Ductable air-cooled scroll 

chillers and heat pumps

22

Cooling recovery circuit (optional)

The system consists in a hot water supplying by an heat recovery 
system on the compressor(s) discharge gas, on an auxiliary 
desuperheater exchanger.
On an heat pump model, the optional desuperheater can be used 
whatever the running mode, COOLING or HEATING.
This optional equipment is only available on request, and factory 
mounted.

 Operating  mode

The heat recovery is possible only if the unit is running, on COOLING 
mode or on HEAT PUMP mode.
For the same cooling or heating capacity, the desuperheater system 
allows a free heating of hot water with a reduction of the total input 
power of the unit.

 Principle and precaution of hydraulic connection

In order to allow the unit to start up and to run under good conditions, 
the circuit must be as short as possible, and the water 

fl

 ow of the 

desuperheater must start slowly to normal operating condition, with a 
water 

fl

 ow equal to 10% of its standard value, and must be calculated 

for a hot water inlet temperature of +50°C.
Thus, it is recommended to have a hydraulic diagram making it possible 
to obtain very quickly a hot water at the inlet of the desuperheater (3 ways 
valve + cont temperature sensor on the exchanger water inlet).
The controller set point must be adjusted to +50°C minimum.
The recovery circuit must be done in accordance with the standards 

in force and plan all of the necessary elements in a closed circuit: 
circulation pump (optionally supplied), expansion vessel, safety valve, 
mesh 

fi

 lter, 

fi

 ller, drainer, bleeders, thermometers, pressure gauges and 

cut-off and insulation valves.
The circulation pump can only work in a closed circuit. The command 
is performed from a thermostat located on the unit.
Attention: a detailed attention must carried with the selection of the 
expansion tank, because the recovery water circuit can reach the 
temperature of 120°C in the event of stopping of the circulator or non 
hot water consumption.
-  Install heating elements on all pipes that could be exposed to freezing 

temperatures.

PLATES

EXCHARGER

EXPANSION

VESSEL

ELECTRICAL

HEATER

MESH

FILTER

VA

SHUT-OFF

LVE

DRAINAGE

CIRCUIT

SAFETY

VALVE

NO RETURN

-

VALVE

VA

AIR BLEEDER

LVE

THERMOMETER

MANOMETER

CIRCULATOR

PUMP

FILLED

CIRCUIT

3-WAY

VALVE

FLEXIBLE

CONNECTION

Agua de red

A consumo

Opcional

30PA/PH

Min. 50ºC

 Technical characteristics of the recovery circuit

30PA/PH/PAC/PHC

STD version

HEE version

90STD

100STD 120STD 160STD 180STD 90HEE

100HEE

120HEE

160HEE

180HEE

Recovery capacity 

 (kW)

4,4

5,2

6,2

8,1

8,9

4,5

5,2

6,3

7,7

8,8

Nominal water 

fl

 ow (m

3

/h)

0,38

0,45

0,53

0,70

0,76

0,39

0,44

0,54

0,67

0,76

Pressure drop (m.w.c.)

0,06

0,09

0,17

0,30

0,36

0,07

0,09

0,18

0,27

0,35

Cooling capacity (kW)

17,8

21,3

25,3

33,0

36,2

18,5

21,1

25,6

31,6

35,8

Power input (kW)

6,8

7,9

8,6

10,8

12,7

6,2

7,1

7,8

10,0

11,9

Hydraulic 

connections

Type

Threaded

Threaded

Diameter

1” M 

1” M 

Pump

(optional)

Type

Humid rotor

Humid rotor

Number

1

1

Motor output (kW)

0,05

0,05

Max. absorbed current (A)

0,4

0,4

Avail. pressure (m.w.c.) 

(max. pump speed) 

5,54

5,45

5,35

5,15

5,07

5,52

5,46

5,34

5,19

5,07

Additional 

weight

Recovery circuit (kg)

5,3

5,3

6,8

6,8

6,8

5,3

5,3

6,8

6,8

6,8

Pump (optional) (kg)

3,2

3,2

 

Capacity recovered by the desuperheater circuit for nominal conditions and recovery water at 50/60ºC.

 



The change of speed of the pump is made by a button that changes color according to the selected speed (blue: low; green: medium; yellow: high).

Summary of Contents for 30PA

Page 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Page 2: ......

Page 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Page 4: ......

Page 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Page 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Page 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Page 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Page 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Page 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Page 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Page 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Page 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Page 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Page 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Page 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Page 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Page 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Page 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Page 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Page 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Page 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Page 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Page 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Page 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Page 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Page 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Page 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Page 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Page 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Page 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Page 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...

Page 33: ...ulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction __________Discharge ________ Diff _______ Unit Inlet_____________Outlet________...

Page 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...

Page 35: ......

Page 36: ...Order No 10057 06 2016 Supersedes order No 08 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: