Control Module (CM) Operation

When voltage is applied the power LED (DSI) will continuously flash 1/4 second off. The module starts a 3-minute
compressor delay timer. This delay can be bypassed by pressing the override switch for at least 1/2 second. The
Status LED (DS3) must be flashing or the override switch will not function.
On a call for cooling, the control module checks for 24vac to be present at T1 for a period of 7 seconds. It also
checks that the 3-minute compressor delay has clasped or overridden and also checks the state of the HPS/COTP. If
on alarms are detected  nor delays are active the module will energize the compressor contactor relay. A timer is
started to provide minimum 3½  minute compressor run period.

During compressor operation the module continuously checks the HPS/COTP state ( Status  LED ( DS3)and K1 LED
(DS4) are ”NO” steady). If the circuit poens  (24 vac not present at T7) the module will  immediately  shut down the
compressor and display the alarm Alarm LED (DS2) “ON” steady ). Power must be cycled to restore normal control
operation.

The OPS state is ignored during the first 60 seconds of operation .After this time if the OPS is open (24 vac not
present at T9) the compressor will be shut down. Alarm LED (DS2) displays the state of the OPS. A double blink (2-
1/4 ) second blinks, I second 0ff) indicates the OPS is open . If the OPS opens during operation and remains open for
longer that 60 seconds the module will lockout unit operation and display the alarm. Power must be cycled to restore
normal control operation.

The LPS is monitored during a call  for cooling . The LPS is ignored during the first 2 ½ minutes of operation . The
Alarm LED (DS2) displays the state of the LPS. A single blink (1/4 second on, 1 second off) indicates that the LPS is
open. If the LPS remains open after 2 ½ minutes or opens later during the call for cooling (24 vac not  present at
T11) the module shuts down the compressor. The 3-minute compressor delay is started and the cycle repeats. If the
call for cooling remains and this LPS cycle is repeated 3 times the module will lock out and display the alarm. Power
must be cycled to restore normal control operation.

When the call for cooling is satisfied and the compressor has run for at least 3 ½ minutes the module shuts off the
compressor. The CM stats the 3-minute compressor delay timer.

Summary of Contents for 38AF Series

Page 1: ...Installation Manual...

Page 2: ...nstalling starting up and servicing air conditioning equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualifie...

Page 3: ......

Page 4: ...V Ph Hz 380 3 50 Operating Current Amp 44 05 54 84 59 38 85 12 108 68 120 42 Model 06E2250611 06E2265611 06E627506 06E6299681 06E2265611 06E627506 Type Semi Hermetic Reciprocating Quantity 1 1 1 1 2 2...

Page 5: ...d a o l n U y B l o r t n o C p e t S y t i c a p a C Starter Electrical Controls Type Pre Charging from Factory kg 5 9 1 x 2 6 3 1 x 2 0 5 9 2 0 5 9 1 0 6 3 1 0 7 2 1 g k g n i g r a h C n o i t a r...

Page 6: ...38AE020 040 38AF020 040 38AE050 060 38AF050 060 Dimension...

Page 7: ...rom above to lift unit from the rails or pad when unit is in final position COMPRESSOR MOUNTING As shipped the compressor is held tightly in place by self locking bolts Before starting unit loosen sel...

Page 8: ...brazing to prevent formation of copper oxide Install field supplied thermostatic expansion valve s in indoor section If 2 thermostatic expansion valves are installed for 2 step cooling install field...

Page 9: ...least within sight in the compressor sight glass Add oil if necessary see Tables l 2 Compressor hold down bolts must be snug but not tight Refer to Compressor Mounting section and tag on compressor f...

Page 10: ...se Heater The heater prevents refrigerant migration and compressor oil dilution during shutdown whenever compressor is not operating It is wired into the control circuit and cycles with the compressor...

Page 11: ...2 rows of fins 38AE020 or 3 rows of fins 38AE010 015 025 060 and restrict outdoor airflow Use a flashlight to determine if dirt or debris has collected between coil sections Clean coil as follows 1 T...

Page 12: ...e s replace with correct type and size 4 Check thermostat setting 5 Check Time Guard ll devices 6 Check for excessive compressor current draw Reset breaker replace if defective 7 Reset lockout circuit...

Page 13: ...ity control solenoid valve if used 3 Miswired capacity control liquid line solenoid if used 4 Weak broken or wrong valve body spring COMPERSSOR WILL NOT LOAD 1 Miswired capacity control liquid line so...

Page 14: ...14 38AE020 38AF020 Wiring Diagram...

Page 15: ...15 Wiring Diagram 38AE025 030 040 38AF025 030 040...

Page 16: ...16 Wiring Diagram 38AE050 060 38AF050 060...

Page 17: ...state is ignored during the first 60 seconds of operation After this time if the OPS is open 24 vac not present at T9 the compressor will be shut down Alarm LED DS2 displays the state of the OPS A do...

Page 18: ...ned y n ____________ Is the oil level in each compressor crankcase visible in the compressor sight glasses y n ____________ Check Voltage Imbalance Line to line volts ab____v ac____v bc_____v ab ac bc...

Reviews: