1-2. HIGH TEMPERATURE
・
HIGH VOLTAGE CAUTION
1-2-1.Do not touch the Chiller during operation since the surface of it reaches a high
temperature.
1-2-2. Do not touch the absorbent pump, the refrigerant pump, the purge pump during
operation, since they reach a high temperature.
1-2-3. Do not touch the junction box during operation, since it contains high pressure wiring.
1-2-4. Do not touch the terminal box during operation, since it contains high voltage wiring.
1-3. USE ENVIRONMENT
1-3-1. Machine room
Absorption Chiller is indoor use ONLY.
IP number of Absorption Chiller is IP40.
Please keep the machine room temperature between 5
℃
and 40
℃
for protection of the
solution crystallization during chiller shut down. Please keep the humidity in the
machine room within 90%.
1-3-2. Field wiring
For CE, please connect to power source by overvoltage category
Ⅲ
, and to other wiring
by overvoltage category
Ⅱ
.
1-3-3. Altitude
Please install Absorption Chiller at a height of less than 1000m above sea level.
If the location is higher than 1000m above sea level, please contact Carrier agent.
1-4. WATER TREATMENT
Refer to "4. Maintenance" section.