17
Heat pump heating performance continued
† The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from sup-
plement heaters should be added to those values to obtain total system capacity.
‡ The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these
values to obtain total system kw’s.
EDB—Entering Dry Bulb
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55
°
F (12.8
°
C).
3. Maximum outdoor operating air temperature for cooling mode is 125
°
F (51.7
°
C), except some 3 phase models is 115
°
F (46.7
°
C).
4. Minimum outdoor operating air temperature for heating mode is –30
°
F (–34.4
°
C).
5. Maximum outdoor operating air temperature for heating mode is 66
°
F (18.9
°
C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and 9
following.)
8. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.
9. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical
rise to the valve connections at the unit.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
∞
F
–3
7
17
27
37
47
57
67
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
EDB
CFM
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
Total Integ† Kw‡
38YCA060-32, 52, 62, 33, 53, 63 Outdoor Section With F(A,B)4AN(F,B)060 Indoor Section
65
1800
2000
2200
30.0
30.4
30.8
27.6
27.9
28.3
4.24
4.31
4.38
34.6
35.0
35.4
31.8
32.2
32.5
4.37
4.43
4.49
39.4
39.9
40.2
36.0
36.3
36.7
4.51
4.55
4.60
44.9
45.4
45.8
39.9
40.3
40.7
4.67
4.70
4.74
50.7
51.2
51.7
46.2
46.6
47.0
4.85
4.88
4.91
58.1
58.7
59.2
58.1
58.7
59.2
5.12
5.13
5.16
66.6
66.4
66.2
66.6
66.4
66.2
5.47
5.42
5.40
71.9
71.1
70.4
71.9
71.1
70.4
5.69
5.61
5.57
70
1800
2000
2200
29.4
29.9
30.3
27.1
27.5
27.9
4.38
4.45
4.52
34.3
34.7
35.1
31.5
31.9
32.2
4.54
4.59
4.65
39.1
39.5
39.9
35.6
36.0
36.4
4.68
4.72
4.78
44.5
44.9
45.4
39.5
39.9
40.3
4.85
4.88
4.93
50.2
50.7
51.2
45.7
46.1
46.5
5.05
5.07
5.10
57.4
58.0
58.5
57.4
58.0
58.5
5.32
5.33
5.36
66.1
66.3
66.1
66.1
66.3
66.1
5.70
5.66
5.63
72.1
70.9
69.9
72.1
70.9
69.9
5.97
5.84
5.78
75
1800
2000
2200
28.9
29.3
29.8
26.5
27.0
27.4
4.53
4.59
4.66
33.9
34.3
34.7
31.2
31.5
31.9
4.71
4.76
4.82
38.7
39.2
39.5
35.3
35.7
36.0
4.87
4.91
4.96
44.1
44.5
44.9
39.2
39.5
39.9
5.05
5.08
5.11
49.7
50.2
50.6
45.2
45.7
46.1
5.25
5.27
5.30
56.8
57.3
57.8
56.8
57.3
57.8
5.54
5.54
5.56
65.5
66.1
66.0
65.5
66.1
66.0
5.94
5.93
5.88
72.2
72.3
70.8
72.2
72.3
70.8
6.26
6.20
6.08
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4AN(F,B)
060
1.00
1.00
CD3(A,B)A
060
0.97
1.05
FB4ANB
070
0.98
0.94
CC5A/CD5A/CD5BW
060
0.97
0.99
FG3AAA
060
0.97
1.00
CE3AA
060
0.97
0.98
CC5A/CD5A/CD5BA
060
0.97
1.05
—
—
—