WIRING DIAGRAM NOTES:

1. CARRIER THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCU-

RATE FOR MODEL NUMBERS BEGINNING WITH TSTAT _ _ _ _ _
_ _.

2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.

3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEM-

PERATURE SWITCH, OR 5-MINUTE COMPRESSOR CYCLE PRO-
TECTION.

CONNECT

24-V

FIELD

WIRING

TO

FACTORY-

PROVIDED STRIPPED LEADS.

4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME

UNITS.

5. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE

COMPRESSOR CYCLE PROTECTION AND 4 CYCLES PER HR
LIMIT. SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR
DETAILS.

6. TO STAGE ELECTRIC RESISTANCE HEAT, CONSULT OUTDOOR

THERMOSTAT INSTALLATION INSTRUCTIONS.

7. FOR DUAL FUEL THERMOSTATS, UNDERLINED LETTER ON

DUAL TERMINAL INDICATES ITS USAGE.

FOR EXAMPLE: O/W2 MEANS O

O/W2 MEANS W2

OUTDOOR TEMPERATURE SENSOR MUST BE ATTACHED IN ALL
DUAL FUEL INSTALLATIONS.

JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMI-
NALS MUST BE PRESENT.

8. Y1 AND O CONNECTIONS TO 2-STAGE FURNACES MAY NOT

EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW
TERMINAL.

Fig. 12—Typical 24-v Circuit Connections using Carrier Model DF Thermostat with Single- or 2-Stage Furnace

A97538

G

R

Y/Y2

O/W2

CARRIER

DUAL FUEL

THERMOSTAT

MODEL DF

SINGLE-STAGE

FURNACE

HEAT PUMP

G

Y

W

C

Y

R

O

W2

Y1/W2

C

B

L

S1

S2

R

C

FURNACE

COMPRESSOR

 FAN

24 VAC HOT

24 VAC COM

N/A

RVS HEATING

RVS SENSING

OUTDOOR
SENSOR
CONNECTION

OUTDOOR
TEMPERATURE
SENSOR

W/W1

See note 7

RVS COOLING

G

R

Y/Y2

O/W2

CARRIER

DUAL FUEL

THERMOSTAT

MODEL DF

TWO-STAGE OR

VARIABLE SPEED

FURNACE

HEAT PUMP

G

C

Y

R

O

W2

Y1/W2

C

B

L

S1

S2

R

C

O

W2

Y1

FURNACE LO

COMPRESSOR

 FAN

24 VAC HOT

24 VAC COM

FURNACE HI

RVS HEATING

RVS SENSING

OUTDOOR
SENSOR
CONNECTION

OUTDOOR
TEMPERATURE
SENSOR

W/W1

W/W1

Y/Y2

See notes 7 and 8

RVS COOLING

A97539

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

A97413

9

Summary of Contents for 38YKC Series

Page 1: ...y from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly a...

Page 2: ...ications locate unit at least 6 in above roof surface Step 4 Operating Ambients The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode...

Page 3: ...f refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDO...

Page 4: ...ctric shock fire or death CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 7 CONNECT CONTROL WIRING R...

Page 5: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Page 6: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Page 7: ...24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN...

Page 8: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Page 9: ...JUMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 12 Typical 24 v Cir...

Page 10: ...rgized Cooling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor f...

Page 11: ...ocedure is valid when indoor airflow is within 21 of its rated CFM 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure suction pressure by attaching a gage to suction valve service...

Page 12: ...R TEMPERATURE F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65 6 10 13 16 19 21 24 27 30 33 36 38 41 70 7 10 13...

Reviews: