24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

14

Amber Status Light

Amber colored STATUS light indicates operation and error status.  See

Table 7

 for definitions. 

5x7 LED Matrix

The  Primary  Control  Module  (PCM)  is  equipped  with  a  5x7  LED

matrix.  This matrix will display the 4 highest priority diagnostic codes

in a scrolling fashion with 2 seconds in between each code.  At the end

of  the  4th  highest  priority  diagnostic  code  there  is  a  5  second  pause

before the list repeats.

VFD Communications Light

The PCM is equipped with a bi-color LED for indicating successful or

unsuccessful communication  with the VFD.  This  LED  is located just

below the VFD-PCM communication port on the PCM.  The LED will

flash  green  when  good  messages  are  received  from  the VFD  and  red

when bad or no messages are received from the VFD.  

Bluetooth® Module

This unit is equipped with a module, which includes Bluetooth wireless

technology that allows a user to connect via an application on a phone or

tablet.  It is recommended that the Bluetooth Module be activated during

the installation process.  

Follow these steps to download and activate Bluetooth Module:

1. Download the app

– Search  the  App  Store™  or  Google  Play™  for  Carrier  Service

Technician to download.  The app is available on phone and tablet

devices.   If  you  already have  the  app  downloaded, please  ensure

you have updated to latest version. 

To Activate Bluetooth Module:

1. Login  to  the  Carrier  Service  Technician  app  using  your

HVACPartners username and password.

2. On the App  Home screen,  tap  the Connect  to  Equipment  button.

Please  ensure  your  equipment  is  powered  on  and  your  mobile

device  is  within  10  feet  of  the  equipment  throughout  this  whole

process

NOTE: 

In  order  to  connect  to  equipment  using  Bluetooth,  you  must

have Bluetooth enabled on your mobile device, and you must allow the

Service  Tech  app  to  access  Bluetooth  and  location  services  in  your

device  permissions.    For  more  information  on  how  to  enable  these

features  and  permissions,  please  consult  documentation  from  your

device manufacturer. 

3. The  app  will  scan  for  nearby  Bluetooth  enabled  equipment.    To

activate a new unit, the app will display "New Equipment".   Tap on

that item and then select the Pair button

4. The  app  will  display  the  equipment  Serial  and  Model  number.

Please confirm these are correct for the equipment you are trying to

activate and tap continue. 

5. The  app  will  now  automatically  progress  through  the  activation

process.    Once  the  steps  are  complete,  the  unit  is  activated

successfully  and  your  device  will  be  automatically  paired  to  the

equipment. 

NOTE: 

You will only have to perform this activation once and you will

now be able to pair to this equipment directly with the app in the future. 

Variable Frequency Drive (VFD)

The  inverter  or  variable  frequency  drive  (VFD)  is  located  inside  the

control  box.  This  is  an  air-cooled  device  that  communicates  with  the

PCM  and  drives  the  compressor  to  the  demanded  RPM.  The  VFD

provides DC voltage to the fan motor and sends a fan RPM signal to the

electronics on the fan motor.  The VFD changes the line voltage to 300

volts 3-phase, and varies the frequency to drive the compressor at the

desired RPM.  

Input Filter Board

The input filter board connects the line voltage to the VFD.  The input

filter board ensures the inherent electrical noise generated by VFD does

not affect other electronics in the household and contains fuses to protect

against excess input current. 

Reactors

There  are  either  1  or  2  reactors  per  model.    These  reactors  are  large

inductors and must be connected to the VFD to operate.  

Variable Speed Compressor

This unit contains a high-side variable speed compressor that has a wide

operating  range.  Some  models  contain  variable  speed  rotary

compressors while others contain variable speed scroll compressors.  All

of the variable speed compressors operate on 300VDC provided by the

inverter. This compressor can only be operated by the specific inverter

supplied with the unit.

Time Delays

The unit time delays include:

• Five minute time delay to start cooling operation when there is a call

from the user interface. To bypass this feature, momentarily short and

release Forced Defrost pins.

• Five  minute  compressor re-cycle  delay  on  return  from a  brown-out

condition.

Vapor Injection Electronic Expansion Valve (EXV-VI)

Some  models  in  this  product  family  contain  a  secondary  EXV  for

controlling  the  vapor  injection  circuit.   This  circuit  is  comprised  of  a

brazed  plate  heat  exchanger  (BPHE),  an  EXV  (EXV-VI)  and

interconnecting tubing.  The PCM drives this EXV closed except for in

high  ambient  cooling  in  efficiency  mode.    The  control  of  the  vapor

injection  circuit  allows  greater  capacity  and  efficiency  than  when  not

operational.

BLDC Inverter-Controlled Fan Motor

The fan  motor  included  in this  unit  is  a  Brushless DC  motor with an

integrated control module. The control module is supplied DC voltage

from the VFD.  The speed command is provided from the VFD through

a 0-5V signal.  The commanded speed is determined by the PCM and is

communicated  through  Modbus  to  the  VFD.    The  motor  cannot  be

connect  to  line  voltage.    Fan  motor  speed  varies  based  on  outdoor

ambient temperature and compressor speed.  The fan motor may cycle

off and on if extremely low airflow is desired.

Pressure Equalization Valve (PEV)

The PEV is located at the discharge of the compressor and the inlet to the

accumulator.  The purpose of the PEV is to prevent the compressor from

starting with a high pressure differential, which can cause compressor

damage.    Occasionally  the  unit  may  experience  a  brief  starting  delay

while the PEV equalizes pressure before startup.

High Pressure Switch

This unit contains a high pressure switch to protect against high pressure

conditions.  This switch must be closed for the VFD to be powered. 

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.
Do not attempt to apply line voltage directly to the compressor. This

will destroy the compressor

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...