G 3800 X015 Configuration Software
October 2002
G 3800 X015 Configuration Software
October 2002
G 3800 X015 Configuration Software
October 2002
Parameter
Description
Operation mode
Standard:
This setting means that activation of the alarm system takes place upon prior
release by the reset button. This entails that the object “Reset” must be config-
ured.
Auto reset:
With this setting, the system activates itself automatically upon acknowledge-
ment, when all passive and active detectors are in their “normal” position (in
which they do not trigger off alarms)
Note:
Operation mode can be selected for any object of the ISA alarm - but
applies to the entire system. If the object “Reset” is selected to include a reset
button, the system assumes that the operation mode “Standard” is to be select-
ed. Simultaneously, the option operation mode is deactivated and can only be re-
activated by unclicking the object “Reset”.
If “Auto reset” is selected, the system prevents configuration of the “Reset”
object.
Passive detector
Disable address
Enter an address (A1..P8) or a flag (W1..Z8) whose activation (“1”-signal) will leave
out the Passive detector function of the monitoring system whereby it cannot
trigger off any further alarms.
On-delay
Enter a time value in seconds (0..255) for which the alarm signal is delayed upon
activation of the alarm contact.
Active detector
Disable address
Enter an address (A1..P8) or a flag (W1..Z8) whose activation (“1”-signal) will leave
out the Passive detector function of the monitoring system whereby it cannot
trigger off any further alarms.
If a contact is activated during resetting, the system triggers off a new alarm
When this object is configured, the operation mode “Standard” is automatically
selected.
Lamp test:
This object makes it possible to test the function of lamps indicating the status of
the alarm contacts. All alarm channels are activated upon actuation of the lamp
test button.
Alarm siren:
The alarm siren indicates the occurence of an alarm. The channel configured for
this object can be used for alarm output on a random number of output modules.
It usually activates a relay output switching a siren.
Parameters: