Centre of gravity coordinates

Placement on site

Once the unit is discharged, it must be freed from the transport 
supports so that the inserts available for the silent-blocks can be 
accessed. 
Each support is 

fi

 xed to the crossbar using 2 M4 screws. 

M4 screws for 

fi

 xing the support 

Mounting 

hole

Location designation

Before moving the unit, it must be checked that all panels are 
fastened in place. Lift and lower with care.
When choosing the location, whatever may be the selected fashion, 
the following precautions have to be taken into consideration:

 

It is mandatory to comply with norm EN 378-3 on Safety and 
Environmental Requirements. Part 3: “In situ” installation and 
protection to people.

 

The area where the unit will be located must be perfectly accessible 
for cleaning and maintenance operations (check minimum free 
space for maintenance). Leave enough space for air circulation 
around the unit.

 

Check that the unit is perfectly levelled.

 

It is necessary to check that the surface of the 

fl

 oor or the 

structure supports the weight of the unit (please, consult the 
weight of the unit in the section “Anchorage for silent-blocks”). 

 

Foresee appropriate damping devices in all the installation so 
that noise and vibration transmission is avoided (refer to the 
“Anchorage for silent-blocks”). 
In the event of assembling directly on silent-blocks to the 
ground, it is recommended that a template of the unit’s footprint 
with the anchoring points of the silent-blocks be made.
With the help of the crane or the forklift truck, the unit will be 
raised to a su

  cient height that the silent-blocks can be screwed 

into its base. The 4 silent-blocks must remain oblique and the 
interiors perpendicular to the unit. 
M10 metric threads have been provided for their placement in 
the supports indicated in the following section “Anchorage for 
silent-blocks”. A hex key 17 or Allen wrench 8 will be used for 
this operation based on the 
type of screw used.
This image shows how the 
silent-block option that can be 
supplied for this unit is 

fi

 xed 

to the unit.

7 - LOCATION AND ASSEMBLING

Minimum free space for commissioning and

maintenance operations

1m

1m

0,5m

A

30PA

A (m)

90STD to 100STD

1,2

120STD to 180STD

1,5

30PA

A (m)

90HEE

1,2

100HEE to 120HEE

1,5

160HEE to 180HEE

1,2

30PA

Centre of gravity 

(mm)

Weight

empty 

(kg)

X

Y

Z

90STD

453 384 528

302

100STD

488 398 576

310

120STD

625 399 676

372

160STD

619 400 666

390

180STD

625 397 674

388

90HEE

502 422 614

294

100HEE

569 417 673

351

120HEE

628 426 742

368

160HEE

940 435 573

450

180HEE

936 434 579

455

Since it is an unit designed to work indoors, some specific 
installation norms must be followed:

 

Ensure that the location of the supply and return grilles does 
not generate air recirculation.

 

Check that there are no obstructions in the air supply and return 
grille slats due to being tightly closed

6 - TRANSPORT AND HANDLING

Summary of Contents for 30PA 180

Page 1: ...TALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80057 09 2018 Ductable air cooled scroll chillers 30PA 90 180 Nominal cooling capacity 17 36...

Page 2: ...Checks on the plug fan HEE version 9 Air ducts connections 10 Hydraulic connections 11 Condensate drain connection 14 9 OPTIONS 14 Condensation pressure control 14 Air filter 15 Cooling recovery circ...

Page 3: ...the product In case of a leak Toxicity According to EN 378 1 R 410A belongs to the A1 A1 group i e with high safety both in the mix and also in the case of a leak Although it is not toxic in case of a...

Page 4: ...ciency Variable speed electronic plug fan M00 M01 STD HEE 3 OPERATION LIMITS With control of the condensation pressure operating up to 15 C Minimum outlet temperature With the option of glycol water f...

Page 5: ...h the hooks to prevent damage to the housing The unit must be lifted and fixed with care with maximum inclination of 15 since it could harm its operation Do not raise by points outside of those specif...

Page 6: ...ent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made With the help of the crane or the forklift truck the unit will...

Page 7: ...power level Measurement conditions ducted discharge and return For nominal operating conditions EN 14511 Acoustic power reference 10E 12 W tolerance of 2 dB partial charge of 4 dB Note The unit has a...

Page 8: ...s and probe values On screen display of alarms codes Installation norms In order to establish the unit s electric power supply cable inlet calculation of the lead section protections etc refer to The...

Page 9: ...tion in mm for a pulley centre distance of 100 mm e pulley centre distance in mm E see table below for the value f force applied At the centre of the centre distance e apply a force f as determined in...

Page 10: ...must be insulated and must not be composed of materials that propagate fire nor expel toxic gases in the event of a fire The internal surfaces must be smooth and should not pollute the air that circu...

Page 11: ...cing it into the installation Minimum installation volume The electronic control for these units incorporates an auto adaptive control for the compressor operating time based on the time set for anti...

Page 12: ...to the desired temperature Corrosion behaviour Water content Concentration mg l AISI 316 Copper Organic substances 0 Electrical conductivity 500 S cm 500 S cm NH3 2 2 20 0 20 Chlorides 300 300 0 Sulph...

Page 13: ...ble with these characteristics whether stainless steel or titanium Plan the anti freeze protection for the installation when the outdoor temperature is low water with anti freeze thermal insulation of...

Page 14: ...n option for the pan is recommended Mandatory when outdoor temperatures are below 3 C 9 OPTIONS Servomotor Damper M01 assembly VERTICAL air supply M00 assembly HORIZONTAL air supply Servomotor Damper...

Page 15: ...ter filler drainer bleeders thermometers pressure gauges cut o and insulation valves The circulation pump can only work in a closed circuit The command is performed from a thermostat located on the un...

Page 16: ...4 4 5 2 6 2 8 1 8 9 Nominal water flow m3 h 0 38 0 45 0 53 0 70 0 76 Pressure drop m w c 0 06 0 09 0 17 0 30 0 36 Cooling capacity kW 17 8 21 3 25 3 33 0 36 2 Power input kW 6 8 7 9 8 6 10 8 12 7 Hyd...

Page 17: ...afety device is built into the electronic control This is activated in COOLING mode when the water outlet temperature is lower than the set value This causes the stop of the outdoor fan and the compre...

Page 18: ...water flow The filling of the hydraulic circuit is then carried out Open the water circuit valves and ensure that the water circulates around the exchanger with the pump in service Bleed the air in th...

Page 19: ...compressor stopped monitoring the pressures to control any anomaly Low pressure schrader valve optional pressure gauge connection High pressure schrader valve optional pressure gauge connection Electr...

Page 20: ...anel etc Check that the insulation foam is not unstuck or torn 12 MAINTENANCE The minimal maintenance operations and their periodicity will be made according to the national regulations Any interventi...

Page 21: ...ed further lubrication Servomotor optional In units with a condensation pressure regulation damper in the STD version it is advisable to check the state of the servomotor Filters are moved by lifting...

Page 22: ...nd in the unit s data plate 30PA 90V HEE 100V HEE 120V HEE 160V HEE 180V HEE Volume l 3 0 3 3 3 3 3 3 6 2 Operators shall ensure that the unit is checked for leaks ad minima according to the following...

Page 23: ...ch for leaks complete charge e Temperature of air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The...

Page 24: ...red for treatment Refrigerant Energy transfer fluid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directive 2...

Page 25: ...INSTALLATION Air cooled chillers Installation sketch and units location Telephone Installer Responsible for installation and or commissioning Installation work reference Address Unit Unit model Seria...

Page 26: ...Circulation pump Secundary emission system Emission control system Two ways Three ways Manometers reading m w c Pump Suction_________ Discharge ________Di ______ Unit InletOutlet __________ Di _______...

Page 27: ......

Page 28: ...Order No 10057 09 2018 Supersedes order No 07 2018 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: