Ductable air-cooled scroll 

chillers and heat pumps

6

4. A

VAILABLE

 

CONFIGURATIONS

According to the air supply: 

•  Assembly M00

 

  HORIZONTAL air supply.

•  Assembly M01

 

  VERTICAL air supply.

According to the type of supply fan:

•  STD version (Standard):

  

Centrifugal fan coupling by pulleys and belts. 

•  HEE version (High Energy Ef

fi

 ciency):

 

Variable speed electronic plug-fan. 

M00

M01

STD

HEE

These units work with refrigerant gas 

R-410A

3. S

AFETY

 

ADVICE

To avoid any risk of accident during installation, commissioning or 
maintenance, it is obligatory to take into consideration the following 
speci

fi

 cations for the units: refrigerated circuits under pressure, refrigerant 

presence, electrical voltage presence and implantation place.

Because of all of this, only quali

fi

 ed and experienced personnel can 

perform maintenance tasks or unit repairs. 

It is required to follow the recommendations and instructions 
in the maintenance brochures, the labels, and the speci

fi

 c 

instructions. 
It is necessary to comply with the norms and regulations 
in effect. It is recommended to consult the competent 
authorities regarding the applicable regulations for users 
of units or components under pressure. The characteristics 
of these units or components are included on the plates of 
characteristics or in the regulatory documentation provided 
with the product.

In case of a leak:
-  Toxicity: According to ASHRAE 34, R-410A belongs to the A1/A1 group, 

i.e. with high safety both in the mix and also in the case of a leak. 

-  Although it is not toxic, in case of a leak to atmospheric pressure the 

liquid phase evaporates. The resulting vapours are heavier than air 
and can displace the technician local air. In case of an accidental 
discharge in a closed enclosure, fans must be used to eliminate said 
vapours.

-  Although the R-410A is not 

fl

 ammable, when in contact with a 

fl

 ame 

o hot spot it can decompose in 

fl

 uorhydric acid HF and 

fl

 uophosgene 

COF

2

 highly toxic and corrosive.

-  To detect leaks, an electronic leak detector, an ultraviolet lamp or 

soapy water must be used. Flame detectors do not help.

Important

: Immediately repair any refrigerant leak, using 

a recovery unit speci

fi

 c for R-410A that avoids a possible 

mixture of refrigerants and/or oils.

The compressor and line surfaces can reach temperatures 
above 100ºC causing burns to the body. In the same fashion, 
under certain conditions these surfaces can reach very cold 
temperatures that can cause freezing risks.

Use safety goggles and gloves on the job. Be careful with 
sharp parts or elements in the unit. 

V-220005

V-220004

Caution: 

Before intervening in the unit, verify that the main 

power to the unit is cut off. An electric shock can cause 
personal damage.

Refrigerant leaks:

A periodical check must be performed for refrigerant gas leaks as 
per Regulation (CE) Nº517/2014 over 

certain greenhouse effect 

fl

 uoride gases. 

Please, consult the frequency of checks in chapter 

of “Maintenance”.

Components of the R-410A

R-32

R-125

Chemical formula

CH2F2

CHF2CF3

Weight ratio

50%

50%

Unitary global warming potential (GWP) 

675

3.500

Global warming potential (GWP) 

2.088

Note:

 In order to recycle these units follow the stipulations 

of Directive 2012/19/EU on

 Waste electrical and electronic 

equipment

 (WEEE).

Summary of Contents for 30PA

Page 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS 30PA PH PAC PHC Nominal cooling capacity 17 7 36 0 kW Nominal heating capacity 21 8 42 6 kW 50 Hz Ductable air cooled scroll chillers and heat pumps Original...

Page 2: ......

Page 3: ...rage for silent blocks 12 Sound level 12 9 Checking before commissioning 13 Electrical connections 13 Checks in the centrifugal fan STD version 14 Checks on the plug fan HEE version 14 Air ducts conne...

Page 4: ......

Page 5: ...two versions STD Standard HEE High Energy Efficiency These units have been made for operation indoors in the production of hot and or cold water applicable to heating cooling and industry They are equ...

Page 6: ...in case of a leak to atmospheric pressure the liquid phase evaporates The resulting vapours are heavier than air and can displace the technician local air In case of an accidental discharge in a clos...

Page 7: ...kW 7 31 8 90 9 90 12 90 14 20 Net efficiency COP 2 97 2 94 3 00 2 97 3 01 Seasonal efficiency Average climate SCOP 3 11 3 12 3 07 2 95 2 95 s Heat 121 122 120 115 115 Prated kW 16 77 19 19 21 82 26 3...

Page 8: ...foss POE 160 SZ ICI Emkarate RL 32 CF Mobil EAL Artic 22 CC Volume of oil l 3 0 3 3 3 3 3 3 6 2 Refrigerant Type R 410A Global warming potential GWP 2 088 Charge kg 6 0 6 3 6 8 8 9 9 2 Environment imp...

Page 9: ...tained in accordance with the calculation conditions established by the certification body EUROVENT Values calculated in accordance with the EN 14825 2013 standard given for bivalente temperature of 5...

Page 10: ...ation of the load for transport and in particular the maximum speed Transport The unit must be handled with care to avoid transport damage Thus we recommend Do not dispose of the transport supports or...

Page 11: ...mbling directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made 8 LOCATION AND ASSEMBLING With the help...

Page 12: ...unit and flexible connections in the hydraulic tubes If necessary an acoustic technician must commission a study Sound pressure level Measurement conditions in a clear field measured at a distance of...

Page 13: ...electrical connections before energizing the unit Check that the automatic switch is closed Omitting this can cause personal damage Make the ground connection before any other electrical connection V...

Page 14: ...ning the tensor screw The belt tension must be checked after 24 hours of motor operation Attention Before performing these operations it is necessary to verify that the unit is disconnected from mains...

Page 15: ...se and vibration transmission Flexible connections Optionally these units can be sent with flexible connections for supply and return air In case of asking together for flexible connections and damper...

Page 16: ...a stable temperature during the defrosting cycles Hydraulic connections 30PA PH PAC PHC Minimum volume I Minimum flow m3 h Maximum flow m3 h 90STD 101 2 2 6 2 100STD 120 2 7 7 4 120STD 143 3 1 8 8 16...

Page 17: ...be treated by using materials compatible with these characteristics whether stainless steel or titanium The units hydraulic circuits are made of copper pipes The exchanger plates are made of AISI 316...

Page 18: ...t leaks and condensation Ensure that the material used is steam barrier type Otherwise cover the insulation using appropriate protection The water must be analysed and the circuit must be set out acco...

Page 19: ...clogging of the plate exchanger The following graph represents the pressure drop for that filter 1 2 20 25 3 4 5 6 7 8 9 10 15 2 3 10 15 20 6 7 4 5 8 9 9 0 H E E 1 0 0 H E E 1 2 0 H E E 1 6 0 H E E 1...

Page 20: ...37 0 55 0 75 0 9 1 5 0 55 Maximum abs current A 1 4 2 0 2 3 2 7 4 0 2 0 Minimum water flow m3 h 1 2 1 2 1 2 3 0 4 8 3 0 Maximum pressure m w c 20 7 28 0 30 3 29 5 31 6 20 6 Maximum water flow m3 h 5 4...

Page 21: ...s stipulation is the only one allowing a best operation of the motorized damper with a homogeneous flow of the air In order to remove the damper it is necessary to unscrew from the unit and disconnect...

Page 22: ...valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the unit Attention a detailed attention must carried with the selection of the expa...

Page 23: ...available pressure m w c Flow m3 h 6 7 5 3 4 Pump 9 0 S T D t o 1 0 0 S T D 9 0 H E E t o 1 0 0 H E E 1 2 0 S T D t o 1 8 0 S T D 1 2 0 H E E t o 1 8 0 H E E 3 4 1 2 5 6 Hydraulic connections of the...

Page 24: ...r circulation control A differential pressure switch detains the operation of the unit when it does not detect water circulation Defrost control This control s mission is to eliminate the ice that mig...

Page 25: ...ll type compressors and have a phase control relay Verify that they turn in the correct direction and if not reverse the power wires COMPRESOR SCROLL COMPROBAR SENTIDO DE GIRO COMPRESSEUR SCROLL V RIF...

Page 26: ...this means that the mesh filter is obstructed it must be disassembled and cleaned Repeat until the obstruction is eliminated from the filter Once the circuit is free of contaminating elements read the...

Page 27: ...given in this brochure must be respected and complied with to guarantee a correct operation of the units Next several possible operation problems are stated which could happen if the conditions of the...

Page 28: ...dirt measuring the difference in temperature at the piping level at the inlet and at the outlet of the dehydrant If necessary replace Mesh filter It is also necessary to install a filter in the hydra...

Page 29: ...pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filter in the return air optional Clean usually Depending on the installation conditions the filter a...

Page 30: ...intoxication fire and explosion linked to the refrigerant At the end of its useful life the refrigerant must be retrieved and recycled as per the current regulations Oil Oils used for cooling machines...

Page 31: ...c Replace filter d Search for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise h...

Page 32: ...OVERVIEW OF THE INSTALLATION Air cooled chillers air water heat pumps Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work ref...

Page 33: ...ulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction __________Discharge ________ Diff _______ Unit Inlet_____________Outlet________...

Page 34: ...Ductable air cooled scroll chillers and heat pumps 34 Notes...

Page 35: ......

Page 36: ...Order No 10057 06 2016 Supersedes order No 08 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: