Parameter
Description
Alarm siren
Siren time
With this setting you determine how long the alarm output is to remain activated
when an alarm occurs. The value can lie between 0 and 60 min.
The system becomes alert again, when the siren time has elapsed and no alarm
contact is activated any more.
A value entered here is automatically adopted by the Common siren.
Flash when Alarm
By ticking off this checkbox, the option Flashing Channels allows you to select
which channels are to flash in case of alarm as well as their flash interval (see
below). The alarm siren channel is thereby constantly switched on.
Note.:
The options Flash Interval and Flashing Channels only appear when the
option Flash when Alarm has been selected.
Flash Interval
Here you can enter the switch on/off time span of the flashing alarm signals. The
option “Flash when Alarm” must be switches on.
The value can lie between 0 and 60 s. Please note that flash intervals below 2
seconds may turn out inaccurately because of the cycle time. When the value 0 is
entered, flashing takes place at the fastest possible rate.
Flashing Channels
By mouse-click on this option, an address matrix appears in which you can select
the channels which are to flash upon an alarm. This option is only available when
the option Flash when Alarm has been selected.
Alarm signal
Alarm signal delay
With this setting you can determine the time which is to elapse from the alarm
siren is activated till the alarm signal is activated. The value can lie between 0 and
10 min.