GUN OUTPUTS (STATUS BITS)
GUN OUTPUTS (VALUE)
Actual Flow Rate
This is the actual flow rate in cc’s/minute for the Gun.
Fault
This output is energized anytime a fault condition is
recognized by the software. Even if the fault is disabled
(known as a soft-fault) on the CONFIG ALARMS screen,
this bit will be true as long as the condition persists. Fluid
flow will not be halted when this bit is true unless it is
configured to do so on the CONFIG ALARMS screen. If
it is configured to be a hard-fault, this bit and the Spray
Shutdown bit will both be true and the system will stop
spraying (see Spray Shutdown, below).
Gun Status Flags
Bit #
TABLE 1.2 - GUN STATUS
FLAGS WORD
0 Fault
1 Run
2
Spray Shutdown
3
Flush Request
4
Motor On (Master)
5
Motor On (Slave)
6
7
8
9
10
11
12
13
14
15
Run
This bit is true if the gun is configured properly, a good job
number has been loaded, and the gun has been placed
in Run Mode or the Volume Fill Mode. This bit is false if a
fault occurs, if it is Halted, or in the Ready state.
Spray Shutdown
This bit is true if a fault condition exists and the specific
fault that exists is enabled on the CONFIG ALARMS
screen (turned on). This indicates that the flow of fluid
from the fluid panel has been stopped as the result of a
detected fault condition.
Flush Request
This bit is true when the pot-life timer has expired. (For
more information, see “Mixed Volume and Pot-Life Timer”
in the “Operation’s Manual”.)
Motor On (Master, Slave)
The Motor On bit is set true by the software when it wants
the motor amp to be active. There is a bit provided for the
Gun’s Master Channel and a second bit provided for the
the Gun’s Slave channel. As long as this bit is true and
the motor amplifier is not faulted, the pump will be held
rigid in place by the motor amplifier. If this bit is false, the
pump is allowed to free-wheel.
LN-9418-01-R0 (08/2018)
12 / 17
www.carlisleft.com
EN
OUTPUT