General information and characteristics

MOUNTING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.

Before installing the Room Controller, turn off all power to

the Unit that will supply power to the Room Controller.

!

WARNING

S

Turn OFF all power to unit.

G

P

C

Fig. 11 – Mounting Screws

S

Unscrew the side fixing screw.

S

Open the Room Controller rear mounting base to expose
mounting holes. The base can be removed to simplify
mounting (snap apart carefully at hinge to separate
mounting base from remainder of the Room Controller).

S

Route the Room Controller wires through the large hole
in the mounting base. Level mounting base against wall
(for aesthetic value only the Room Controller need not

be level for proper operation) and mark the wall through
the 2 mounting holes.

S

Drill two 3/16” (5 mm) mounting holes in wall where
marked.

S

Secure mounting base correctly (

UP

) to wall with 2

screws and anchors provided, (additional anchoring

holes available for more secure mounting if needed)
making sure all wires extend through hole in mounting
base.

S

Adjust length and routing of each wire to reach the
proper terminal in the connector block on the mounting
base, with 1/4” (6 mm) of extra wire (strip only 1/4” (6

mm) of insulation from each wire to prevent adjacent
wires from shorting together when connected).

2

G

P

C

Fig. 12 – Connection Cable

S

Match and connect equipment wires to proper terminals
in the connector block. Both power and communication
wires must be connected correctly for proper Room

Controller operation.

2

G

P

C

Fig. 13 – Connection Cable

S

Push any excess wire into the wall and against mounting
base.

If the air sensor is being used on the Room Controller,
seal hole in wall to prevent air leaks.
Leaks can affect sensor operation.

3

4

5

6

7

3 To indoor Unit

4 Rigid PVC conduit inside

1--3/16” (30 mm) min.

5 Plaster approx. 1--3/16” (30 mm)

6 Room Controller

7 Connector block

Fig. 14 – Mounting location

S

Push the Room Controller snap hinge to the base.

S

Tighten the side fixing screw.

33MC

--

U

RC

Summary of Contents for 33MC-URC

Page 1: ...33MC URC INSTALLATION MANUAL 40QNC 40QNQ 40KMC 40KMQ Room Controller ...

Page 2: ...r accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to t...

Page 3: ...ceiver board connection on the electronic board inside the unit REMOTE FCU 6 FCU 3 FCU 2 FCU 1 Fig 9 Daisy Chain Wiring Multidrop POWER The thermostat will be powered by unregulated 12 5 volts DC nominal 10V min to 20V max which is provided by the electronic board inside the unit The power consumption will be 50mA 12 5 volts DC For applications where more than one FCU is to be controlled the FCU c...

Page 4: ...all with 2 screws and anchors provided additional anchoring holes available for more secure mounting if needed making sure all wires extend through hole in mounting base S Adjust length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 6 mm of extra wire strip only 1 4 6 mm of insulation from each wire to prevent adjacent wires from shorting...

Page 5: ...om Controller terminal block in the same way as shown in diagram 2 Wiring Materials required supplied by installer 1 small screwdriver Standard Double insulated wire recommended Unit Configuration Room Controller Configuration Setup To enter installer setup hold the MODE button down for 5 seconds After 5 seconds a 10 will appear This indicates that the user is setting the first software configurat...

Page 6: ...n This mode will exit automatically after 10 seconds of no buttons being depressed The only way to abort a louver change is to change the value back to its original value NOTE S If units are grouped to one Room Controller all units will end up having the same louver value S Louver Mode selection is not available during OFF mode Room Controller ON up down Keep it pressed for 5 seconds To change the...

Page 7: ...red as an A C Only unit it will operate in cool mode with demand S The louver will operate according to user selected position If user selected louver is Auto louver operates according to cool louver If the unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on...

Page 8: ... W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 33MC URC 1SI Replaces NEW Printed in U S A Edition Date 07 06 33MC URC ...

Reviews: