Carrier 25HCA Installation Instructions Manual Download Page 7

7

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum

method is the most positive way of assuring a system is free of air
and liquid water. See Fig. 8.

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN
SYSTEM

VACUUM TIGHT
TOO WET

TIGHT
DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

Fig. 8

---

Deep Vacuum Graph

CHECK FOR TIGHT, DRY SYSTEM 

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

A95425

Fig. 9

---

Triple Evacuation Method

Triple Evacuation Method

The triple evacuation method should only be used when vacuum

pump is only capable of pumping down to 28 in. of mercury
vacuum, and system does not contain any liquid water. Refer to

Fig. 9 and proceed as follows:

1. Pump system down to 28 in. of mercury and allow pump

to continue operating for an additional 15 minutes.

2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and

open until system pressure is 2 psig.

4. Close service valve and allow system to stand for 1 hour.

During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture.

5. Repeat this procedure as indicated by Fig. 9. System will

then be free of any contaminants and water vapor.

Final Tubing Check
IMPORTANT

: Check to be certain factory tubing on both

indoor and outdoor unit has not shifted during shipment. Ensure
tubes are not rubbing against each other or any sheet metal. Pay
close attention to feeder tubes, makings sure wire ties on feeder
tubes are secure and tight.

STEP 9

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal

box cover removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction
of improper voltage. See unit rating plate for recommended

circuit protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do
not install system where voltage may fluctuate above or below
permissible limits.

NOTE

: Use copper wire only between disconnect switch and

unit.

NOTE

: Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within
sight from and readily accessible from unit, per Section 440--14
of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into
unit control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur.
The ground may consist of electrical wire or metal conduit

when installed in accordance with existing electrical codes.

25H

C

A

Summary of Contents for 25HCA

Page 1: ...ION 3 12 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Elevate Unit 3 Step 6 Install TXV 3 4 Step 7 Check Defrost The...

Page 2: ...suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windo...

Page 3: ...31 1 2 X 31 1 2 9 1 8 6 9 16 24 11 16 35 X 35 9 1 8 6 9 16 28 7 16 A05177 Fig 3 Tiedown Knockout Requirements On rooftop applications locate unit at least 6 in above roof surface STEP 4 Operating Ambi...

Page 4: ...m down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut driver Save the clamp 4 Remove R 22 TXV using...

Page 5: ...bserve the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field su...

Page 6: ...l 1 2 turn 15 ft lb DO NOT OVER TIGHTEN Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on...

Page 7: ...outdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes makings sure wire ties on feeder tubes are secure an...

Page 8: ...lated 35 C minimum wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must b...

Page 9: ...ng system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated fully open liquid and vapor service valves 2 Unit is shipped with valve stem s closed...

Page 10: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 12 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 11: ...the start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 13 in the ON position When Quiet Shift switch is placed in ON position and a...

Page 12: ...claim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on outdoor unit This ch...

Page 13: ...370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 398 112 107 102 97 405 113 108 103 98 412 114 109 104 99 419 115 110 105 100 426 117 112 107 102 433 118 113 108 103 440 119 1...

Page 14: ...longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and...

Reviews: