Alarm of sensor
Do the sensors measuring each area of the
Chilled water inlet
Chiller have short circuits or open
temperature sensor has failure.
circuits?
→
Check all the sensors of the
Cooling water inlet
Chiller and contact Carrier
temperature sensor has failure.
service agent.
Cooling water outlet
NOTE :
temperature sensor has failure.
The Chiller automatically
stops for safety reasons when either
Cooling water intermediate
the generator’s
temperature sensor has failure.
temperature sensor or Chilled
water temperature sensor has
Condenser temperature
alarm.
sensor has failure.
It does not stop when the other
sensors have alarm, but this could
cause control failure. Please
contact Carrier service agent as
soon as possible.
Refrigerant temperature
sensor(Evaporator)has failure.
Driving hot water inlet
temperature sensor has failure.
Driving hot water control valve
outlet temperature sensor has failure.
Driving hot water outlet
temperature sensor has failure.
Diluted solution temperature
sensor (Absorber outlet ) has
failure.
Chilled water outlet
temperature sensor has failure.
High temperature generator’s
temperature sensor has failure.
Purge tank pressure
sensor has failure.
37