background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

On rooftop applications, mount on level platform or frame. Place unit

above a load-bearing wall and isolate unit and tubing set from structure.

Arrange supporting members to adequately support unit and minimize

transmission  of  vibration  to  building.  Consult  local  codes  governing

rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind

baffles.  Consult  the  Service  Manual  -  Residential  Split  System  Air

Conditioners and Heat Pumps Using Puron® Refrigerant for wind baffle

construction.

NOTE: 

Unit must be level to within ±2° (±3/8 in./ft,±9.5 mm/m.) per

compressor manufacturer specifications.

Step 3 – Clearance Requirements

When  installing,  allow  sufficient  space  for  airflow  clearance,  wiring,

refrigerant  piping,  and  service. Allow  24  in.  (609.6  mm)  clearance  to

service  end  of  unit  and  48  in.  (1219.2  mm)  (above  unit.  For  proper

airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8

mm) on all remaining sides must be maintained. Maintain a distance of

24 in. (609.6 mm) between units.  Position so water, snow, or ice from

roof or eaves cannot fall directly on unit. 
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof

surface. 

Step 4 – Operating Ambient

The  minimum  outdoor  operating  ambient  in  cooling  mode  is  55°F

(12.78°C)  without  low  ambient  cooling  enabled,  and  the  maximum

outdoor operating ambient in cooling mode is 125°F (51.67°C). 

Step 5 – Elevate Unit

Elevate  unit  per  local  climate  and  code  requirements  to  provide

clearance above estimated snowfall level and ensure adequate drainage

of unit.

Step 6 – In Long-Line Applications, Install Liquid-Line 

Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths of      greater

than 80 ft. (24.38 m) and/or when elevation difference between indoor

and  outdoor  unit  is  greater  than  ±20  ft.  (±6.10  m),  follow  the  piping

configuration  and  liquid  line  solenoid  valve  (LSV)  accessory

requirements from the Residential Piping and Long-line guideline. CCH,

start  gear  and  piston  changes  do  not  apply.  If  required  by  Long-Line

Guideline,  install  LSV  kit,  part  no.  KHALS0401LLS.  LSV  should  be

installed within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing

toward outdoor unit. 
Make the necessary electrical connections as shown in 

Fig. 4

 and 

Fig. 5

and  by  following  the  Installation  Instructions  included with  accessory

kit. 

IMPORTANT: 

Flow arrow must point toward outdoor unit.

A180243

Fig. 4 – Liquid Line Solenoid Electrical Connection

(Required for long line applications)

A150776

Fig. 5 – Infinity Furnace or Fan Coil Wiring with Communicating 

Variable Speed AC

Step 7 – Make Piping Connections

CAUTION

!

UNIT OPERATION HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Do not allow water and/or ice to build up in base pan.

CAUTION

!

UNIT OPERATION HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Locate  the  unit  in  such  a  way  that  it  is  stable  in  all  circumstances

including adverse weather conditions. 

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or death.

Relieve  pressure  and  recover  all  refrigerant  before  system  repair  or

final  unit  disposal.  Use  all  service  ports  and  open  all  flow-control

devices, including solenoid valves.

Green

Yellow

White

     
     Connection (optional)

Red

     LLS

LS

User Interface

Optional Remote

Room Sensor

                      Furnace or
                      Fan Coil

Variable Speed

AC or HP

A

B

C

D

C

S2

A

B

C

D

A

B

C

D

S1

D

C

B

A

Wall Control

HP or AC

OA

T

R

Y

O

W

C

HUM

C

Humidifier

24v

ac

Furnace or Fan Coil

’C’ connection optional

Sheild Cable

D not required

Unused Wires

WT

YL

GN

D

C

B

A

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: