background image

12

TROUBLESHOOTING PROBLEM 

Problem Solution

COMPRESSOR DOES NOT RUN 

Contractor Open

1. Power 

off. 

2. 

Fuses blown in field power circuit. 

3. 

No control power. 

4. 

Thermostat circuit opens. 

5. 

Time Guard ll device not operating. 

6. 

Compressor circuit breaker tripped. 

7. 

Safety device lock-out circuit 
active.

8. 

Low-pressure switch opens. 

9. 

High-pressure switch open. 

10.  Compressor over temperature 

switch open. 

11. Loose 

electrical 

connections. 

12. Compressor 

stuck. 

Contractor Closed 

1. Compressor 

leads 

loose. 

2. Motor 

windings 

open. 

3. Single 

phasing. 

COMPRESSOR STOPS ON HIGH-
PRESSURW SWITCH 

Outdoor Fan On

1. 

High-pressure switch faulty. 

2. 

Reversed fan rotation 

3. Airflow 

restricted. 

4. Air 

recalculating. 

5. 

Non condensable in system. 

6. Refrigerant 

overcharge. 

7. 

Line voltage incorrect. 

8. 

Refrigerant system restrictions. 

Outdoor Fan Off

1. 

Fan slips on shaft. 

2. Motor 

not 

running. 

3. Motor 

bearings 

stuck. 

4. 

Motor overload open. 

5. 

Motor burned out. 

COMPRESSOR CYCLES ON LOW-
PRESSURE SWITCH 

Indoor-Air Fan Running

1. 

Compressor suction service valve 
partially closed. 

2. 

Liquid line solenoid valve(s) fails to 
open.

3. 

Filter drier plugged. 

4. 

Expansion valve power head 
defective.

5. 

Low refrigerant charge. 

1. Restore 

power. 

2. 

After finding cause and correcting.  Replace with 
correct size fuse. 

3. 

Check secondary fuse(s); replace with correct type 
and size. 

4. Check 

thermostat 

setting. 

5. 

Check Time Guard ll devices. 

6. 

Check for excessive compressor current draw. 
Reset breaker; replace if defective. 

7. 

Reset lockout circuit at thermostat or circuit 
breaker.

8. 

Check for refrigerant undercharge, obstruction of 
indoor airflow, or whether compressor suction 
shutoff valve is fully open. Be sure outdoor fans 
are operating correctly. 

9. 

Check for refrigerant overcharge, obstruction of 
outdoor airflow, air in system. or whether 
compressor discharge valve is fully open. Be sure 
outdoor fans are operating correctly. 

10.  Check for open condition. Allow for reset. Replace 

if defective. 

11.  Tighten all connections. 
12. See 

compressor 

service 

literature. 

1. Check 

connections 

2. 

See compressor service literature. 

3. 

Check for blown fuse. Check for loose connection 
at compressor terminal. 

1. Replace 

switch. 

2. 

Confirm rotation, correct if necessary. 

3. Remove 

obstruction. 

4. 

Clear airflow area. 

5. 

Purge and recharge as required. 

6. 

Purge as required. 

7. 

Consult Power Company. 

8. 

Check or replace filter drier, expansion valve, etc. 
Check that compressor discharge service valve is 
fully open. 

1. 

Tighten fan hub set screws. 

2. 

Check power and capacitor. 

3. Replace 

bearings. 

4. 

Check overload rating. Check for fan blade 
obstruction.

5. Replace 

motor. 

1. Open 

valve 

fully. 

2. 

Check liquid line solenoids valve (s) for proper 
operation Replace if necessary. 

3. 

Replace filter drier. 

4. Replace 

power 

head. 

5. 

Add charge. Check low-pressure switch setting. 

Summary of Contents for 38AF Series

Page 1: ...Installation Manual...

Page 2: ...nstalling starting up and servicing air conditioning equipment can be hazardous due to system pressures electrical components and equipment location roofs elevated structures etc Only trained qualifie...

Page 3: ......

Page 4: ...V Ph Hz 380 3 50 Operating Current Amp 44 05 54 84 59 38 85 12 108 68 120 42 Model 06E2250611 06E2265611 06E627506 06E6299681 06E2265611 06E627506 Type Semi Hermetic Reciprocating Quantity 1 1 1 1 2 2...

Page 5: ...d a o l n U y B l o r t n o C p e t S y t i c a p a C Starter Electrical Controls Type Pre Charging from Factory kg 5 9 1 x 2 6 3 1 x 2 0 5 9 2 0 5 9 1 0 6 3 1 0 7 2 1 g k g n i g r a h C n o i t a r...

Page 6: ...38AE020 040 38AF020 040 38AE050 060 38AF050 060 Dimension...

Page 7: ...rom above to lift unit from the rails or pad when unit is in final position COMPRESSOR MOUNTING As shipped the compressor is held tightly in place by self locking bolts Before starting unit loosen sel...

Page 8: ...brazing to prevent formation of copper oxide Install field supplied thermostatic expansion valve s in indoor section If 2 thermostatic expansion valves are installed for 2 step cooling install field...

Page 9: ...least within sight in the compressor sight glass Add oil if necessary see Tables l 2 Compressor hold down bolts must be snug but not tight Refer to Compressor Mounting section and tag on compressor f...

Page 10: ...se Heater The heater prevents refrigerant migration and compressor oil dilution during shutdown whenever compressor is not operating It is wired into the control circuit and cycles with the compressor...

Page 11: ...2 rows of fins 38AE020 or 3 rows of fins 38AE010 015 025 060 and restrict outdoor airflow Use a flashlight to determine if dirt or debris has collected between coil sections Clean coil as follows 1 T...

Page 12: ...e s replace with correct type and size 4 Check thermostat setting 5 Check Time Guard ll devices 6 Check for excessive compressor current draw Reset breaker replace if defective 7 Reset lockout circuit...

Page 13: ...ity control solenoid valve if used 3 Miswired capacity control liquid line solenoid if used 4 Weak broken or wrong valve body spring COMPERSSOR WILL NOT LOAD 1 Miswired capacity control liquid line so...

Page 14: ...14 38AE020 38AF020 Wiring Diagram...

Page 15: ...15 Wiring Diagram 38AE025 030 040 38AF025 030 040...

Page 16: ...16 Wiring Diagram 38AE050 060 38AF050 060...

Page 17: ...state is ignored during the first 60 seconds of operation After this time if the OPS is open 24 vac not present at T9 the compressor will be shut down Alarm LED DS2 displays the state of the OPS A do...

Page 18: ...ned y n ____________ Is the oil level in each compressor crankcase visible in the compressor sight glasses y n ____________ Check Voltage Imbalance Line to line volts ab____v ac____v bc_____v ab ac bc...

Reviews: