background image

3

General information and characteristics

IMPORTANT: Read the entire instruction manual before
starting the installation.

S

For trouble--free installation, which should be carried out
by a qualified installer, follow the installation chart
sequence.

S

Follow all current national safety code requirements. In
particular ensure that a properly sized and connected

ground wire is in place.

S

After installation, thoroughly test the system operation
and explain all system functions to the owner.

S

Leave this manual with the owner for consultation
during future periodic maintenance.

S

Dispose of packaging material in accordance with local
requirements.

S

The manufacturer denies any responsibility and warranty
shall be void if these installation instructions are not
observed.

S

Inspect equipment.

For damage due to improper

transportation or handling, file an immediate claim with
the shipping company.

Do not

install or use damaged

units.

S

In case of any malfunction, turn the unit off, disconnect
the main power supply and contact a qualified service

engineer.

WIRING

The Room Controller will be capable of controlling from 1 to 6
Fan Coil Units.
The total run length of the wire connecting the Room Controller to
the FCUs should be kept to under 500 feet (150 m.).
Only daisy chain wiring will be allowed (See Figure 1).

The Room Controller will connect to the receiver board connection
on the electronic board inside the unit.

REMOTE

FCU 6

FCU 3

FCU 2

FCU 1

Fig. 9 – Daisy Chain Wiring (Multidrop)

POWER

The thermostat will be powered by unregulated 12.5 volts DC

nominal (10V min. to 20V max) which is provided by the

electronic board inside the unit.
The power consumption will be 50mA 12.5 volts DC.
For applications where more than one FCU is to be controlled, the
FCU closest to the Room Controller will be the only one that

supplies power to the Room Controller.
The control should be protected from damage if accidental
miswiring of power, ground and signal.

Choosing the installation site and Installation

Room Controller Location

The Room Controller can be located anywhere. However, if the

installation requires the system in the location to use the air sensor
on the Room Controller; then, the controller should be mounted:

S

Approximately 5 ft. (1.5 m) from floor.

Fig. 10 – Minimum Clearances

S

In the same area where the unit is located, preferably on
an inside partitioning wall.

S

On a section of wall without pipes or duct work.

If the air sensor on the Room Controller has been selected, it

should

NOT

be mounted:

S

Close to a window, on an outside wall, or next to a door
leading to the outside.

S

Exposed to direct light and heat from a lamp, sun,
fireplace, or other temperature--radiating object which

may cause a false reading.

S

Close to or in direct airflow of a heating or cooling
supply.

S

In areas with poor air circulation, such as behind a door
or in an alcove.

Maximum of 500 ft. (150 m) of total network wiring.

33MC

--

U

RC

Summary of Contents for 33MC-URC

Page 1: ...33MC URC INSTALLATION MANUAL 40QNC 40QNQ 40KMC 40KMQ Room Controller ...

Page 2: ...r accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to t...

Page 3: ...ceiver board connection on the electronic board inside the unit REMOTE FCU 6 FCU 3 FCU 2 FCU 1 Fig 9 Daisy Chain Wiring Multidrop POWER The thermostat will be powered by unregulated 12 5 volts DC nominal 10V min to 20V max which is provided by the electronic board inside the unit The power consumption will be 50mA 12 5 volts DC For applications where more than one FCU is to be controlled the FCU c...

Page 4: ...all with 2 screws and anchors provided additional anchoring holes available for more secure mounting if needed making sure all wires extend through hole in mounting base S Adjust length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 6 mm of extra wire strip only 1 4 6 mm of insulation from each wire to prevent adjacent wires from shorting...

Page 5: ...om Controller terminal block in the same way as shown in diagram 2 Wiring Materials required supplied by installer 1 small screwdriver Standard Double insulated wire recommended Unit Configuration Room Controller Configuration Setup To enter installer setup hold the MODE button down for 5 seconds After 5 seconds a 10 will appear This indicates that the user is setting the first software configurat...

Page 6: ...n This mode will exit automatically after 10 seconds of no buttons being depressed The only way to abort a louver change is to change the value back to its original value NOTE S If units are grouped to one Room Controller all units will end up having the same louver value S Louver Mode selection is not available during OFF mode Room Controller ON up down Keep it pressed for 5 seconds To change the...

Page 7: ...red as an A C Only unit it will operate in cool mode with demand S The louver will operate according to user selected position If user selected louver is Auto louver operates according to cool louver If the unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on...

Page 8: ... W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 33MC URC 1SI Replaces NEW Printed in U S A Edition Date 07 06 33MC URC ...

Reviews: