background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

16

If the outdoor air or coil thermistor should fail, the control will flash the

appropriate fault code (see 

Table 7

.)  

IMPORTANT: 

The outdoor air thermistor and coil thermistor should be

factory mounted in the final locations.  Check to ensure thermistors are

mounted properly (See 

Fig. 28

, 

Fig. 29

 and 

Fig. 30

).

Outdoor Air Thermistor

The outdoor air thermistor is a 10Kohm resistor used for multiple system

operations.    It  provides  the  outdoor  air  temperature  to  the  primary

control  module  and  user  interface.    It  is  essential  for  controlling  the

system  and  is  used  in  almost  all  modes  of  operation.    The  sensor  is

mounted in the control box per 

Fig. 28

.

A200045

Fig. 28 – Outdoor Air Thermistor Mounting Location

Outdoor Coil Thermistor

The  outdoor  coil  thermistor  is  a  10Kohm  resistor  used  for  multiple

system  operations.    It  provides  the  coil/liquid  line  temperature  to  the

primary control module and user interface.  It is used for low ambient

operation  and  assistance  with  OAT  temperature  measurement.    The

sensor  must  be  securely  mounted  to  the  tube  connecting  the  coil  and

distributor.  See 

Fig. 29

 for proper placement.  See 

Table 4

 for proper

resistances.

A200046

Fig. 29 – Outdoor Coil Thermistor Mounted on Coil

Discharge Thermistor (ODT)

Discharge thermistor is used for protection against over temperature of

the  compressor  and  the  discharge  superheat  calculations.    Proper

mounting is required to ensure that the unit exits the start-up mode.  The

ODT is located on the compressor discharge stub-out (see 

Fig. 30

).

A200086

Fig. 30 – Discharge Thermistor (ODT) Mounting Locations

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of outdoor air

thermistor (OAT) and/or outdoor coil thermistor (OCT). 

If  the OAT  sensor should  fail the outdoor  unit will operate  at  a  fixed

speed. 

If the OCT sensor should fail, the outdoor unit will operate at a fixed

speed. 

Variable Speed Compressor Winding Resistance

This  compressor  operates  with  3-phase  variable  frequency  PWM

variable  voltage.  For  troubleshooting  certain  fault  codes    related  to

compressor resistances, follow these steps:

1. Disconnect compressor power leads from the inverter terminals, 

U (YEL), V (RED), and W (BLK).

2. Measure  the resistance between YEL  to RED, YEL to  BLK,  and

RED to  BLK and compare to 

Table 6

 values. Each resistance set

should be equal.

3. Measure the resistance to ground for each lead.

4. If  the  resistances  are  correct  then  reconnect  power  leads  to

appropriate terminal.

5. If  the  resistances  appear  to  be  abnormal,  it  will  be  necessary  to

measure the resistance at the compressor fusite terminals.

6. Remove  the  sound  blanket  and  harness  plug,  measure  the

resistances, and compare to 

Table 6

.

7. Reinstall  compressor  sound  blanket  making  sure  discharge

thermistor and compressor power harness are routed as they were

from the factory

Table 5 – ODT Resistance Values versus Temperatures

TEMPERATURE (°C)

RESISTANCE (K OHMS)

25

50.15 + / - 5.0%

75

7.565 + / - 3.0%

125

1.7  + / - 1.4%

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage and/or

improper operation.

In order to minimize the ambient influence, make sure the thermistor

curved surface hugs the pipe surface and is secured tight using the wire

tie fished through the original slot, insulating polymer body.

Table 6 – Variable Speed Compressor Resistances

(winding resistance at 68°F

?

 (20°F)

WINDING

24

36

48

60

Between terminals T1, T2, and T3

.74

.453

.424

.424

Between terminal & ground

>1 mega OHM

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: