33
Properties Menu
Navigates to
Property
pages
Login with one of the following passwords:
•
User level - type
user
•
Admin level - type
admin
- Unit configuration
- Sensor configuration
- Setpoints Password Level: None
- Alarm configuration
- Maintenance
- Service test
- Touchscreen setup
•
Factory level - type
Touch
- Startup wizard
- ET (Equipment Touch) system
NOTE:
Only the buttons that are authorized for a spe-
cific password level are visible.
Password Level: None
Properties/Status
This menu shows the status or value of the listed point.
Password Level: None
Properties /
Unit Configuration
Cooling Lockout
Default: 50
Range: –20 to 80°F
Does not allow free cooling mode if OAT is above this
temp.
Cooling Lockout Offset
Default: 3
Range: 1 to 10°F
Increases the Lockout setpoint by the value of the setting.
Password Level: Admin
Properties /
Sensor Calibration
Allows calibration of sensor.
Default: 0
Range: –10 to 10°F
Password Level: Admin
Table 8 —
App Controller Screen Navigation (cont)
SCREEN NAMES
DISPLAY
DETAILS