background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

9

5. If the outdoor ambient temperature is between 65°F and 105°F and

the  indoor  temperature  is  between  65°F  and  80°F  then  select

"subcool" (See 

Fig. 13

).

6. The  next  screen  will  show  the  target  subcooling  that  should  be

attained  while  charging  (see 

Fig. 14

).    Before  selecting  "Start"

verify that the service valves are open. 

7. Upon  selecting "Start"  the system  will  enter into  charging  mode.

The outdoor compressor and fan will operate at a fixed speed and

the  UI  will  display  a  stabilization  time  (see 

Fig. 15

).    Once  this

clock  reaches  zero  the  charge  can  be  adjusted  to  meet  the  target

subcooling.

8. Compare  the  subcooling  taken  at  the  liquid  service  valve  to  the

subcooling target listed on the charging screen.  Add refrigerant if

the  subcooling  is  low  and  remove  charge  if  subcooling  is  high.

Tolerance should be +0 and -2°F.  

9. If any adjustment is necessary, add or remove the charge slowly (no

greater than 0.5 lb per minute) and allow system to operate for 15

minutes to stabilize before declaring a properly charged system. 

The use of a commercial charge metering device (restrictor) such as

Imperial  liquid  low  side  charger  model  535-C  or  Watsco

ChargeFaster  model  CH200  is  recommended  when  adding

refrigerant to an operating system.  This prevents potential damage

of liquid slugging of the compressor and allows the subcooling to

stabilize quicker.

10. If  the  outdoor  ambient  is  below  65°F  or  above  105°F  then  the

refrigerant must be weighed in.  Press the "weigh-in" option in the

"refrigerant charge" screen (see 

Fig. 16

).  

11. Press the text "line set" and "vapor line" to choose line set length

and vapor line diameter (see 

Fig. 17

 and 

Fig. 18

). After complete,

press "next" to advance to next screen.  

12. If this is a new install, i.e. the ODU is factory charged, then select

"new install" in the "charging mode selection" screen (see 

Fig. 19

)

.

13. The "new install charge weigh-in" screen will show the additional

charge that needs to be added to the system to account for the ID

coil and line set (see 

Fig. 20

).

14. If this is a complete re-charge then select "complete recharge" in the

"charging mode selection" screen.  This screen will show the total

amount of charge to add for the indoor coil, line set, and outdoor

unit  (see 

Fig. 21

).    The  "charge  breakdown"  screen  shows  the

charge required for each component of the system.

15. Add additional required charge for line set and indoor coil size then

fully open liquid and vapor service valves. 

Charge level should then be appropriate for the system to achieve

rated capacity. The charge level could then be checked at another

time when both the indoor and outdoor temperatures are in a more

favorable range.  This ensures maximum efficiency and reliability. 

If lineset is less than 15 feet (4.57 m) in length, charge removal may

be necessary and will be shown as a negative number on UI screen.

UI screen displays charge in lb and oz, while unit rating plate is in

decimal format.

A200031

Fig. 13 – Select Refrigerant Subcooling

A200032

Fig. 14 – Liquid Service Valve Subcooling Target

A200033

Fig. 15 – Charging Mode Information Screen

A200034

Fig. 16 – Weigh-in Option for charging below 65°F OAT and above 

105°F OAT

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in improper unit operation.

For new installations only

: Add additional refrigerant due to indoor

coil, line set and vapor line settings. Outdoor unit is pre-charged with

weight of refrigerant shown on rating plate.

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: