Installation Instructions

25HCA

Comfort

t

Series Heat Pump with Puron

r

Refrigerant

Sizes 18 To 60

1 1/2 To 5 Nominal Tons

A05341

Fig. 1

---

25HCA

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION RECOMMENDATIONS

2

. . . . . . . . . . . . .

INSTALLATION

3 -- 12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 -- Check Equipment & Jobsite

3

. . . . . . . . . . . . . . .

Step 2 -- Install on Solid Pad

3

. . . . . . . . . . . . . . . . . . . . . .

Step 3 -- Clearance Requirements

3

. . . . . . . . . . . . . . . . . .

Step 4 -- Operating Ambient

3

. . . . . . . . . . . . . . . . . . . . . .

Step 5 -- Elevate Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 6 -- Install TXV

3 -- 4

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 7 -- Check Defrost Thermostat

5

. . . . . . . . . . . . . . . . .

Step 8 -- Make Piping Connections

5 -- 7

. . . . . . . . . . . . . .

Step 9 -- Make Electrical Connections

7 -- 8

. . . . . . . . . . . .

Step 10 -- Compressor Crankcase Heater

8

. . . . . . . . . . . . .

Step 11 -- Install Electrical Accessories

8

. . . . . . . . . . . . . .

Step 12 -- Start--Up

9 -- 11

. . . . . . . . . . . . . . . . . . . . . . . . . .

Step 13 -- Check Charge

12

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 14 -- Final Checks

12

. . . . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

12

. . . . . . . . . . . . . . . . . . . . . .

PURON REFRIGERANT QUICK REFERENCE GUIDE

14

Summary of Contents for 25HCA

Page 1: ...ION 3 12 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Elevate Unit 3 Step 6 Install TXV 3 4 Step 7 Check Defrost The...

Page 2: ...suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windo...

Page 3: ...31 1 2 X 31 1 2 9 1 8 6 9 16 24 11 16 35 X 35 9 1 8 6 9 16 28 7 16 A05177 Fig 3 Tiedown Knockout Requirements On rooftop applications locate unit at least 6 in above roof surface STEP 4 Operating Ambi...

Page 4: ...m down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut driver Save the clamp 4 Remove R 22 TXV using...

Page 5: ...bserve the following S Use a brazing shield S Wrap service valves with wet cloth or use a heat sink material Outdoor units may be connected to indoor section using accessory tubing package or field su...

Page 6: ...l 1 2 turn 15 ft lb DO NOT OVER TIGHTEN Refrigerant Tubing and Sweat Connections Connect vapor tube to fitting on outdoor unit vapor service valves see Table 2 Connect liquid tubing to adapter tube on...

Page 7: ...outdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes makings sure wire ties on feeder tubes are secure an...

Page 8: ...lated 35 C minimum wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must b...

Page 9: ...ng system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated fully open liquid and vapor service valves 2 Unit is shipped with valve stem s closed...

Page 10: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 12 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 11: ...the start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 13 in the ON position When Quiet Shift switch is placed in ON position and a...

Page 12: ...claim refrigerant if temperature is lower Allow a tolerance of 3 F Heating Check Chart Procedure To check system operation during heating cycle refer to the Heating Check Chart on outdoor unit This ch...

Page 13: ...370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 398 112 107 102 97 405 113 108 103 98 412 114 109 104 99 419 115 110 105 100 426 117 112 107 102 433 118 113 108 103 440 119 1...

Page 14: ...longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and...