Unit Configuration

5.

Configuration Item 10 — Heat pump Vs Cooling mode

H -- The Room Controller will allow and display the

following modes: Off, Fan, Auto, Cool, Dry, and Heat.

C -- The Room Controller will allow and display the

following modes: Off, Fan, Cool, and Dry.

6.

Configuration Item 11 — Room thermistor override

On-- Room Thermistor Override active. Units will be

controlled to the air temperature read in at the Room

Controller.

OF-- Room Thermistor Override not active.

All units will be controlled to the room air thermistors

located on their own respective units.

7.

Configuration Item 12 — Celsius Vs Fahrenheit

C -- Indicates that all temperatures will be displayed in

degrees C.

F -- Indicates that all temperatures will be displayed in

degrees F.

Keep it pressed for

at least 5 seconds

Check the

value

Change the

value

up

down

Next

item

To check/change

the values of items

11 and 12 go back

to point

A

A

up

down

Fig. 15 – Unit Configuration Setup

Louver Mode Selection

To enter louver mode selection, make sure the Room Controller is

on and hold the “FAN” SPEED button down for 5 seconds. After 5
seconds, the selected louver setting will be displayed. Depressing

the up and down arrows will allow the user to modify the louver
setting between swing and auto.
The two setting will be displayed in the following way:

“S“ with Swing Louver Icon

-- represents Swing Louver.

“A” with Auto Louver Icon

-- represents Auto Louver.

The fan icon shall also be displayed in the louver mode. Press
“FAN” SPEED button to exit LOUVER Mode Selection. This

mode will exit automatically after 10 seconds of no buttons being
depressed.
The only way to abort a louver change, is to change the value back

to its original value.

NOTE

:

S

If units are grouped to one Room Controller , all units will end
up having the same louver value.

S

Louver Mode selection is not available during

OFF

mode.

Room Controller

ON

up

down

Keep it pressed

for 5 seconds

To change

the value

Automatic

(AUTO)

Or

Continuous

movement

(swing)

Fig. 16 – Louver Mode Selection

8.

New DFS Modular Platform D Unit configuration

To enter New DFS Modular Platform D unit configuration, hold

the “UP“ and “DOWN“ buttons down together for 5 seconds while
the Room Controller is in off mode. After 5 seconds, a “20“ will

appear.
This indicates that the user is setting the first software

configuration item. To check the value of configuration item “20“,

press the “MODE” button.
The value for the New DFS Modular Platform D Heat Pump / AC

Only configuration will be displayed. To change the value, use the
“UP“ and “DOWN“ buttons. Once the value that you want is

selected, press the fan button to send that configuration data to the

unit.

Only the current value being displayed is transmitted. Once the
“FAN” button is pressed, the Room Controller will switch to

displaying the configuration index.
To move to the next setting, press the “MODE” button again and

the “20“ will be displayed.
Press the “UP“ button and the display will change to “21“. The
”MODE” button will toggle the display between the software

configuration index (i.e. “20“, “21“, etc.) and the configuration
value.
The“UP”/”DOWN” buttons will change either the index or the

value, which ever is displayed at the time.
Unit Configuration items 20--24 are available at this point.

33MC

--

U

RC

Summary of Contents for 33MC-URC

Page 1: ...33MC URC INSTALLATION MANUAL 40QNC 40QNQ 40KMC 40KMQ Room Controller ...

Page 2: ...r accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to t...

Page 3: ...ceiver board connection on the electronic board inside the unit REMOTE FCU 6 FCU 3 FCU 2 FCU 1 Fig 9 Daisy Chain Wiring Multidrop POWER The thermostat will be powered by unregulated 12 5 volts DC nominal 10V min to 20V max which is provided by the electronic board inside the unit The power consumption will be 50mA 12 5 volts DC For applications where more than one FCU is to be controlled the FCU c...

Page 4: ...all with 2 screws and anchors provided additional anchoring holes available for more secure mounting if needed making sure all wires extend through hole in mounting base S Adjust length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 6 mm of extra wire strip only 1 4 6 mm of insulation from each wire to prevent adjacent wires from shorting...

Page 5: ...om Controller terminal block in the same way as shown in diagram 2 Wiring Materials required supplied by installer 1 small screwdriver Standard Double insulated wire recommended Unit Configuration Room Controller Configuration Setup To enter installer setup hold the MODE button down for 5 seconds After 5 seconds a 10 will appear This indicates that the user is setting the first software configurat...

Page 6: ...n This mode will exit automatically after 10 seconds of no buttons being depressed The only way to abort a louver change is to change the value back to its original value NOTE S If units are grouped to one Room Controller all units will end up having the same louver value S Louver Mode selection is not available during OFF mode Room Controller ON up down Keep it pressed for 5 seconds To change the...

Page 7: ...red as an A C Only unit it will operate in cool mode with demand S The louver will operate according to user selected position If user selected louver is Auto louver operates according to cool louver If the unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on...