2.4.7. Common Siren
• Function: Common output of ISA-, Smoke-, Intruder- and Water alarm
• Application: Output of several alarms on one siren in addition to or in replacement of alarm
system specific sirens
• Select with mouse (“Common Siren”)
Description
The Common Siren offers the possibility of transmitting the alarms of all alarm systems on one channel. The
alarm of the siren output behaves in the same way as the individual alarm sirens. If several alarms are on, they
are indicated wtih the following priority:
1. Smoke alarm
2. Intruder alarm
3. Water alarm
4. ISA alarm
The operation of the common siren is independent of whether a siren was configured in the individual alarm
system.
Note:
The signal time entered in the Common siren is automatically adopted by the individual sirens. This also
applies to reversed function.
If an alarm has been acknowledged or reset, the Master Generator also resets the signal of the common siren.
Parameters:
Parameter
Description
Common siren
Channel function
Here you select one or several alarm systems whose alarm will also activate this
siren.
Siren time
Here you enter the max. time for which this siren is to remain activated. The value
can lie between 0 min and 60 min.
Application Example
Task:
In a commercial building, different alarm systems (smoke, water, ISA and Intruder) are to acti-
vate the siren mounted outside.
Solution:
The alarm systems described in the previous examples are used. The relay for the outdoor siren
is configured for address I1. The siren time of each connected alarm is configured.