...

Page 4: ...ctric shock fire or death CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 7 CONNECT CONTROL WIRING R...

Page 5: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Page 6: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Page 7: ...24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN...

Page 8: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Page 9: ...JUMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 12 Typical 24 v Cir...

Page 10: ...rgized Cooling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor f...

Page 11: ...ocedure is valid when indoor airflow is within 21 of its rated CFM 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure suction pressure by attaching a gage to suction valve service...

Page 12: ...R TEMPERATURE F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65 6 10 13 16 19 21 24 27 30 33 36 38 41 70 7 10 13...

Reviews: