background image

4.  Adjustment and Verification

Perform combustion test

  COMBUSTION MUST BE VERIFIED WITH THE (OPTIONAL) 

BURNER COVER IN PLACE — 

 

Remove the burner cover if installed. Set up and adjust the 
burner using the following procedure. Replace the burner cover, 
allow the burner/appliance to run at least 15 minutes, then 
check combustion again. Readjust the burner is necessary. 
The CO

2

 will increase when the cover is put on, particularly 

if combustion air is piped to the burner.

 

If air is ducted to an (optional) air adapter, combustion must 
be set based on the air inlet temperature. Air temperature 
variations will change how much air enters the burner, so the 
combustion must be set to anticipate the variations. Follow 
the guidelines below.

Adjust burner using test instruments

1.

  Operate burner for 15 minutes before making final adjustments using 

test equipment.

2.

  Check for leaks in fuel  piping.

 

Inspect fuel piping system for leaks. Repair any leaks to avoid 
fire hazard from oil leakage or combustion problems due to 
air infiltration into oil.

3.

  Inspect flame

•  Look at flame through appliance combustion chamber observation 

port. The flame should be well-defined and should not impinge on 
any appliance surface. (If you make air or gas pressure changes 
later, inspect the flame again.)

 

Do not attempt to confirm combustion simply by inspecting 
the flame visually. You must use combustion test instruments. 
Failure to properly verify/adjust combustion could allow unsafe 
operation of the burner, resulting in severe personal injury, 
death or substantial property damage.

4.

  Insert test probe into vent to sample flue products.

 

Heating units designed for natural draft operation are normally 
set for a slightly negative pressure, usually -0.01 to -0.02 
inches w.c. draft at the combustion chamber test port. Ap-
pliances designed for forced draft (positive pressure in the 
chamber) must be air-tight to prevent exfiltration of harmful 
combustion products. Failure to properly set draft for the 
appliance could result in severe personal injury or death.

5.  Use combustion test equipment to verify that the burner is properly 

set up for your installation. 

Appliances with positive pressure in the 

chamber may require a wider air opening. See appliance instructions 
for details. Verify/adjust settings by testing with instruments.
•  With the burner equipped with the correct positioning bar, oil nozzle 

and initial air band setting, the flue products will usually contain 
between 11½% and 12½% CO

2

 (5.9% and 3.8% O

2

) and zero 

smoke. (Based on air inlet temperature of 70°F — see Table 4 
for the proper values at other air temperatures for burners with 
ducted combustion air.)

•  Depending on length of air piping (when used) and on air tempera-

ture, CO

2

 may change one per cent or more with the cover in place.

•  Check smoke. It should be zero on the Bacharach scale.
•  Set the appliance flue damper or barometric draft regulator so the 

draft or pressure in the vent complies with the appliance manu-
facturer’s instructions.

Re-install (optional) burner cover and check combustion again

1.

  Allow the burner to operate with the cover on for at least 15 minutes. 

(Insert a temperature probe to measure incoming combustion air 
tempeature if combustion air is ducted to the burner.)
•  Retest CO

2

 (or O

2

) and smoke again. The values will change when 

the cover is installed. Depending on length of air piping and on 
air temperature, CO

2

 may change one per cent or more with the 

cover in place.

•  Make sure the CO

(or O

2

) values are in the range given in Table 4 

for the inlet air temperature measured. IF NOT, remove the cover 
and adjust the air band more open to decrease CO

2

 (increase O

2

or close the air band slightly to increase CO

2

 (decrease O

2

).

•  Tighten air band clamping screw.

 

All installations should be checked after one to two weeks of 
operation to ensure the appliance/burner units are operating 
correctly.

Table 4 

Burners using inside air for combustion – 

Use “65°F or higher” row in table below. 
Burners with ducted combustion air – 

MEASURE incoming combustion air temperature 

and set the CO

2

 (or O

2

) using the following chart:

Incoming combustion  

air temperature

during setup

CO

2

 min CO

2

 max

O

2

 max

O

2

 min

–20°F to 0°F

10.2%

11.0%

7.0%

5.8%

5°F to 30°F

11.0%

11.5%

5.8%

5.5%

35°F to 60°F

11.5%

12.2%

5.5%

4.2%

65°F or higher

12.0%

12.5%

4.6%

3.9%

MN66-3P  090721

– 11 –

Carlin Select EZ-66 Oil/Bio Fuel Burner Instruction Manual

Summary of Contents for EZ-66

Page 1: ...NORA recommends single pipe oil systems and high quality filtration for all fuel types This should in clude at least a 10 micron Spin on filter Double filtration provides even greater assurance clean...

Page 2: ...ke the user aware of all potential hazards and perform the training outlined below Train the user To properly operate the burner appliance per this manual and the appliance instructions see User s inf...

Page 3: ...for the Installation of Oil Burning Equipment ANSI NFPA 70 National Electrical Code and all applicable local codes Canadian installations Burner appliance installations in Canada must comply with the...

Page 4: ...uver obstruction If you can t find the louver reduction for the grilles used assume free area is 20 of total for wood louvers or 60 of total for metal louvers Screens can be no finer than inch mesh an...

Page 5: ...ther guidelines of this manual and the appliance manual Welded flange burners 1 Verify the bolt pattern on the appliance chamber matches the flange pattern 2 Verify the insertion depth UTL matches the...

Page 6: ...ssary to ensure reliable contact with the electrodes Install nozzle check electrodes 1 Loosen the clamp screw on the retention ring assembly see Figure 5 page 7 Slide the retention ring assembly off o...

Page 7: ...the lead edge of the slide aligns to the number given in Table 2 page 8 Lock in place by first tightening the oil line thumb nut then tightening the locking screw Air shutter 1 The air shutter is fix...

Page 8: ...d Air band Head Air band Head Air band Head GPH 100 PSI open Dim A open Dim A open Dim A open Dim A 15 20 0 15 0 15 20 0 15 20 0 15 20 0 20 0 20 0 1 25 1 70 2 2 15 2 60 4 0 4 75 2 3 20 2 3 65 5 5 4 5...

Page 9: ...oil has higher viscosity which can affect atomization ignition combustion and fuel consumption The nozzle line heater avoids this problem by heating the nozzle line oil to between 120 F and 130 F resu...

Page 10: ...d sized designed correctly o Oil tank has oil and oil line valves are open o Wiring installed per burner appliance instructions o Burner appliance and all components inspected and in good condition 3...

Page 11: ...he burner is properly set up for your installation Appliances with positive pressure in the chamber may require a wider air opening See appliance instructions for details Verify adjust settings by tes...

Page 12: ...ance flue damper or barometric draft regulator so the draft or pressure in the vent complies with the appliance manufacturer s instruc tions Heating units designed for natural draft operation are norm...

Page 13: ...inants in the vicinity of the burner appliance 4 Adjustment and Verification cont Perform the following This burner must be started and serviced at least annually by a qualified service technician Fai...

Page 14: ...nce perform a complete operational test after reassembly to verify the burner operates correctly Failure to verify operation could result in severe personal injury death or substantial property damage...

Page 15: ...pling 9 98109 Air Band Shutter 10 51593S Head positioning slide bar kit 11 51854 Combustion Head Assembly 7 12 62885A Thumb Nut Nozzle Line Item Part Desctiption 13 60103 Electrode Bracket 14 1440700K...

Page 16: ...n a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating oil and bio blends not exceeding B20 U S Only ASTM D396 EZ 66 Oil Bio Fuel Burner User care and maintenance...

Reviews: