![CARLO GAVAZZI LD30 BI10BP IO Series Manual Download Page 32](http://html1.mh-extra.com/html/carlo-gavazzi/ld30-bi10bp-io-series/ld30-bi10bp-io-series_manual_2558585032.webp)
Rev.00 - 01.2020 | LD30 IO-Link manual ENG | © 2020 |
CARLO GAVAZZI Industri
32
EN
7.2.5. Diagnostic parameters
Parameter Name
Index Dec
(Hex)
Access
Default value
Data range
Data Type
Length
Operating Hours
201 (0xC9)
RO
0
0 ... 2 147 483 647 [h]
IntegerT
32 bit
Number of Power Cycles
202 (0xCA)
RO
0
0 ... 2 147 483 647
IntegerT
32 bit
Maximum temperature
– All time high
203 (0xCB)
RO
0
-50 ... 150 [°C]
IntegerT
16 bit
Minimum temperature
- All time low
204 (0xCC)
RO
0
-50 ... 150 [°C]
IntegerT
16 bit
Maximum temperature since
power-up
205 (0xCD)
RO
-
-50 ... 150 [°C]
IntegerT
16 bit
Minimum temperature since
power-up
206 (0xCE)
RO
-
-50 ... 150 [°C]
IntegerT
16 bit
Current temperature
207 (0xCF)
RO
-
-50 ... 150 [°C]
IntegerT
16 bit
Detection counter SSC1
210 (0xD2)
RO
-
0 ... 2 147 483 647
IntegerT
32 bit
Minutes above Maximum
Temperature
211 (0xD3)
RO
-
0 ... 2 147 483 647 [min]
IntegerT
32 bit
Minutes below Minimum
Temperature
212 (0xD4)
RO
-
0 ... 2 147 483 647 [min]
IntegerT
32 bit
Download counter
214 (0xD6)
RO
0
0 ... 65 536
UIntegerT
16 bit
Parameter Name
Index Dec
(Hex)
Access
Default value
Data range
Data Type
Length
SSC1 Hyst Mode
80 (0x50)
R/W
1=Auto
0=Manuel
1=Auto
Uinteger
8 bit
SSC1 Auto hysteresis value
81 (0x51)
-
-
-
RecordT
2x16 bit
AutoHysteresisValueSP1
1 (0x01)
R
-
1 ... 1100 [mm]
Uinteger
16 bit
AutoHysteresisValueSP2
2 (0x02)
R
-
1 ... 1100 [mm]
Uinteger
16 bit
7.2.4. Sensor specific adjustable parameters (continued)