background image

13

Evaporator maintenance

Check that:

the insulating foam is intact and securely in place.

the cooler heaters are operating, secure and correctly
positioned.

the water-side connections are clean and show no sign of
leakage.

Multitube evaporators
The evaporator can be removed  using the following procedure:

Close the chilled water supply and return valves (if
installed), and disconnect the chilled water supply and
return pipe connections.

Drain the water from the cooler.

Remove all temperature sensors from  the cooler.

Fold back the insulation at the refrigerant line
connections.

When the evaporator heads and manifolds are removed, the
outer tube end plates will be visible.

Four evaporator tubes on 30GH/GZ 040-060 units and six
tubes on 30GH/GZ 085-245 units are swaged into the end plate
and cannot be removed. A dot punch mark in the end plate
opposite each one identifies each of them. If any of them
develop a leak, the tube must be plugged, as described below.

Plugging evaporator tubes
A leaking tube can be plugged pending replacement. The
number of tubes plugged will determine when they should be
replaced. Check with Carrier the effect upon chiller performance
of plugging a number of tubes. Carrier will need to know the
number of tubes to be plugged and their positions. The figure
below shows the Elliott method of plugging tubes.

WARNING: Take care when inserting plugs not to damage the
plate material between the tubes. Avoid excessive force. Clean
all components with Locquic N and then coat all surfaces with
several drops of Loctite 75 to ensure a good seal without
applying excessive force.

Elliott tube plug

Components

Part number

Tube brass plug

---T-853--103500S-*

Tube brass ring

---T-853--002570S-*

Brass plug (holes without tubes)

---T-853--1031—S-*

Brass ring (holes without tubes)

---T-853--002631S-*

Loctite

No. 75*

Locquic

“N”*

* Order directly from your Carrier distributor

Replacing cooler tubes
Retubing must be done only by a properly trained service
engineer. Most standard practices can be applied, but for cooler
tubes a 5% crush allowance is made for tube expansion and
twisting (15.87 mm diameter tubes are used in these coolers).

The table below gives the specification of the materials used.

Example:

Tube sheet hole diameter

16.00 mm

Tube outside diameter

15.87 mm

Clearance

0.13 mm

Tube inside diameter before rolling

14.27 mm

Tube inside diameter after rolling

14.48 mm

NOTE: Tubes next to the gasket webs must be flush with the
tube sheets at either end of the cooler.

Preparation of gaskets
When rebuilding the cooler, new gaskets must always be used.
They must conform to the Carrier specification for compressed
gaskets.

Clean the gasket and its place on the tube sheet.

Cover the two matching surfaces (gasket and tube sheet)
with adhesive, and stick them together.

Let the joint dry for 5 minutes.

Moisten the joint with a small amount of compressor oil.

Reinstall the evaporator head within 30 minutes.

Tightening cooler head bolts
Cooler head bolts must be tightened in the specified sequence
and to the correct torque.

Use this tightening sequence:

Hand tighten the first four bolts as shown below in stage 1.

Hand tighten the next bolts as shown below in stage 2.

Starting at the 12 o'clock position, and working clockwise,
insert and hand tighten the remaining outer bolts.

Insert and tighten the six screws in the center of the head.

Plug

Ring

Tube plate

Starting again at 12 o’clock and working clockwise tighten
the outer bolts to the correct torque.

Not less than one hour later insert and tighten the six bolts
in the centre of the head, using the torque values given.

After the cooler has been refilled with clean refrigerant,
use a soap and water solution or an electronic detector to
confirm that there are no leaks.

Replace the evaporator insulation and temperature sensors.

7

4

6

2

8

3

5

1

Bolt size M12 - 71-87 Nm
Bolt size M16 - 171-210 Nm
Bolt size M20 - 171-210 Nm

Stage 2

Stage 1

Summary of Contents for 30GH 040

Page 1: ...and maintenance instructions 30GH 040 245 30GZ 040 245 Air cooled liquid chillers 50 Hz Carrier is participating in the Eurovent Certification Programme Products are as listed in the Eurovent Directo...

Page 2: ...hecks 10 Actual start up 10 Servicing refrigeration components 11 General maintenance 11 Liquid refrigerant charging 11 Compressors 12 Compressor protection circuit board STARTERGUARD 12 Heat exchange...

Page 3: ...temperature C Pressure drop air kPa Pressure drop water kPa Discharge air pressure Pa Fan speed r s or rpm Fan motor input Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V Ph 3 V Ph 1 V Ph 2 V...

Page 4: ...85 145 Do not obstruct 30GH GZ A B C D E F G 040 045 2450 1870 1912 2500 1200 500 1200 050 060 2900 2156 2060 2500 1200 500 1200 085 100 3404 2328 2471 1600 1800 1600 1800 120 145 4322 2328 2471 1600...

Page 5: ...not obstructed At least two sides of the units must be free from obstructions to ensure proper air flow If several units are installed next to each other ensure that the space in between the units is...

Page 6: ...150 DN150 Drain NPT in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Max water side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000...

Page 7: ...ing of the liquid water or brine Refer to the examples below NOTE The compressor must not restart more than 6 times in an hour INSTALLATION SAFETY CONSIDERATIONS Installation start up and servicing th...

Page 8: ...Siting Before siting the unit check that the permitted loading at the site is adequate or that appropriate strenghtening measures have been taken the surface is horizontal flat and intact there is ade...

Page 9: ...valves close to the evaporator in the entering and leaving water lines Use flexible connections to reduce the transmission of vibration to the pipework Insulate all pipework after testing for leaks b...

Page 10: ...he lubricating oil from absorbing refrigerant Check the operation of all accessories chilled water circulating pumps air handlers and other equipment connected to the evaporator Follow the individual...

Page 11: ...H or 12 K 30GZ of subcooling as the liquid refrigerant enters the expansion valve The units 30GH GZ 040 245 use refrigerant For your information we are reproducing here some extracts from the official...

Page 12: ...xchangers Evaporator Protection devices Freeze up prevention thermostat The evaporator is protected against freeze up The protection is provided by two sensors installed in the unit Significant underc...

Page 13: ...r Carrier distributor Replacing cooler tubes Retubing must be done only by a properly trained service engineer Most standard practices can be applied but for cooler tubes a 5 crush allowance is made f...

Page 14: ...or rotating water jets are strictly forbidden Correct and frequent cleaning approximately every three months will prevent 2 3 of the corrosion problems Fan motor replacement This presents no special p...

Page 15: ...efective compressor Refrigerant losses Refrigerant losses Low water flow in the evaporator Blocked expansion valve Blocked filter drier Defective high pressure switch Defective fan s Low water flow in...

Page 16: ...7 Supersedes order No 13187 76 July 1996 Printed on Totally Chlorine Free Paper Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands Manufactu...

Reviews: