7

Unit Configuration

Item

Value

Description

20

1 : Heat pump

Unit Configuration

0 : AC Only

(indoor unit with or without electric heaters)

Defaults to Heat Pump

21

1---199 in increments of 1

CCN Address of the unit
Defaults to 1
To display the hundreds, icon ON/OFF is

.

22

0 –199 in increments of 1

Zone number --- Communications zone the system is located in
Defaults to 0
To display the hundreds, icon ON/OFF is

.

24

0 : Start in Off Mode

Auto Restart

1 : Start in last mode

Defaults to “On”

This mode will exit automatically after 30 seconds of no buttons
being depressed.

NOTE

: If units are grouped to one Room Controller, all units will

end up having the same configuration value.

Service test mode

There is a hidden service test mode that is initiated through a

combination of button presses when the remote is off. The
following combination must be pressed within a 6 seconds period:

DOWN--FAN--UP--FAN--MODE

Once in service test mode, the service test mode message will be

sent, and “Sr“ will be displayed in the temperature icons until the
“DOWN“ button is pressed.
During Service Test mode all the icons are off, the only button that
is active is the “DOWN” button.
To cancel Service Test Mode, press the “DOWN“ button to send a

normal message with “OFF“ mode.
Service Test Mode automatically times out after 30 minutes and the

remote will operate normally.

S

When test mode is selected, the unit will operate as
described below:

The Unit Status (Green) and Timer (Yellow) LEDS
blink every 2 seconds.

The indoor fan will operate according to
user--selected speed. If user selected speed is Auto,
the fan will run in High speed.

If the unit is configured as an A/C Only unit, it will
operate in cool mode with demand.

S

The louver will operate according to user--selected
position. If user selected louver is Auto, louver operates

according to cool louver.

If the unit is configured as a Heat Pump unit, the
louver will operate according to user--selected

position. If user selected louver is Auto, louver
operates according to auto heat or cool louver based

on operating mode.
The unit will run in cool mode for 3 minutes, then it
will run in heat mode for 2 minutes, or until the

indoor coil is greater than 104

_

F. The unit will run

in cool mode until test mode is exited.

Any of the following will cancel the test Mode:

S

When the unit is turned off by the controller.

S

If the power is cycled during the Test Mode, the unit will
return to its normal operating mode.

S

After 30 minutes of receiving the last valid test request
message.

S

Fail Mode

Troubleshooting

Symptom

Possible Cause

Things to check

Solution

No LCD display

1) mis---wiring of the 12 volt power

to Room Controller control.

Verify that + 12 V and Ground are connected to

the proper terminals of the Controller.

Reference Installation wiring section for correct

connections

After disconnecting the

power, correct the wiring

problem and re---cycle

power.

2) Power not online

Check that the units main power is connected.

The main control board should be operating

normally

After verifying the wiring

to the Room Controller,

re---cycle the unit power.

3) No 12 volts between P and G of

terminal block.

Check the installation of the J6 plug on the

main control board.

After disconnecting the

power, correct the wiring

problem and re---cycle

power.

+12 volts applied to

Room Controller at

the correct terminals

and still does not

operate

1) The Room Controller is dam-

aged.

Change the Room Con-

troller and re---cycle pow-

er.

33MC

--

U

RC

Summary of Contents for 33MC-URC

Page 1: ...33MC URC INSTALLATION MANUAL 40QNC 40QNQ 40KMC 40KMQ Room Controller ...

Page 2: ...r accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to t...

Page 3: ...ceiver board connection on the electronic board inside the unit REMOTE FCU 6 FCU 3 FCU 2 FCU 1 Fig 9 Daisy Chain Wiring Multidrop POWER The thermostat will be powered by unregulated 12 5 volts DC nominal 10V min to 20V max which is provided by the electronic board inside the unit The power consumption will be 50mA 12 5 volts DC For applications where more than one FCU is to be controlled the FCU c...

Page 4: ...all with 2 screws and anchors provided additional anchoring holes available for more secure mounting if needed making sure all wires extend through hole in mounting base S Adjust length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 6 mm of extra wire strip only 1 4 6 mm of insulation from each wire to prevent adjacent wires from shorting...

Page 5: ...om Controller terminal block in the same way as shown in diagram 2 Wiring Materials required supplied by installer 1 small screwdriver Standard Double insulated wire recommended Unit Configuration Room Controller Configuration Setup To enter installer setup hold the MODE button down for 5 seconds After 5 seconds a 10 will appear This indicates that the user is setting the first software configurat...

Page 6: ...n This mode will exit automatically after 10 seconds of no buttons being depressed The only way to abort a louver change is to change the value back to its original value NOTE S If units are grouped to one Room Controller all units will end up having the same louver value S Louver Mode selection is not available during OFF mode Room Controller ON up down Keep it pressed for 5 seconds To change the...

Page 7: ...red as an A C Only unit it will operate in cool mode with demand S The louver will operate according to user selected position If user selected louver is Auto louver operates according to cool louver If the unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on...

Page 8: ... W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 33MC URC 1SI Replaces NEW Printed in U S A Edition Date 07 06 33MC URC ...

Reviews: