11

8 - CHECKING BEFORE COMMISSIONING 

Where:
V

inst

  Installation volume (l)

V

inst

  Expansion vessel volume (l)

V

1

   Initial volume of 1kg of water (at water temperature with the machine stopped)

V

2

   Final volume of 1kg of water (at water temp. with the machine at normal speed)

P

f

   Final network pressure (safety valve pressure in bars + 1)

P

i

    Initial network pressure (absolute 

fi

 lling pressure of the installation in bars)

Note:

 If the hydraulic circuit has a bu

 er tank, its volume must be 

taken into account for this calculation.

Volume occupied by 1kg of water at di

 erent temperatures:

Maximum installation volume

The water capacity for the installation obtained from this equation 

corresponds to the maximum that the installation allows based on 

the expansion vessel assembled. 

Temperature (ºC) Volume (l)

Temperature (ºC) Volume (l)

0

1,00013

50

1,0121

4

1,00000

60

1,0171

10

1,00027

70

1,0227

20

1,00177

80

1,0290

30

1,00435

90

1,0359

40

1,00782

100

1,0434

f

i

f

vessel

INST

P

V

V

P

P

V

V

)

(

)

(

1

2

=

The calculation of the minimum water volume has been done for 

nominal conditions of water inlet/outlet temperature 12°C/7°C and 

outdoor air temperature 35ºC, only in COOLING mode. This value 

is applicable for the majority of refrigeration applications (group 

with fan-coil units).

Note

: The bu

 er tank is indispensable in installations that operate 

with a reduced volume of water (group with an air handling unit) 

or for industrial processes.

30PA

Minimum 

volume (I)

Minimum 

fl

 ow (m

3

/h)

Maximum 

fl

 ow (m

3

/h)

90STD

101

2,2

6,2

100STD

120

2,7

7,4

120STD

143

3,1

8,8

160STD

187

4,1

11,3

180STD

204

4,3

12,7

90HEE

107

2,1

6,7

100HEE

132

2,9

8,1

120HEE

152

3,3

9,5

160HEE

189

3,7

11,7

180HEE

210

4,0

12,8

Anti-freeze protection with glycol water

If a pure product is used for dilution in order to protect the hydraulic 

circuit, the following instructions must be followed:

 

Do not introduce any of the pure anti-freezing product separately 

and then the water in the installation.

 

Always prepare the water m anti- corrosion 

inhibitor at the correct dosage prior to introducing it into the 

installation.

Minimum installation volume

The electronic control for these units incorporates an auto-adaptive 

control for the compressor operating time based on the time set 

for anti-short-cycle. 
This control reduces the number of times the compressor is started 

up and permanently adjusts the system’s thermal inertia, favouring 

the reduction of the minimum volume of water in the installation. 

The size of the bu

 er tank can also be decreased since the unit 

will be stopped for less time.

Installation water volume

Hydraulic connections

Evaporator operating limits

The curves represent the minimum and maximum admissible 

temperature increases based on the outlet (discharge) 

temperature, for both pure water and glycol water. 
For temperature changes that are not listed between the curves, 

please consult.
The minimum outlet temperature for the unit will be +5ºC with pure 

water and -7ºC with glycol water.

 Example 

For an outlet water temperature of +5ºC:

 Minimum 

temp.: 2,6ºC 



T. condition  7,6ºC / 5ºC 

 Maximum 

temp.:  6,0ºC 



T. condition  11ºC / 5ºC 

Procedure:

 

At minimum, a complete rinsing of the hydraulic installation 

must be performed.

 

After the 

fi

 nal rinsing, the installation must be completely 

drained.

 

Introduce the water/anti-freeze/inhibitor mixture and increase 

the pressure with a hydraulic pump.
We recommend using a 

fi

 lling device with a non-return valve 

for compliance with the domestic anti-contamination standards. 

The device must never in any case be connected to the 

city network if the additives used in the hydraulic circuit are 

not approved by the Ministry of Sanitation in the country of 

installation.

 

Completely purge the installation.

 

Circulate the mixture throughout the entire installation for a 

minimum of 2 hours prior to starting up the unit.

 

Check the final dosage obtained with a densimeter or 

refractometer.

 

Check the pH obtained with pH paper strips or a pH metre.

 

Place a label in a visible place that indicates:

 -the presence of anti-freeze in the installation,

 -the name of the product and the supplier,

 -the dosage and the pH as of the time the unit is started up.

9

8

7

6

5

4

3

2

1

10

-7 -6

-4

-2

0

2

4

6

8

10

12

14

16

18

Water outlet temperature °C

Δ

Admissible difference between water I/O °C

maximum 

Δ

T

minimum 

Δ

T

Summary of Contents for 30PA 180

Page 1: ...TALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80057 09 2018 Ductable air cooled scroll chillers 30PA 90 180 Nominal cooling capacity 17 36...

Page 2: ...Checks on the plug fan HEE version 9 Air ducts connections 10 Hydraulic connections 11 Condensate drain connection 14 9 OPTIONS 14 Condensation pressure control 14 Air filter 15 Cooling recovery circ...

Page 3: ...the product In case of a leak Toxicity According to EN 378 1 R 410A belongs to the A1 A1 group i e with high safety both in the mix and also in the case of a leak Although it is not toxic in case of a...

Page 4: ...ciency Variable speed electronic plug fan M00 M01 STD HEE 3 OPERATION LIMITS With control of the condensation pressure operating up to 15 C Minimum outlet temperature With the option of glycol water f...

Page 5: ...h the hooks to prevent damage to the housing The unit must be lifted and fixed with care with maximum inclination of 15 since it could harm its operation Do not raise by points outside of those specif...

Page 6: ...ent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made With the help of the crane or the forklift truck the unit will...

Page 7: ...power level Measurement conditions ducted discharge and return For nominal operating conditions EN 14511 Acoustic power reference 10E 12 W tolerance of 2 dB partial charge of 4 dB Note The unit has a...

Page 8: ...s and probe values On screen display of alarms codes Installation norms In order to establish the unit s electric power supply cable inlet calculation of the lead section protections etc refer to The...

Page 9: ...tion in mm for a pulley centre distance of 100 mm e pulley centre distance in mm E see table below for the value f force applied At the centre of the centre distance e apply a force f as determined in...

Page 10: ...must be insulated and must not be composed of materials that propagate fire nor expel toxic gases in the event of a fire The internal surfaces must be smooth and should not pollute the air that circu...

Page 11: ...cing it into the installation Minimum installation volume The electronic control for these units incorporates an auto adaptive control for the compressor operating time based on the time set for anti...

Page 12: ...to the desired temperature Corrosion behaviour Water content Concentration mg l AISI 316 Copper Organic substances 0 Electrical conductivity 500 S cm 500 S cm NH3 2 2 20 0 20 Chlorides 300 300 0 Sulph...

Page 13: ...ble with these characteristics whether stainless steel or titanium Plan the anti freeze protection for the installation when the outdoor temperature is low water with anti freeze thermal insulation of...

Page 14: ...n option for the pan is recommended Mandatory when outdoor temperatures are below 3 C 9 OPTIONS Servomotor Damper M01 assembly VERTICAL air supply M00 assembly HORIZONTAL air supply Servomotor Damper...

Page 15: ...ter filler drainer bleeders thermometers pressure gauges cut o and insulation valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the un...

Page 16: ...4 4 5 2 6 2 8 1 8 9 Nominal water flow m3 h 0 38 0 45 0 53 0 70 0 76 Pressure drop m w c 0 06 0 09 0 17 0 30 0 36 Cooling capacity kW 17 8 21 3 25 3 33 0 36 2 Power input kW 6 8 7 9 8 6 10 8 12 7 Hyd...

Page 17: ...afety device is built into the electronic control This is activated in COOLING mode when the water outlet temperature is lower than the set value This causes the stop of the outdoor fan and the compre...

Page 18: ...water flow The filling of the hydraulic circuit is then carried out Open the water circuit valves and ensure that the water circulates around the exchanger with the pump in service Bleed the air in th...

Page 19: ...compressor stopped monitoring the pressures to control any anomaly Low pressure schrader valve optional pressure gauge connection High pressure schrader valve optional pressure gauge connection Electr...

Page 20: ...anel etc Check that the insulation foam is not unstuck or torn 12 MAINTENANCE The minimal maintenance operations and their periodicity will be made according to the national regulations Any interventi...

Page 21: ...ed further lubrication Servomotor optional In units with a condensation pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filters are moved by lifting...

Page 22: ...nd in the unit s data plate 30PA 90V HEE 100V HEE 120V HEE 160V HEE 180V HEE Volume l 3 0 3 3 3 3 3 3 6 2 Operators shall ensure that the unit is checked for leaks ad minima according to the following...

Page 23: ...ch for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The...

Page 24: ...red for treatment Refrigerant Energy transfer fluid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directive 2...

Page 25: ...INSTALLATION Air cooled chillers Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work reference Address Unit Unit model Seria...

Page 26: ...Circulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction_________ Discharge ________Di ______ Unit InletOutlet __________ Di _______...

Page 27: ......

Page 28: ...Order No 10057 09 2018 Supersedes order No 07 2018 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: