Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 10.

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 10

---

Line Connections

A00010

Fig. 11

---

3--Phase Monitor Control

(Applies to 3--Phase Units Only)

Table 3—3--Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor opera-

tion

FLASHING

Reversed phase

ON

Normal

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Ensure compressor rotation is correct.

S

3--phase scroll compresors are rotation
sensitive.

S

A flash LED on phase monitor indicates
reverse rotation. (See Fig. 11 and Table 3)

This will not allow contractor to be energized.

S

Disconnect power to unit and interchange 2
field--wiring leads on unit contactor.

CAUTION

!

Connect Control Wiring

Route 24v control wires through control wiring grommet and

connect leads to control wiring. See Thermostat Installation
Instructions for wiring specific unit combinations. (See Fig. 12.)
Use No. 18 AWG color--coded, insulated (35

°

C minimum) wire.

If thermostat is located more than 100 ft. from unit, as measured

along the control voltage wires, use No. 16 AWG color--coded

wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load
with an accessory transformer as required.

Final Wiring Check
IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing
to ensure wires are not in contact with tubing, sheet metal, etc.

STEP 10

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater

only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. Refer to the Long Line Guideline--Residential Split--System
Air Conditioners and Heat Pumps.

STEP 11

Install Electrical Accessories

Refer to the individual installation instructions packaged with kits

or accessories when installing.

25H

C

A

Summary of Contents for 25HCA

Page 1: ...ION 3 12 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Elevate Unit 3 Step 6 Install TXV 3 4 Step 7 Check Defrost The...

Page 2: ...suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windo...

Page 3: ...31 1 2 X 31 1 2 9 1 8 6 9 16 24 11 16 35 X 35 9 1 8 6 9 16 28 7 16 A05177 Fig 3 Tiedown Knockout Requirements On rooftop applications locate unit at least 6 in above roof surface STEP 4 Operating Ambi...

Page 4: ...m down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut driver Save the clamp 4 Remove R 22 TXV using...

Page 5: ...bserve the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field su...

Page 6: ...l 1 2 turn 15 ft lb DO NOT OVER TIGHTEN Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on...

Page 7: ...outdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes makings sure wire ties on feeder tubes are secure an...

Page 8: ...lated 35 C minimum wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must b...

Page 9: ...ng system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated fully open liquid and vapor service valves 2 Unit is shipped with valve stem s closed...

Page 10: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 12 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 11: ...the start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 13 in the ON position When Quiet Shift switch is placed in ON position and a...

Page 12: ...claim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on outdoor unit This ch...

Page 13: ...370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 398 112 107 102 97 405 113 108 103 98 412 114 109 104 99 419 115 110 105 100 426 117 112 107 102 433 118 113 108 103 440 119 1...

Page 14: ...longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and...

Reviews: