background image

12

Discharge gas thermostat DGT
(only for units with low temperature option)
A sensor in each compressor discharge line opens to shut down
the compressor if the discharge gas temperature exceeds the
preset level.

Cut out 146°C

Cut in 113°C

Crankcase heater
Each compressor is fitted with an electric resistance crankcase
heater which prevents any absorption of refrigerant by the
compressor lubricating oil when the compressor is shut down.
Each heater is held in place by a screw clip which must be
secure. Prolonged exposure of the heater to air will result in its
destruction. The heater is energized when the compressor is
switched off. Regularly check that the heater operates correctly
when the unit is shut down.

WARNING: Never open or disconnect any switch or circuit
breaker which will cut the supply to the heaters, unless the unit
is to be shut down for lengthy service or repair or for a
seasonal shut down. In all cases the heater must be energised
for at least 24 hours before a compressor is restarted.

Compressor protection circuit board (STARTERGUARD)

The purpose of this card is to monitor the compressor
operating environment, in particular:

the crankcase heaters

the contactors

the part winding start timer

the control wiring between these components

The status of the controlled components is displayed via three
different-coloured LEDs:

Green LED: correct operation

Orange LED: signals that the magnetic loop of the card
has detected the presence of a current, either in the
compressor crankcase heater or in the compressor motor.

If the green and orange LEDs are illuminated together,
this indicates that there is no fault.

Red LED  - fault related to:
-

the heater, if the orange LED is not lit

-

the contactor or the power line of the compressor
motor, if the orange LED is lit

If a fault is detected, the compressor is shut down.

Power supply and resetting:
The STARTERGUARD card uses 24 V AC ± 10%, 50 Hz or
60 Hz. When a fault occurs, the 24 V supply must be
interrupted and then restored, in order to reset the card. The
green LED lights up.

Heat exchangers

Evaporator

Protection devices

Freeze-up prevention thermostat
The evaporator is protected against freeze-up. The protection is
provided by two sensors installed in the unit.

Significant undercharge (large bubbles in the sight glass,
drop in suction pressure).
-

Small units (charge below 20 kg per circuit).
After detection and repair completely drain the
refrigerant charge, using a refrigerant recovery unit,
then recharge completely, following the precautions
given above.

-

Large units (charge above 20 kg per circuit).
After detection and repair completely recharge the unit
as described above, operate it for a few minutes and
then let a specialist carry out a chromatographic
analysis to verify the composition of the blend
(range: R-32: 22-24%, R-125: 23-27%, R-134a: 50-54%).

Compressors

Checking the oil charge
Check the oil level and add or remove oil as necessary so that
the level is 1/8 to 3/8 up each sight glass with the compressor
running normally.

WARNING: Use only oils which have been approved for use in
refrigeration compressors. Never use oil which has been
exposed to air.

CAUTION: R-22 oils are NOT compatible with R-407C.

Recommended oil:

R-22 compressors:
-

Mineral oil, Carrier specification No. PP 33-2

-

Suniso 3 GS (Sun Oil Co)

-

Capella WF 32-150

-

Clavus G 32 (Shell Oil Co)

-

Gargoyle Artic (Mobil Oil) - original charge

R-407C compressors:

-

Oil, Carrier specification No. PP 47-26

-

Mobiloil EAL 68 - Carrier reference 470EE as original
charge, in 5 liter containers

WARNING: All fixing devices and fittings which may have
been removed during servicing must always be replaced upon
completion of the work and before restarting the unit.

Tightening torques to be applied

Description

Diameter, mm

Torque, Nm

Discharge valve

M16

135-140

Cylinder head

M12

75-87

Suction and liquid line flange

M12

75-87

Suction valve

M16

135-140

Compressor motor protection

Circuit breaker
Calibrated, thermo-magnetic, manually reset circuit breaker to
protect the motor against locked rotors and excessive current
draw. It also protects against overcurrents up to the trip
capacity indicated on the wiring diagram.

WARNING: Never bypass a circuit breaker or increase its
setting. If a circuit breaker trips, find out why it has done so
and correct the problem before resetting the breaker.

Summary of Contents for 30GH 040

Page 1: ...and maintenance instructions 30GH 040 245 30GZ 040 245 Air cooled liquid chillers 50 Hz Carrier is participating in the Eurovent Certification Programme Products are as listed in the Eurovent Directo...

Page 2: ...hecks 10 Actual start up 10 Servicing refrigeration components 11 General maintenance 11 Liquid refrigerant charging 11 Compressors 12 Compressor protection circuit board STARTERGUARD 12 Heat exchange...

Page 3: ...temperature C Pressure drop air kPa Pressure drop water kPa Discharge air pressure Pa Fan speed r s or rpm Fan motor input Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V...

Page 4: ...85 145 Do not obstruct 30GH GZ A B C D E F G 040 045 2450 1870 1912 2500 1200 500 1200 050 060 2900 2156 2060 2500 1200 500 1200 085 100 3404 2328 2471 1600 1800 1600 1800 120 145 4322 2328 2471 1600...

Page 5: ...not obstructed At least two sides of the units must be free from obstructions to ensure proper air flow If several units are installed next to each other ensure that the space in between the units is...

Page 6: ...150 DN150 Drain NPT in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Max water side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000...

Page 7: ...ing of the liquid water or brine Refer to the examples below NOTE The compressor must not restart more than 6 times in an hour INSTALLATION SAFETY CONSIDERATIONS Installation start up and servicing th...

Page 8: ...Siting Before siting the unit check that the permitted loading at the site is adequate or that appropriate strenghtening measures have been taken the surface is horizontal flat and intact there is ade...

Page 9: ...valves close to the evaporator in the entering and leaving water lines Use flexible connections to reduce the transmission of vibration to the pipework Insulate all pipework after testing for leaks b...

Page 10: ...he lubricating oil from absorbing refrigerant Check the operation of all accessories chilled water circulating pumps air handlers and other equipment connected to the evaporator Follow the individual...

Page 11: ...H or 12 K 30GZ of subcooling as the liquid refrigerant enters the expansion valve The units 30GH GZ 040 245 use refrigerant For your information we are reproducing here some extracts from the official...

Page 12: ...xchangers Evaporator Protection devices Freeze up prevention thermostat The evaporator is protected against freeze up The protection is provided by two sensors installed in the unit Significant underc...

Page 13: ...r Carrier distributor Replacing cooler tubes Retubing must be done only by a properly trained service engineer Most standard practices can be applied but for cooler tubes a 5 crush allowance is made f...

Page 14: ...or rotating water jets are strictly forbidden Correct and frequent cleaning approximately every three months will prevent 2 3 of the corrosion problems Fan motor replacement This presents no special p...

Page 15: ...efective compressor Refrigerant losses Refrigerant losses Low water flow in the evaporator Blocked expansion valve Blocked filter drier Defective high pressure switch Defective fan s Low water flow in...

Page 16: ...7 Supersedes order No 13187 76 July 1996 Printed on Totally Chlorine Free Paper Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands Manufactu...

Reviews: