background image

48

013

NOTE 1

Overcurrent

The inverter peak current limit 

(approximately 200% of the rated current) 

is exceeded. The warning lasts 

approximately 1.5 s, then the frequency 

converter trips and issues an alarm. Shock 

loading or quick acceleration with high-

inertia loads can cause this fault. If the 

acceleration during rampup is quick, the 

fault can also appear after kinetic back-up. 

If extended mechanical brake control is 

selected, a trip can be reset externally.

 

• Remove  the  power  and  check  if  the  motor

shaft can be turned. 

• Check  that  the  motor  size  matches  the  fre

-

quency converter. 

• Check that the motor data is correct in param

-

eters 1–20 to 1–25.

 

014

NOTE 1

Ground Fault

There is current from the output phase to 

ground, either in the cable between the 

frequency converter and the motor or in the 

motor itself. This fault is detected during 

motor operation.

 

• Remove power to the frequency converter and

repair the ground fault. 

• Check for ground faults in the motor by mea

-

suring  the  resistance  to ground  of  the  motor

cables and the motor with a megohmmeter.

 

015

Alarm

Hardware 

Mismatch

A fitted option is not operational with the 

present control board hardware or software  

Record the value of the following parameters and 

contact Danfoss:

•  15-40 FC Type 

• 15-41 Power Section 

• 15-42 Voltage 

• 15-43 Software Version 

• 15-45 Actual Typecode String 

• 15-49 SW ID Control Card 

• 15-50 SW ID Power Card 

• 15-60 Option Mounted 

• 15-61  Option  SW  Version  (for  each  option

slot)

 

016

Alarm

Short Circuit

There is short-circuiting in the motor or 

motor wiring

 

• Remove the power to the frequency converter

and repair the short circuit

 

017

NOTE 1

Control Word 

Timeout (Serial 

Communication 

Failure)

There is no communication to the 

frequency converter. The warning is only 

active when 8-04 Control Word Timeout 

Function is NOT set to [0] Off. If 8-04 

Control Word Timeout Function is set to [5] 

Stop and Trip, a warning appears and the 

frequency converter ramps down until it 

stops, and then it displays an alarm

 

Check the connections on the serial 

communications cables including the shields and 

termination resistors.

8-04 Control 

Timeout 

Function

023

Warning

Internal Fan 

Fault

Monitors operation of the internal cooling 

fan

 

Check for proper fan operation, cycle power to 

VFD and confirm that fan operates at startup

 

029

NOTE 1

Heat Sink 

Overtemperature

The maximum temperature of the heat sink 

has been exceeded. The temperature fault 

does not reset until the temperature drops 

below a defined heat sink temperature. The 

trip and reset points are different based on 

the frequency converter power size

 

• Ambient temperature too high. 

• Motor cables too long. 

• Incorrect  airflow  clearance  above  and  below

the frequency converter. 

• Blocked  airflow  around  the  frequency

converter. 

• Damaged heat sink fan. 

• Dirty heat sink.

 

030

NOTE 1

Motor Phase U 

Missing

Motor phase U between the frequency 

converter and the motor is missing

 

Remove the power from the frequency converter 

and check motor phase U

4-58 Missing 

Motor Phase 

Function

031

NOTE 1

Motor Phase V 

Missing

Motor phase V between the frequency 

converter and the motor is missing

 

Remove the power from the frequency converter 

and check motor phase V

4-58 Missing 

Motor Phase 

Function

032

NOTE 1

Motor Phase W 

Missing

Motor phase W between the frequency 

converter and the motor is missing

 

Remove the power from the frequency converter 

and check motor phase W

4-58 Missing 

Motor Phase 

Function

034

NOTE 1

Fieldbus 

Communication 

Fault

The fieldbus on the communication option 

card is not working

 

Check the communication wiring connections, 

including the shield. Check the termination 

resistors.

 

036

NOTE 1

Mains Failure

This warning/alarm is only active if the 

supply voltage to the frequency converter 

is lost and parameter 14-10 Mains Failure 

is not set to option [0] No Function

 

Check the fuses to the frequency converter, mains 

supply to the unit and the phase imbalance (±3%)  

039

Alarm

Heat Sink Sensor No feedback from the heat sink 

temperature sensor

 

The signal from the IGBT thermal sensor is not 

available on the power card. The problem could 

be on the power card, on the gatedrive card, or the 

ribbon cable between the power card and gate 

drive card

 

045

Alarm

Ground Fault

Ground fault detected on motor start

 

• Remove power to the frequency converter and

repair the ground fault. 

• Check for ground faults in the motor by mea

-

suring  the  resistance  to ground  of  the  motor

cables and the motor with a megohmmeter.

 

046

Alarm

Power Card 

Supply

The supply on the power card is out of 

range

 

Contact Carrier Service

 

047

NOTE 1

24V Supply Low The supply on the power card is out of 

range

 

Contact Carrier Service

 

049

NOTE 1

Speed Limit

When the speed is outside of the specified 

range in parameter 4-12 Motor Speed Low 

Limit [Hz] and parameter 4-14 Motor Speed 

High Limit [Hz], the frequency converter 

shows a warning. When the speed is below 

the specified limit in parameter 1-87 Trip 

Speed Low [Hz](except when starting or 

stopping), the frequency converter trips

 

Contact Carrier Service

1-87 Trip 

Speed Low 

[Hz]

059

Warning

Current Limit 

Exceeded

The current is higher than the value in 

parameter 4-18 Current Limit.

 

Ensure that motor data in parameters 1–20 to 1–

25 are set correctly. Contact Carrier Service

 

Table 13 — 

Alarms List (cont)

CODE WARNING/

ALARM

DESCRIPTION

POSSIBLE CAUSES

DOES MACHINE

SHUT DOWN

ACTION TO

BE TAKEN

REFERENCE

PARAMETER

Summary of Contents for 09FC020

Page 1: ...ART SNOW CLEARING START UP 53 SERVICE 53 Alarms 53 NON OPERATIONAL COMPONENT ALARM REVERSE LOAD WATER FLOW ALARM THERMISTOR ALARM FAN VFD FAILURE Alarm Troubleshooting 54 LEAVING WATER TEMPERATURE ALA...

Page 2: ...been given instruction DANGER Electrical shock can cause personal injury and death After unit power is disconnected wait at least 20 minutes for the Variable Frequency Drives VFD capacitors to discha...

Page 3: ...itrogen Shipping Charge 5 psig Fans and Motors Shrouded Axial Type Vertical Discharge Quantity 4 6 8 10 12 14 16 Maximum Speed rpm r s 1140 19 Coils Type Round Tube Plate Fin No of Coils 4 6 8 10 12 1...

Page 4: ...at Cu Tube Al Fin Not Used Not Used Piping Valve Options 3 way Valves Electrical Options 0 Single Point Power Fused Disconnect High SCCR Control Options BACNet Shipping Options 0 Coil Covers 1 Coil Co...

Page 5: ...922 1069 916 1063 884 1069 932 1127 Table 3 Unit Operating Corner Weights kg UNIT SIZE OPERATING WEIGHT AT CORNER WEIGHTS LBS A B C D E F G H 020 450 516 456 523 030 639 754 643 758 040 433 501 418 4...

Page 6: ...consists of coil protection only Skids are not provided unless selected as a shipping option If overhead rigging is not available at the jobsite the unit should be placed on a skid or pad before drag...

Page 7: ...ove the top of the unit and coils 5 If overhead rigging is not available the unit can be moved on roller or dragged When unit is moved on roller the unit steel skid if equipped must be removed To lift...

Page 8: ...8 Fig 5 09FC 020 Unit Dimensions...

Page 9: ...9 Fig 6 09FC 030 Unit Dimensions...

Page 10: ...10 Fig 7 09FC 040 Unit Dimensions...

Page 11: ...11 Fig 8 09FC 050 Unit Dimensions...

Page 12: ...12 Fig 9 09FC 060 Unit Dimensions...

Page 13: ...13 Fig 10 09FC 070 Unit Dimensions...

Page 14: ...14 Fig 11 09FC 080 Unit Dimensions...

Page 15: ...supplied See Fig 5 11 Be sure unit is level to within 1 8 in 3 2 mm per foot for factory sup plied drains to operate properly NOTE For units that are point loaded such as those using rubber and shear...

Page 16: ...DE OF UNIT BASE RAIL OUTER SIDE OF UNIT BASE RAIL 0 1 3 4 44 mm 1 50 DIA 38 mm RIGGING HOLE B B 0 5 127 mm 0 875 DIA 22 mm MOUNTING HOLE MOUNTING PLATE 0 3 15 16 100 mm 0 1 9 16 39 89 mm REF 0 7 7 8 2...

Page 17: ...tems equipment should be provided to eliminate all air from the system The amount of air that water can hold in solution depends on the pressure and temperature of the water air mixture Air is less so...

Page 18: ...properly in the bolt hole 7 Tighten the nuts evenly by alternating sides until metal to metal contact occurs at the bolt pads Make sure the housings keys engage the grooves completely NOTE It is impor...

Page 19: ...e reattached add the joining pipe include in the Modular Piping Accessory Part No 09FC70000801 Attach with the existing couplings Add insula tion back to the tees and joining pipe section Fig 18 09FC...

Page 20: ...nimum access is a recommendation Local code may require increased spacing 3 Chiller tube service must be done from control panel end for this arrangement See chiller certified drawings for details 09F...

Page 21: ...ote 2 09FC Control Panel NOTES 1 Allow 36 in for fan VFD access Verify 36 in meets local codes 2 EWT and LWT thermistors must be installed in the field Thermistors are supplied inside control panel Ad...

Page 22: ...y protection NOTE Do not use automobile antifreeze or any other fluid that is not approved for heat exchanger duty Only use appropriately in hibited glycols concentrated to provide adequate protection...

Page 23: ...Rt equals the equivalent pressure drop which R1 and R2 are the individual circuits Curves are for 30 Propylene Glycol PG Use multipliers for other fluids or brine concentration amounts Fig 25 09FC 02...

Page 24: ...FC Mode Bypass Mode GPM ft wc WARNING Electrical shock can cause personal injury and death Shut off all power to this equipment during installation There may be more than one disconnect switch Tag al...

Page 25: ...414 506 4 8 39 6 40 40 575 518 633 3 8 31 4 35 35 380 50 342 418 5 9 48 8 50 50 400 360 440 5 6 46 4 50 50 415 374 456 5 4 44 7 50 50 440 396 480 5 1 42 2 45 45 050 380 60 342 418 10 5 8 59 5 60 60 40...

Page 26: ...ng Manangement System CB Circuit Breaker EWT Entering Water Temperature FU Fuse FM Fan Motor GND Ground IN Thermistor or Dry Contact Input LWT Leaving Water Temperature OAT Outdoor Air Temperature R1...

Page 27: ...ocation of field power entry Be sure to seal entering power wire conduit per NEC requirements 3 Maximum field wire sizes allowed by lugs on fused discon nect are listed in Table 4 4 Terminals for fiel...

Page 28: ...NICATION OPTIONS The 09FC controls can support communication via BACnet ARC156 156 kbps or BACnet MS TP 9600 bps 76 8 kbps Wiring for BACnet communication is at Net Net and Shield at the top left of t...

Page 29: ...upper corner post bolts and slide the baffle un derneath the flange bolt Tighten the bolt Drill holes in the bottom of the flange of the baffle and mount with two screws to secure the bottom to the c...

Page 30: ...er The Carrier AppController is the heart of the control system It contains the operating software and controls the operation of the machine The CarrierAppController software continuously evalu ates i...

Page 31: ...uld be set to the upper position for thermistor IN 5 jumper should be on Fig 33 Carrier AppController Jumper Settings Carrier Equipment Touch Display Equipment touch is the user interface for the Carr...

Page 32: ...evel None Home Click on the right to navigate to Snapshot screen The HOME screen is the main screen Displays Leaving water temperature Outdoor air temperature Operating Mode Run Command Occupancy Pass...

Page 33: ...ic password level are visible Password Level None Properties Status This menu shows the status or value of the listed point Password Level None Properties Unit Configuration Cooling Lockout Default 50...

Page 34: ...0 F hi 245 Range 100 to 245 F Non Operational Comp This drives the Non Operational Component alarm The is the alarm offset value CWST This is a low limit alarm offset Reverse Load Water Flow This alar...

Page 35: ...lect the exclamation point in the top left of the screen from the Snapshot screen Trends NOTE Example screen shown Review trends for points that have trending enabled Access from the Snapshot screen b...

Page 36: ...36 Table 8 App Controller Screen Navigation cont SCREEN NAMES DISPLAY Properties Alarms Alarm Help 11 screens Password Level None...

Page 37: ...ller Screen Navigation cont SCREEN NAMES DISPLAY DETAILS Properties Alarms Alarm History Password Level None Properties Startup Wizard Password Level Factory Properties Startup Wizard Fan Speed PID Pa...

Page 38: ...38 Properties Startup Wizard Mixing Valve PID Password Level Factory Table 8 App Controller Screen Navigation cont SCREEN NAMES DISPLAY DETAILS...

Page 39: ...39 Table 8 App Controller Screen Navigation cont SCREEN NAMES DISPLAY Properties Startup Wizard Help 11 screens Password Level Factory...

Page 40: ...ion cont SCREEN NAMES DISPLAY DETAILS Properties ET System Password Level Factory Properties ET System Module Status Password Level Factory Properties ET System Alarms Password Level Factory Propertie...

Page 41: ...ctory Properties ET System Setup Module Setup Communication Password Level Factory Properties ET System Browser Password Level Factory Properties Touchscreen Setup Password Level Admin Table 8 App Con...

Page 42: ...60 VFD 1 400 50 VFD 1 400 60 VFD 1 415 50 VFD 1 460 60 VFD 1 575 60 VFD 1 050 380 50 VFD 1 VFD 2 380 60 VFD 1 VFD 2 400 50 VFD 1 VFD 2 400 60 VFD 1 VFD 2 415 50 VFD 1 VFD 2 460 60 VFD 1 VFD 2 575 60 V...

Page 43: ...Display Line 1 1 Small 0 21 Display Line 1 2 Small 0 22 Dis play Line 1 3 Small 0 23 Display Line 2 Large and 0 24 Dis play Line 3 Large The settings are accessed by selecting QUICK MENU Q3 Function...

Page 44: ...u key is used for programming all parameters These can be accessed immediately unless a password has been created via 0 60 Main Menu Password 0 61 Access to Main Menu without Password 0 65 Personal Me...

Page 45: ...0 0 3 02 Min Reference Hz 0 0 0 0 0 0 0 0 0 0 0 3 03 Max Reference Hz 60 60 60 60 60 60 60 60 60 60 60 3 13 Type Reference remote 1 1 1 1 1 0 0 0 0 0 0 3 15 Src Ref 1 analog input 1 1 1 1 1 1 1 1 1 1...

Page 46: ...pendent 30 4 45 6 60 8 45 6 30 4 45 6 45 6 53 2 53 2 60 8 60 8 Voltage 460V 60 of V s 2V 3V 4V 5V 6V 7V 8V Drive Designation FVFD 1 FVFD 1 FVFD 1 FVFD 1 FVFD 2 FVFD 1 FVFD 2 FVFD 1 FVFD 2 FVFD 1 FVFD...

Page 47: ...C link voltage drops below the undervoltage limit the frequency converter checks if a 24 V DC back up supply is connected If no 24 V DC back up supply is connected the frequency converter trips after...

Page 48: ...ient temperature too high Motor cables too long Incorrect airflow clearance above and below the frequency converter Blocked airflow around the frequency converter Damaged heat sink fan Dirty heat sink...

Page 49: ...the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation Check the power card 072 Alarm Emergency Stop A...

Page 50: ...10V Fan Initial Start Speed The speed that the module s fans are briefly run on initial startup D 100 R 0 to 100 Fan Minimum Speed The lowest speed that the module s fan is commanded when the fans va...

Page 51: ...ly Setpoint BAV chws_setpoint 3024 R W 15 75 F 44 Cooling Lockout Offset BAV oat_cl_lockout_offset 3027 R W 1 10 F 3 Cooling Lockout Temperature BAV oat_cl_lockout 9002 R W 20 80 F 50 Power Fail Resta...

Page 52: ...er allows the controller to transmit more messages while it has the token but it also increases the overall time it takes for the token to pass through the network For a router set this value to a hig...

Page 53: ...N OPERATIONAL COMPONENT ALARM If LWT Cooling Lockout Temp Cooling Lockout Offset Non Operational Component Alarm Offset and Unit is in free cooling mode for 3 minutes alarm contact will close valves w...

Page 54: ...a Sensor reading at controller is out of range Action Taken by Controller Alarm shown on display and alarm output energized Reset Method Automatic once reading is back in range Possible Causes Loose c...

Page 55: ...n controller health See table below Error Lights based on controller health See table below If Run LED shows And Error LED shows Status is 1 flash per second 1 flash per second alternating with the Ru...

Page 56: ...a handle inserted into the actuator See Fig 41 Fig 41 Manual Valve Operation Valve Linkage Adjustment This information will help return the valve linkage to the proper configuration to assure optimum...

Page 57: ...5 and 6 Replacing Thermistors EWT LWT Add a small amount of thermal conductive grease to the thermis tor well and end of probe For all probes tighten the retaining nut 1 4 turn past finger tight See F...

Page 58: ...046 55 13 8 628 57 14 8 232 59 15 7 857 61 16 7 500 63 17 7 152 64 18 6 841 66 19 6 536 68 20 6 247 70 21 5 972 72 22 5 710 73 23 5 461 75 24 5 225 77 25 5 000 79 26 4 786 81 27 4 582 82 28 4 389 84...

Page 59: ...point or boiling point of water using either voltage drop measured across thermistor at the J3 terminal by determining the resistance with unit shut down and thermistor disconnected from J3 Com pare...

Page 60: ...Avoid the use of coil brighteners acid cleaning prior to painting high pressure washers poor quality water for cleaning Totaline Indoor and Outdoor Coil Cleaner is non flammable hy poallergenic nonba...

Page 61: ...ded Routine Periodic clean water rinse especially in coastal and indus trial applications Check heat exchanger coils for debris clean as necessary Every 3 months Check all joints and valves for leaks...

Page 62: ...WIRING IS IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE NEC U S A FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES 3 WIRING FOR MAIN FIELD POWER SUPPLY MUST BE RATE 75 C...

Page 63: ...reset and current active alarms are displayed D Inactive R Inactive Active Point Name Description Default Range Cool Enable Enables or disables cooling operation D Enable R Disable Enable Lvg Wtr Temp...

Page 64: ...point is increased by this number of degrees when receiving a Demand Level 3 signal D 3 F R 0 to 10 F Point Name Description Default Range Leaving Water Temperature Alarm Low Leaving Water Temp Alarm...

Page 65: ...emperature value over the network The remote controller must have a network accessible outdoor air temperature sensor value D 999 F R 50 to 150 F System Control Setpoint Allows using another controlle...

Page 66: ...hysical sensor is wired and connected to the appropriate input channel of this controller Network A network sensor value provided to this controller Locked Value The controller s sensor input is manua...

Page 67: ...Num I O Type Sensor Actuator Type Min Max or Resolution I O configuration parameter for the points listed below Changing these parameters could cause improper control and or equip ment damage Use ext...

Page 68: ...ed The lowest speed that the module s fan is commanded when the fans variable frequency drive is enabled D 20 R 0 to 100 Fan Speed PID This BACnet Object calculates the amount of fan speed required to...

Page 69: ......

Page 70: ...es the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53090030 01 Printed in U S A Form 09FC 1SI Pg 70 3 21 Replace...

Page 71: ...es No 4 Electrical power wiring is installed properly Yes No 5 Unit is properly grounded Yes No 6 Electrical circuit protection has been sized and installed properly Yes No 7 All terminals are tight Y...

Page 72: ...than 2 Contact local utility for assistance 2 Verify flow rate Set unit in free cooling mode prior to setting flow rate Pressure entering unit _____ psig kPa Pressure leaving unit _____ psig kPa Unit...

Reviews:

Related manuals for 09FC020