Object
Function
Channel
In-/outputs
Alarm switch
Alarm contact
A1..A8
Push button input
Acknowledgement
B1
Push button input
Reset
B2
Push button input
Lamp test
B3
Semiconductor output LED for source in-
A1..A8
cation on a panel
Relay output
Alarm siren
B4
Configuration of Master Generator
ISA alarm:
Alarm sources
A1.. A8
Passive detector
ISA alarm:
Alarm
B1
Acknowledgement
acknowledgement
ISA alarm: Reset
Alarm reset
B2
ISA alarm: Lamp test
Activation of all
B3
LEDs on the panel
ISA alarm: Alarm siren Alarm sounding
B4
Application Example
Task:
In a chemical factory, eight laboratories are to be provided with alarm switches. Upon activation
of an alarm button, the fire staff of the factory is informed via a siren. When the fire staff has
acknowledged the alarm, they go to the lab where the alarm was started.
Solution:
The alarm switches are coded for channels A1 to A8. The source of the alarm is indicated on a
panel whose LED is activated via a mimic display. The addresses correspond to those of the
alarm contacts. The fire staff uses a button coded for address B1 to acknowledge the alarms.
The alarm is reset through a reset button coded for address B2. The alarm is sounded by
means of a horn activated through a relay output of DSM 8 coded for address B4.