Fig. 10—Typical 24-v Circuit Connections using Carrier Model HP Thermostat with Smart Heat

and No Outdoor Thermostat, 1 Outdoor Thermostat, or 2 Outdoor Thermostats and

Carrier Model 2S Thermostat with FK4C/40FKA Fan Coil and Intelligent Staging

A97543

24 VAC HOT

R

G

W/W1

Y/Y2

O/W2

RVS COOLING

C

B

S1

S2

SUPPLEMENTAL

HEATING

RELAY

CARRIER

PROGRAMMABLE

THERMOSTAT

MODEL HP

FA, FB, FC, FH

FAN COIL WITH

SMART HEAT

 HEAT 
PUMP

Y1/W2

L

R

C

Y

G

O

W2T

W3

W2D

Y

0

R

C

O

W2

Y

INDOOR FAN

HEAT STAGE 2

COOL/HEAT
STAGE 1

NOT USED

24 VAC COM

NOT USED

TROUBLE 

OPTIONAL
OUTDOOR
SENSOR
CONNECTION

CUT
JW1

  

SHR

  

SHR

  

ODT

A97541

24 VAC HOT

R

G

W/W1

Y/Y2

O/W2

RVS COOLING

C

B

S1

S2

CARRIER

PROGRAMMABLE

THERMOSTAT

MODEL HP

FA, FB, FC, FH

FAN COIL WITH

SMART HEAT

HEAT 

PUMP

Y1/W2

L

R

C

Y

G

O

W2T

W3

W2D

Y

0

R

C

O

W2

Y

INDOOR FAN

HEAT STAGE 2

COOL/HEAT
STAGE 1

NOT USED

24 VAC COM

NOT USED

TROUBLE 

OPTIONAL
OUTDOOR
SENSOR
CONNECTION

JW1

A98631

24 VAC HOT

R

G

W/W1

Y/Y2

Y/Y2

Y1/W2

R

DH

RVS COOLING

C

B

L

S1

S2

Y

W2

CARRIER

PROGRAMMABLE

THERMOSTAT

MODEL 2S

40FKA

FK4C

FAN COIL

 HEAT 

PUMP

G

O

O/W2

W2

Y1

C

W1

R

O

24 VAC COMM

HEAT STAGE 2

HEAT STAGE 3

COOL/HEAT
STAGE 1

FAN

RVS HEATING

TROUBLE

OUTDOOR
SENSOR
CONNECTION

C

J1 JUMPER

REMOVE
J2 JUMPER
FOR HEAT
STAGING

Intelligent Sequencing Application:  Model 2S thermostat with 
switch C OFF and switch D ON uses single-speed heat pump, 
FK4 or 40FKA fan coil with selected 2:1 size ratio heaters.  Provides 3 
stages of auxiliary heat for even heating comfort via W/W1 
and Y1/W2.  Refer to FK4 or 40FKA Installation Instructions.

A97542

24 VAC HOT

R

G

W/W1

Y/Y2

O/W2

RVS COOLING

C

B

S1

S2

CARRIER

PROGRAMMABLE

THERMOSTAT

MODEL HP

ONE

OUTDOOR

THERMOSTAT

 HEAT 
PUMP

Y1/W2

L

R

C

Y

G

O

W2T

W3

W2D

Y

0

R

C

O

W2

Y

INDOOR FAN

HEAT STAGE 2

COOL/HEAT
STAGE 1

NOT USED

24 VAC COM

NOT USED

TROUBLE 

OPTIONAL
OUTDOOR
SENSOR
CONNECTION

CUT
JW1

  

ODT

FA, FB, FC, FH

FAN COIL WITH

SMART HEAT

7

Summary of Contents for 38YKC Series

Page 1: ...y from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly a...

Page 2: ...ications locate unit at least 6 in above roof surface Step 4 Operating Ambients The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode...

Page 3: ...f refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDO...

Page 4: ...ctric shock fire or death CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 7 CONNECT CONTROL WIRING R...

Page 5: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Page 6: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Page 7: ...24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN...

Page 8: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Page 9: ...JUMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 12 Typical 24 v Cir...

Page 10: ...rgized Cooling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor f...

Page 11: ...ocedure is valid when indoor airflow is within 21 of its rated CFM 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure suction pressure by attaching a gage to suction valve service...

Page 12: ...R TEMPERATURE F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65 6 10 13 16 19 21 24 27 30 33 36 38 41 70 7 10 13...