Ductable air-cooled scroll 

chillers and heat pumps

27

-  Verify the absence of any leaks of the refrigerant. In the event of a leak:

•  Completely empty the unit using a speci

fi

 c recovery unit for R-410A 

and repair the leak. 

•  Next, reload the gas into the unit according to load data provided 

in the technical characteristics table and in the unit's data plate.

•  Add the refrigerant via the schrader valve of the liquid line, whilst 

the compressor is in operation, monitoring the pressures should 
there be any anomaly. 

Cooling MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air 

condenser

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Water 

evaporator

Water inlet temperature

ºC

Water outlet temperature

ºC

Liquid inlet temperature

ºC

Evaporator outlet temperature (4) ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Heating MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air 

evaporator

Liquid inlet temperature

ºC

Gas outlet temperature (4)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Water 

condenser

Water inlet temperature

ºC

Water outlet temperature

ºC

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Possible problems at commissioning

All  indications  given  in  this  brochure  must  be  respected  and 

complied with to guarantee a correct operation of the units.

Next, several possible operation problems are stated which could 
happen if the conditions of the commissioning are not appropriate.
- Insuf

fi

 cient water 

fl

 ow. Very high temperature differences between 

water inlet into and outlet from the unit caused by:

•  Insuf

fi

 cient air bleeding.

•  Small water circulation pump or anti-clockwise rotation.

•   Other situations which may prevent correct water circulation.

- Insuf

fi

 cient thermal charge in the installation. The limiting operating 

values are quickly reached by:

•   Incorrect  operation  of  the  emissions  system  (fan  coils,  air 

conditioning exchangers, etc.).

-  Air recirculation in the unit, originated by some obstacle in the air 

aspiration or supply.

Operational checks

Check the unit operation by verifying the electronic control and the 
safety devices.
It is also recommendable to create a report, taking note of the date, 
which includes the following information: 
-  the nominal voltage, 
-  current absorbed by the compressors, fans and other electrical 

components, 

- signi

fi

 cant temperatures in the cooling circuit (see attached table), 

-  other aspects considered interesting such as alarms detected by the 

electronic control of the unit. 

The recording of these parameters whilst the unit is running allows 
controlling the installation performance and it is the best possible way 
to avoid breakdowns since the analysis of these data makes early 
detection of anomalies possible or the provision of the necessary means 
available to ensure that they do not take place.

Schrader valve for 

refrigerant load

Summary of Contents for 30PA

Page 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Page 2: ......

Page 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Page 4: ......

Page 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Page 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Page 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Page 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Page 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Page 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Page 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Page 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Page 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Page 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Page 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Page 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Page 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Page 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Page 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Page 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Page 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Page 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Page 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Page 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Page 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Page 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Page 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Page 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Page 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Page 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Page 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Page 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...

Page 33: ...ulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction __________Discharge ________ Diff _______ Unit Inlet_____________Outlet________...

Page 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...

Page 35: ......

Page 36: ...Order No 10057 06 2016 Supersedes order No 08 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: