background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

15

Outdoor Pressure Transducers

There are two pressure transducers installed on this unit.  One is located

at the discharge of the compressor and the other is located at the suction

of the compressor.  These are labeled as "P1" and "P2" on the PCM and

the  connection  to  the  control  board  can  be  interchanged  without

impacting  the  pressure  measurements  or  system  control.    These

transducers  have a  range  from  0  to 620 psig and  are  used  for system

protection, calculating superheats, and diagnostics.  

Crankcase Heater Operation

This  unit  has a  compressor  crankcase  heater  that  will  be  energized to

prevent the compressor from being the coldest part of the system thus

enhancing  the  reliability.    The  indoor  unit  and  UI  do  not  need  to  be

installed for the crankcase heater to operate properly.

Infinity Controlled low ambient cooling

This unit is capable of low ambient cooling down to 0F (-17.8C) with

Low Ambient enabled on the Infinity Control. A low ambient kit is not

required. 
The  Infinity  Control  provides  an  automatic  evaporator  coil  freeze

protection algorithm  that  eliminates the  need for  an  evaporator  freeze

thermostat.  The only accessory that may be required is wind baffles in

locations which are likely to experience cross winds in excess of 5 miles

an hour. This generally occurs only on roof and open area applications. 
Low ambient cooling must be enabled in the User Interface setup. The

outdoor unit fan will cycle on and off based on outdoor coil temperature,

outdoor air temperature, and suction pressure measurements to keep the

compressor running at the proper conditions.

Troubleshooting

Systems Communication Failure

If communication with the Infinity control is lost with the User Interface

(UI),  the  control  will  flash  the  appropriate  fault  code  (see 

Table 7

).

Check the wiring to the User Interface and the indoor and outdoor units

and power. 

Model Plug

Each control board contains a model plug. The correct model plug must

be installed for the system to operate properly (see 

Table 3

).

The model plug is used to identify the type and size of unit to the control. 

On new units, the model and serial numbers are input into the board’s

memory  at  the  factory.  If  a  model  plug  is  lost  or  missing  at  initial

installation, the unit will operate according to the information input at

the factory and the appropriate error code will flash temporarily. An RC

replacement  board  contains  no  model  and  serial  information.  If  the

factory control board fails, the model plug must be transferred from the

original board to the replacement board for the unit to operate.

NOTE: 

The model plug takes priority over factory model information

input at the factory.  If the model plug is removed after initial power up,

the unit will operate according to the  last valid model plug installed, and

flash the appropriate fault code temporarily.

Pressure Switch Protection

The outdoor unit is equipped with high pressure switch. If this switch

opens the VFD will lose line power and the compressor and fan motor

will not operate.  The high pressure switch opens at 670 +/- 10 psig and

closes at 470 +/- 25 psig.  If this occurs the PCM will set a diagnostic

code  per  table  7.    The  outdoor  pressure  transducer  installed  at  the

discharge of the compressor is monitored by the PCM and the PCM will

take action to avoid the high pressure switch from opening.  

Compressor Protection

The Primary Control Module continuously monitors the operation of the

compressor  and  takes  action  when  it  is  nearing  the  edge  of  the

boundaries  of  reliable  operation.    The  PCM  utilizes  the  pressure

transducers to maximize the reliability and minimize the off time of the

system  due  to  operation  outside  of  the  compressor  boundaries.    The

PCM  takes  different  actions  for  each  edge  of  the  boundary,  but  each

culminates  in  a  reduction  of  compressor  speed  to  the  minimum

allowable and, in the worst case, will power off the compressor to avoid

excursions outside the boundaries.  If a shutdown does occur then the

PCM will set a diagnostic code per 

Table 7

.

Line Voltage Diagnostics

The primary control module monitors the line voltage for low and high

voltage events.  If a low voltage or high voltage event occurs and another

fault occurs simultaneously the PCM will set a fault that indicates this

was due to the system conditions and not the components.  If this occurs

several  times  in  a  row  the  PCM  will  set  a  malfunction  and  lock  out

operation for 1-4 hours, depending on the condition.  Refer to 

Table 7

 for

the list of  fault codes and 

Table 8

 for the list of malfunctions and the

lockout times for each one.

Forced Defrost Pins (J9)

The forced defrost pins have several functions.  When shorting the pins

using a clip wire the below functions can be executed:

• If the pins  are  shorted more than 1 second and less  than 5 seconds

when the system has just turned off and an active call for cooling is

present, the 5 minute initial on-time will be defeated.

• If the unit is in the OFF mode and the pins are shorted at power on the

unit will enter into Status Code Recall Mode. 

Temperature Thermistors

Thermistors  are  electronic  devices  which  sense  temperature.   As  the

temperature increases, the resistance decreases.  Thermistors are used to

sense  outdoor  air  (OAT),  coil  temperature  (OCT),  and  the  outdoor

discharge thermistor (ODT) at the outlet from the compressor. 

Refer to 

Table 4

 and 

Table 5

 for resistance values versus temperature for

the OAT and OCT. 

Table 3 – Model Plug Information

MODEL

NUMBER

MODEL  PLUG

NUMBER

PIN RESISTANCE

(K-ohms)

Pins 1-4

Pins 2-3

24VNA624

HK70EZ009

5.1

91

24VNA636

HK70EZ021

11

39

24VNA648

HK70EZ033

18

11

24VNA660

HK70EZ045

18

220

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage and/or

improper operation.
Do not attempt to install an incorrect model plug as this could cause

some units to operate incorrectly and fail prematurely.

Table 4 – Resistance Values versus Temperature

TEMPERATURE

RESISTANCE (ohms)

25.0°C (77.0°F)

10.0 + / - 2.3%

0.0°C (32.0°F)

32.6 + / - 3.2%

-17.8°C (0 °F)

85.5 + / - 3.4%

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: