8 - CHECKING BEFORE COMMISSIONING 

 

It is advisable to use 

fl

 exible hoses for connecting the piping 

to the unit in order to reduce the transmission of vibrations to 
the building to the greatest degree. It is mandatory to assemble 
hoses if the unit is installed over shock absorbers. Optionally, 

fl

 exible hydraulic connections kit can be supplied.

 

The pipe layouts must be set out with the lowest possible 
number of bends to minimise pressure drops. The pipes must 
be correctly supported to prevent exerting excessive force on 
the unit connections.

 

Before insulating the tubes and charging the system perform 
a preliminary check to verify that there are no drops in the 
installation.

 

The pipes must be carefully insulated to prevent leaks and 
condensation. Ensure that the material used is steam barrier 
type. Otherwise, cover the insulation using appropriate 
protection. 

 

The water must be analysed and the circuit must be set out 
according to the results. If necessary, an expert in water 
treatment must be consulted (see section on corrosion 
behaviour).

 

In installations to open circuits, if it is not possible to 

maintain the water conditions within the values indicated in 

the corrosion behaviour table featured, it will be necessary 

to install an exchanger that separates the unit circuit from 

the circuit of the water circuit to be dealt with by using 

materials compatible with these characteristics, whether 

stainless steel or titanium.

  

 

Plan the anti-freeze protection for the installation when the 
outdoor temperature is low: water with anti-freeze, thermal 
insulation of the hydraulic circuit, electrical heaters in the 
hydraulic circuit, draining from the installation when the unit 
does not work, etc.

In this case the installer must set up the complete hydraulic 
circuit with all the components: thermal bu

 er tank, motorised 

pump group, expansion vessel, safety, regulation, cut-o

  and 

draining valves, air bleeder valve, etc.

It is also necessary to install a 

fi

 lter in the hydraulic power 

supply to the unit in order to prevent clogging of the plate 

exchanger. Non-compliance with this recommendation 

can cause reduced 

fl

 ow which can lead to freezing and 

breaking of the exchanger. 

Both at the inlet and the outlet of the unit, install thermal 
pressure gauges which enable supervising the operation of the 
installation, or at least plan the installation of these.
Note: optionally, a kit can be supplied with :
- A stainless steel mesh 

fi

 lter (500 microns). 

- Cut-o

  and water regulation valves. 

- Flexible hydraulic connections of 500 mm.

Schematic diagram of the hydraulic 

circuit

DIFFERENTIAL

PRESSURE SWITCH

PLATES

EXCHARGER

SHUT-OFF

VALVE

DRAINAGE

CIRCUIT

1

2

20

25

3

4

5

6

7

8

10

9

15

2

3

10

15

20

6

7

4

5

8 9

120STD / 160STD

90STD / 100STD

180STD

Flow (m

3

/h)

30PA pressure drop (m.w.c.)

1

2

3

4

5

6

7

8

10

9

15

20

25

2

3

10

15

20

6

7

4

5

8 9

90HEE - 100HEE120HEE - 160HEE - 180HEE

30PA pressure drop (m.w.c.)

Flow (m

3

/h)

Summary of Contents for 30PA 180

Page 1: ...TALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80057 09 2018 Ductable air cooled scroll chillers 30PA 90 180 Nominal cooling capacity 17 36...

Page 2: ...Checks on the plug fan HEE version 9 Air ducts connections 10 Hydraulic connections 11 Condensate drain connection 14 9 OPTIONS 14 Condensation pressure control 14 Air filter 15 Cooling recovery circ...

Page 3: ...the product In case of a leak Toxicity According to EN 378 1 R 410A belongs to the A1 A1 group i e with high safety both in the mix and also in the case of a leak Although it is not toxic in case of a...

Page 4: ...ciency Variable speed electronic plug fan M00 M01 STD HEE 3 OPERATION LIMITS With control of the condensation pressure operating up to 15 C Minimum outlet temperature With the option of glycol water f...

Page 5: ...h the hooks to prevent damage to the housing The unit must be lifted and fixed with care with maximum inclination of 15 since it could harm its operation Do not raise by points outside of those specif...

Page 6: ...ent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made With the help of the crane or the forklift truck the unit will...

Page 7: ...power level Measurement conditions ducted discharge and return For nominal operating conditions EN 14511 Acoustic power reference 10E 12 W tolerance of 2 dB partial charge of 4 dB Note The unit has a...

Page 8: ...s and probe values On screen display of alarms codes Installation norms In order to establish the unit s electric power supply cable inlet calculation of the lead section protections etc refer to The...

Page 9: ...tion in mm for a pulley centre distance of 100 mm e pulley centre distance in mm E see table below for the value f force applied At the centre of the centre distance e apply a force f as determined in...

Page 10: ...must be insulated and must not be composed of materials that propagate fire nor expel toxic gases in the event of a fire The internal surfaces must be smooth and should not pollute the air that circu...

Page 11: ...cing it into the installation Minimum installation volume The electronic control for these units incorporates an auto adaptive control for the compressor operating time based on the time set for anti...

Page 12: ...to the desired temperature Corrosion behaviour Water content Concentration mg l AISI 316 Copper Organic substances 0 Electrical conductivity 500 S cm 500 S cm NH3 2 2 20 0 20 Chlorides 300 300 0 Sulph...

Page 13: ...ble with these characteristics whether stainless steel or titanium Plan the anti freeze protection for the installation when the outdoor temperature is low water with anti freeze thermal insulation of...

Page 14: ...n option for the pan is recommended Mandatory when outdoor temperatures are below 3 C 9 OPTIONS Servomotor Damper M01 assembly VERTICAL air supply M00 assembly HORIZONTAL air supply Servomotor Damper...

Page 15: ...ter filler drainer bleeders thermometers pressure gauges cut o and insulation valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the un...

Page 16: ...4 4 5 2 6 2 8 1 8 9 Nominal water flow m3 h 0 38 0 45 0 53 0 70 0 76 Pressure drop m w c 0 06 0 09 0 17 0 30 0 36 Cooling capacity kW 17 8 21 3 25 3 33 0 36 2 Power input kW 6 8 7 9 8 6 10 8 12 7 Hyd...

Page 17: ...afety device is built into the electronic control This is activated in COOLING mode when the water outlet temperature is lower than the set value This causes the stop of the outdoor fan and the compre...

Page 18: ...water flow The filling of the hydraulic circuit is then carried out Open the water circuit valves and ensure that the water circulates around the exchanger with the pump in service Bleed the air in th...

Page 19: ...compressor stopped monitoring the pressures to control any anomaly Low pressure schrader valve optional pressure gauge connection High pressure schrader valve optional pressure gauge connection Electr...

Page 20: ...anel etc Check that the insulation foam is not unstuck or torn 12 MAINTENANCE The minimal maintenance operations and their periodicity will be made according to the national regulations Any interventi...

Page 21: ...ed further lubrication Servomotor optional In units with a condensation pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filters are moved by lifting...

Page 22: ...nd in the unit s data plate 30PA 90V HEE 100V HEE 120V HEE 160V HEE 180V HEE Volume l 3 0 3 3 3 3 3 3 6 2 Operators shall ensure that the unit is checked for leaks ad minima according to the following...

Page 23: ...ch for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The...

Page 24: ...red for treatment Refrigerant Energy transfer fluid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directive 2...

Page 25: ...INSTALLATION Air cooled chillers Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work reference Address Unit Unit model Seria...

Page 26: ...Circulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction_________ Discharge ________Di ______ Unit InletOutlet __________ Di _______...

Page 27: ......

Page 28: ...Order No 10057 09 2018 Supersedes order No 07 2018 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: