66
Maintenance
Navigation: i-Vu
®
/ Field Assistant: Properties > Control Program
> Maintenance
-
Fan VFD Enable Test
– When set to
Enable
,
Binary Output #4
is enabled for up to 5 minutes.
D: Disable
R: Disable/Enable
Fan VFD Speed % Test
– When set to a value greater than 0,
Analog Output #1
is enabled for up to 5
minutes.
Binary Output #4
is also enabled with this test.
D: Disable
R: Disable/Enable
Bypass Valve Test
– When set to
Enable
,
Binary Output #2
is enabled for up to 5 minutes to open the
bypass valve. When set to
Disable
,
Binary Output #1
is enabled to close the bypass valve.
D: Disable
R: Disable/Enable
Bypass Valve % Test
– When set to a value greater than 0,
Analog Output #2
is enabled for up to 5
minutes.
D: Disable
R: Disable/Enable
Alarm Indicator Test
– When set to
Enable
,
Binary Output #3
is enabled for up to 5 minutes.
D: Disable
R: Disable/Enable
Point Name – Description
Default/Range
Point Name — Description
Default/Range
Unit
Fan VFD Run Status
— Indicates that the fans’, variable frequency drive is running.
R: Off/On
Ext Demand Limit Status
— The external demand limit input status.
R: Off/On
Leaving Water Temp
— The current leaving water temperature value.
R: -56 to 245F
Entering Water Temp
— The current entering water temperature value.
R: -56 to 245F
Leaving Water Temp Source
— The source of the
Leaving Water Temp
value.
States:
-
N/A
- No sensor value associated with this device
-
Local
- A physical sensor is wired and connected to the appropriate input channel of this controller
-
Network
- A network sensor value provided to this controller
-
Locked Value
- The controller’s sensor input is manually locked to a specific value
R: N/A
Local
Network
Locked Value
Entering Water Temp Source
— The source of the
Entering Water Temp
value.
States:
-
N/A
- No sensor value associated with this device
-
Local
- A physical sensor is wired and connected to the appropriate input channel of this controller
-
Network
- A network sensor value provided to this controller
-
Locked
Value
- The controller’s sensor input is manually locked to a specific value
R: N/A
Local
Network
Locked Value
Outdoor Air Temp Source
- The source of the
Outdoor Air Temp
value.
States:
-
N/A
- No sensor value associated with this device
-
Local
- A physical sensor is wired and connected to the appropriate input channel of this controller
-
Network
- A network sensor value provided to this controller
-
Locked
Value
- The controller’s sensor input is manually locked to a specific value
R: N/A
Local
Network
Locked Value
Control Setpoint Source
— The control setpoint value's source.
States:
-
Local
- The leaving water temperature setpoint software point
-
Network
- A network value provided to this controller
R: Local
Network
Occupancy
Occupancy Status
— The module's occupancy status.
R: Unoccupied/Occupied
BAS On/Off
— Determines the occupancy state of the controller and can be set over the network by another
device or third party BAS.
Options:
-
Inactive
— Occupancy is determined by a remote contact
-
Occupied
— The controller is always in the occupied mode
-
Unoccupied
— The controller is always in the unoccupied mode
D: Inactive
R: Inactive
Occupied
Unoccupied
Schedules
— The controller's occupancy status based on the local schedule.
R: Unoccupied/Occupied
Remote Contact
— The current status of Input Channel #4.
R: Inactive/Active
Global Occupancy
— The System Occupancy network input's current state.
D: Unoccupied
R: Unoccupied/Occupied
Reset
Cooling Supply Setpoint Reset
— The leaving water temperature setpoint's current reset method.
R: Inactive
OAT Reset
Demand Limit
Calculated OA Clg Reset
— Based on outdoor air temperature, the amount of cooling reset.
R: __F
Demand Limit
Ext Demand Limit
— The current status of Input Channel #6.
R: Inactive/Active
System Cooling Demand Level
— This module's system cool demand level currently in effect.
R: 0 to 3
Summary of Contents for 09FC020
Page 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Page 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Page 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Page 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Page 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Page 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Page 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Page 69: ......