7
Electrical data
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† Time-delay fuse.
‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30
°
C (86
°
F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable
(NM), trade name ROMEX, shall be that of 60
°
C (140
°
F) conductors, per the NEC (ANSI/NFPA 70) Article 336-36.
If other than uncoated (non-plated), 60
°
or 75
°
C (140
°
or 167
°
F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
NOTE:
Control circuit is 24v on all units and requires external power source. Copper wire must be used from disconnect to unit. All motors/compressors contain
internal overload protection. Model Size 042 MCA value greater than 048 due to UL testing.
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning, Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
RLA
— Rated Load Amps
OUTDOOR
UNIT
V/PH
60 Hz
OPER VOLTS*
COMPR
FAN
FLA
MCA
MIN WIRE
SIZE**
60
°
C/75
°
C
MAX
LENGTH
(Ft)‡
60
°
C/75
°
C
MAX FUSE†
OR HACR
TYPE CKT
BKR AMPS
Max
Min
LRA
RLA
018-33, 34
208-230/1
253
197
49.0
9.8
0.5
12.8
14/14
70/70
20
024-35
61.0
11.4
0.5
14.8
14/14
50/45
20
024-36
61.0
11.7
0.5
15.1
14/14
50/45
20
030-36
73.0
14.7
1.4
19.8
14/14
35/35
30
030-37
75.0
13.7
1.4
18.5
14/14
40/40
30
036-36
105.0
18.0
1.4
23.9
12/12
50/50
35
036-37
92.0
17.5
1.4
23.3
12/12
50/50
35
042-32
124.0
27.8
1.4
36.2
8/8
80/80
50
042-33
129.0
28.0
1.4
36.4
8/8
80/80
50
048-32
140.0
24.4
1.4
31.9
8/8
90/90
50
048-33
129.0
23.7
1.4
31.0
8/8
95/90
50
060-32
165.0
30.8
1.4
39.9
8/8
75/70
60
060-33
169.0
30.8
1.4
39.9
8/8
75/70
60
030-57
208/230/3
253
187
68.0
9.0
1.4
12.7
14/14
70/65
15
036-56
90.0
11.4
1.4
15.7
14/14
50/50
20
036-57
75.0
11.0
1.4
15.2
14/14
50/50
20
042-52
92.0
16.4
1.4
21.9
12/12
60/60
30
042-53
99.0
15.9
1.4
21.3
12/12
60/60
30
048-52
105.0
14.1
1.4
19.0
14/14
40/40
25
048-53
99.0
13.5
1.4
18.3
14/14
45/40
25
060-52
123.0
17.0
1.4
22.9
12/12
55/55
35
060-53
123.0
18.5
1.4
24.5
12/12
55/55
35
036-66
460/3
506
414
45.0
6.2
0.8
8.6
14/14
95/95
15
036-67
37.5
5.6
0.8
7.8
14/14
95/95
15
042-63
49.5
8.7
0.8
11.7
14/14
140/140
15
048-62
52.5
7.1
0.8
9.7
14/14
145/145
15
048-63
49.5
7.4
0.8
10.1
14/14
145/145
15
060-62
66.5
8.5
0.8
11.4
14/14
130/130
15
060-63
62.0
9.6
0.8
12.8
14/14
130/130
20