background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

Final Tubing Check

IMPORTANT: 

Check to be certain factory tubing on both indoor and

outdoor  unit  has  not  shifted  during  shipment.  Ensure  tubes  are  not

rubbing  against  each  other  or  any  sheet  metal.  Pay  close  attention  to

feeder tubes, making sure wire ties on feeder tubes are secure and tight.   

Step 8 – Make Electrical Connections

Be  sure field wiring complies with local and national fire, safety, and

electrical codes, and voltage  to system  is within limits shown on unit

rating  plate.  Contact local  power  company  for  correction  of  improper

voltage. See unit rating plate for recommended circuit protection device.

NOTE: 

Operation of unit on improper line voltage constitutes abuse and

could affect unit reliability. See unit rating plate.  Do not install unit in

system where voltage may fluctuate above or below permissible limits.

NOTE: 

Use copper wire only between disconnect switch and unit.

NOTE: 

Install  branch circuit disconnect of adequate size  per NEC to

handle  unit  starting  current.  Locate  disconnect  within  sight  from  and

readily accessible from unit, per Section 440-14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires from

disconnect  through  power  wiring  hole  provided  and  into  unit  control

box.

Connect Ground and Power Wires

Connect  ground  wire  to  ground  connection  in  control  box  for  safety.

Connect power wiring to contactor as shown in 

Fig. 9

.

A14028

Fig. 9 – Line Power Connections

Connect Control Wiring

Connect  to  Infinity  connections.    Only  two  wires  (AB)  to  Infinity

capable  indoor  unit  (furnace  or  fan  coil)  is  required.    Typical  4  wire

(ABCD) may be connected (see 

Fig. 5

IMPORTANT: 

This system requires the power supply to the outdoor

unit, and the indoor unit, for the UI to communicate with the outdoor

unit.

General Information

Use No. 18 AWG or larger color-coded, insulated (35°C minimum) wire

for low voltage control wires.
All wiring must be NEC Class 2 and must be separated from incoming

power leads. 
Use furnace transformer, fan coil transformer, or accessory transformer

for control power requirement of system accessories external to the OD

unit. The outdoor unit has its own transformer power.
Installations  using  greater  than  200  feet  of  low voltage wiring  should

consult  the  Infinity  wall  control  manual  for  additional  guidelines

regarding  daisy  chaining  wiring  method  and  terminating  resistors.

Never route control wiring in parallel to high voltage power wires when

possible  as  electrical  noise  may  transfer  and  generate  nuisance  fault

codes.  Where low  voltage  control and  high voltage  wires  must  cross

paths, do so at perpendicular angles to eliminate transferred noise.  
If  further  communication  issues  exist,  consider  using  shielded  low

voltage wires and only connect  shielding to C terminal at  end nearest

indoor coil.  

Final Wiring Check

IMPORTANT: 

Check  factory  wiring  and  field  wire  connections  to

ensure terminations are secured properly. Check wire routing to ensure

wires are not in contact with tubing, sheet metal, etc.

Step 9 – Compressor Crankcase Heater

This compressor has a standard crankcase heater.  Furnish power to the

unit a minimum of 24 hr before starting the unit for the first time. 

To  furnish  power  to  heater  only,  set  thermostat  to  OFF  and  close

electrical disconnect to outdoor unit.  

Power  is  not  required  to  the  indoor  unit  or  User  Interface  for  proper

operation  of  heater.    Crankcase  heater  will  however  be  intelligently

energized as needed even when the UI and indoor unit is not installed, as

long as there is power to the outdoor unit even if the indoor unit and UI

are not yet installed. 

Airflow Setup for Infinity Control Furnace or FE 

Fan Coil (communicating)

This  system  can  only  be  installed  with  Infinity-capable  indoor  and

Infinity  System  Control  .  When  using  an  Infinity  control,  airflow  is

automatically selected based on equipment size.  The user has the option

of  selecting Comfort, Efficiency  and Max airflow  for  Cooling  modes.

These should  be  selected  based  on  balance between  the  homeowner’s

comfort  and  energy  consumption  expectations.  See  User  Interface

Installation Instructions for additional available adjustments. 

NOTE: 

Ensure  control  is  updated  with  the  latest  available  software

version.
Due to using a communicating control with the fan coil or the furnace,

dip  switch  adjustments  are  not  necessary.    The  outdoor  unit

configuration and the indoor airflows are determined by communicating

control setup.

Verify that the PCM, VFD and wall control are the latest software before

proceeding with the next steps.

Step 10 – Install Accessories

There  are  no  refrigeration  circuit  or  electrical  accessories  required  or

available for installation within the unit.  External to the unit, the same

accessories  such  as  the  liquid  line  solenoid,  support  feet,  snow  rack,

wind baffle etc., are available on other Carrier units can also be used on

this  line  of  product.    Refer  to  the  individual  Installation  Instructions

packaged with kits or accessories when installing.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do  not  supply  power  to  unit  with  compressor  terminal  box  cover

removed.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The  unit  cabinet  must  have  an  uninterrupted  or  unbroken  ground  to

minimize personal injury if an electrical fault should occur. The ground

may  consist  of  electrical  wire  or  metal  conduit  when  installed  in

accordance with existing electrical codes.

DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES

TERMINAL

BLOCK

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: